Plan Review Notes
Plan Review Notes For Permit 07120434
Permit Number 07120434
Review Stop P
Sequence Number 2
Notes
Date Text
2008-02-14 14:26:26PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 **PREVIOUS REVIEW COMMENTS**
  
 1. **OK, COMMENT ADDRESSED**
  
 2. ** OK,COMMENT ADDRESSED**
  
 3. **OK, COMMENT ADDRESSED**
  
 4. **OK, COMMENT ADDRESSED**
  
 5. **NO COMMENT RESPONSE, NEW COMMENTS TO FOLLOW WITH
 THE REDESIGNED SYSTEM ADDING THE MACERATING UNIT**
  
 PLEASE CLARIFY HOW THE NEW WATER CLOSET WITH THE NEW
 AERATOR FITTING WILL BE INSTALLED TO MEET THE ROUGH IN
 REQUIREMENTS OF THE SPECIFIED KOHLER MODEL NUMBER
 K-3554 WHICH IS 4" A.F.F. AND HOW THE AERATOR FITTING
 WILL BE FIRE STOPPED. PLEASE REFERENCE THE AERATOR
 FITTING CUT SHEET WITH ROUGH-IN DIMENSIONS ATTACHED TO
 THESE COMMENTS. PER SECTION *106.1.1, INFORMATION ON
 CONSTRUCTION DOCUMENTS AND SECTION *713, FIRE RESISTANT
 JOINT SYSTEMS.
  
 6. **NO COMMENT RESPONSE, AERATOR FITTING REQUIRED FOR
 THE WASHINGMACHINE AND MACERATING UNIT**
  
 NOTE: DETAIL REQUIRED ON HOW AERATOR FITTING WILL BE
 SUPPORTED. PER SECTION *308 PIPING SUPPORT.
  
 7. **OK, COMMENT ADDRESSED**
  
 **THE FOLLOWING ARE NEW COMMENTS FOR THE REDESIGNED
 PLUMBING SYSTEM WITH THE ADDITION OF THE MACERATING
 UNIT**
  
 8. SHEET P101 IS MISSING THE CERTIFICATE OF
 AUTHORIZTION NUMBER FOR TEELE & ASSOCIATES. PER FLORIDA
 ADMINISTRATIVE CODE (2) 61G15-23.002 AND FLORIDA
 STATUTES 471.023 (2). PLEASE REFERENCE CERTIFICATE OF
 AUTHORIZTION NUMBER FOR TEELE & ASSOCIATES FROM DBPR
 WEB SITE ATTACHED TO THESE PLUMBING COMMENTS.
  
 9. PER CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION
 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION DOCUMENTS,
 SPECIAL INSPECTION AND STRUCTURAL OBSERVATION PROGRAMS,
 AND OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS
 WITH EACH APPLICATION FOR A PERMIT.
 **ONLY ONE COPY OF THE MANUFACTURE'R SPECIFICATION
 SHEETS FOR THE MACERATING UNIT WAS SUBMITTED. TWO
 COMPLETE COPIES OF SPECIFICATION SHEETS ARE REQUIRED.
  
 10. SHEET P101 SANITARY RISER: A} A 4" AERATOR FITTING
 IS REQUIRED FOR THE WASHING MACHINE AND MACERATING
 UNIT. BOTH THE WASHING MACHINE AND MACERATING UNIT CAN
 DRAIN INTO THE SAME AERATOR FITTING. PER CONINE
 MANUFACTURING DESIGN MANUAL #802.
 B} THE 1-1/2"VENT FROM THE COLLECTION TANK OF THE
 MACERATING UNIT SHALL BE REQUIRED TO TIE BACK INTO THE
 4" STACK36" ABOVE THE AERATOR FITTING AND AN 1-1/2
 VENT IS REQUIRED FOR THE 2" LINE FROM THE DISCHARGE OF
 THE MACERATING UNIT.
 NOTE: PER THE SUBMITTED MANUFACTURER SPECIFICATION
 PAGE #5 STATES, "WARNING: DO NOT USE AN AIR ADMITTANCE
 VALVE (CHEATER, MECHANICAL VENTS), WHICH ARE ONE-WAY
 VALVES. THE AIR PRESSUR IN AND OUTSIDE THE MACERATING
 PUMP UNIT MUST REMAIN CONSTANT." PER CONINE
 MANUFACTURING DESIGN MANUAL #802.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]