| 2008-02-14 14:26:26 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED 2ND TIME: |
| | |
| | **PREVIOUS REVIEW COMMENTS** |
| | |
| | 1. **OK, COMMENT ADDRESSED** |
| | |
| | 2. ** OK,COMMENT ADDRESSED** |
| | |
| | 3. **OK, COMMENT ADDRESSED** |
| | |
| | 4. **OK, COMMENT ADDRESSED** |
| | |
| | 5. **NO COMMENT RESPONSE, NEW COMMENTS TO FOLLOW WITH |
| | THE REDESIGNED SYSTEM ADDING THE MACERATING UNIT** |
| | |
| | PLEASE CLARIFY HOW THE NEW WATER CLOSET WITH THE NEW |
| | AERATOR FITTING WILL BE INSTALLED TO MEET THE ROUGH IN |
| | REQUIREMENTS OF THE SPECIFIED KOHLER MODEL NUMBER |
| | K-3554 WHICH IS 4" A.F.F. AND HOW THE AERATOR FITTING |
| | WILL BE FIRE STOPPED. PLEASE REFERENCE THE AERATOR |
| | FITTING CUT SHEET WITH ROUGH-IN DIMENSIONS ATTACHED TO |
| | THESE COMMENTS. PER SECTION *106.1.1, INFORMATION ON |
| | CONSTRUCTION DOCUMENTS AND SECTION *713, FIRE RESISTANT |
| | JOINT SYSTEMS. |
| | |
| | 6. **NO COMMENT RESPONSE, AERATOR FITTING REQUIRED FOR |
| | THE WASHINGMACHINE AND MACERATING UNIT** |
| | |
| | NOTE: DETAIL REQUIRED ON HOW AERATOR FITTING WILL BE |
| | SUPPORTED. PER SECTION *308 PIPING SUPPORT. |
| | |
| | 7. **OK, COMMENT ADDRESSED** |
| | |
| | **THE FOLLOWING ARE NEW COMMENTS FOR THE REDESIGNED |
| | PLUMBING SYSTEM WITH THE ADDITION OF THE MACERATING |
| | UNIT** |
| | |
| | 8. SHEET P101 IS MISSING THE CERTIFICATE OF |
| | AUTHORIZTION NUMBER FOR TEELE & ASSOCIATES. PER FLORIDA |
| | ADMINISTRATIVE CODE (2) 61G15-23.002 AND FLORIDA |
| | STATUTES 471.023 (2). PLEASE REFERENCE CERTIFICATE OF |
| | AUTHORIZTION NUMBER FOR TEELE & ASSOCIATES FROM DBPR |
| | WEB SITE ATTACHED TO THESE PLUMBING COMMENTS. |
| | |
| | 9. PER CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION |
| | 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION DOCUMENTS, |
| | SPECIAL INSPECTION AND STRUCTURAL OBSERVATION PROGRAMS, |
| | AND OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS |
| | WITH EACH APPLICATION FOR A PERMIT. |
| | **ONLY ONE COPY OF THE MANUFACTURE'R SPECIFICATION |
| | SHEETS FOR THE MACERATING UNIT WAS SUBMITTED. TWO |
| | COMPLETE COPIES OF SPECIFICATION SHEETS ARE REQUIRED. |
| | |
| | 10. SHEET P101 SANITARY RISER: A} A 4" AERATOR FITTING |
| | IS REQUIRED FOR THE WASHING MACHINE AND MACERATING |
| | UNIT. BOTH THE WASHING MACHINE AND MACERATING UNIT CAN |
| | DRAIN INTO THE SAME AERATOR FITTING. PER CONINE |
| | MANUFACTURING DESIGN MANUAL #802. |
| | B} THE 1-1/2"VENT FROM THE COLLECTION TANK OF THE |
| | MACERATING UNIT SHALL BE REQUIRED TO TIE BACK INTO THE |
| | 4" STACK36" ABOVE THE AERATOR FITTING AND AN 1-1/2 |
| | VENT IS REQUIRED FOR THE 2" LINE FROM THE DISCHARGE OF |
| | THE MACERATING UNIT. |
| | NOTE: PER THE SUBMITTED MANUFACTURER SPECIFICATION |
| | PAGE #5 STATES, "WARNING: DO NOT USE AN AIR ADMITTANCE |
| | VALVE (CHEATER, MECHANICAL VENTS), WHICH ARE ONE-WAY |
| | VALVES. THE AIR PRESSUR IN AND OUTSIDE THE MACERATING |
| | PUMP UNIT MUST REMAIN CONSTANT." PER CONINE |
| | MANUFACTURING DESIGN MANUAL #802. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |