| Plan Review Notes For Permit 07120434 |
| Permit Number |
07120434 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-03-07 08:50:16 | ****************PROVISO**************** | | | NOTE: REVISION REQUIRED WITH THE FOLLOWING INFORMATION | | | ON SHEET P101: | | | | | | A} A 4" AERATOR FITTING IS REQUIRED FOR THE RELOCATED | | | WASHING MACHINE AND NEW MACERATING UNIT. | | | | | | B} THE 1-1/2" VENT FROM THE TOP OF THE MACERATING UNIT | | | COLLECTION TANK SHALL TIE INTO THE 2" VENT 6" ABOVE THE | | | WASHING MACHINE STANDPIPE INLET. | | | | | | C} THE 2" VENT SHALL BE REQUIRED TO TIE BACK INTO THE | | | 4" SOIL STACK A MINIMUM OF 36" ABOVE THE NEW 4" AERATOR | | | FITTING FOR THE WASHING MACHINE AND MACERATING UNIT. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|