| 2007-12-26 14:54:02 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET P101, ISOMETRIC SANITARY RISER DIAGRAM: |
| | CLEARLY INDICATE ALL PIPE SIZES PER THE FOLLOWING |
| | SECTION *106.3.5.1.3, PLUMBING AND SOVENT DESIGN MANUAL |
| | #802. |
| | |
| | A} SOVENT STACK = 4". |
| | |
| | B} AREATOR BOX (NEW & EXISTING) = 4" X 3". |
| | |
| | C} RELOCTED WASHING MACHINE HORIZONTAL BRANCH = 3". |
| | |
| | D} RELOCATED WASHING MACHINE VERTICAL DROP = 3". |
| | |
| | E} RELOCATED WASHING MACHINE TRAP = 2". |
| | |
| | 2. SHEET P101, EXISTING FLOOR PLAN DETAIL: PLEASE |
| | CORRECT/ADD THE FOLLOWING PER SECTION *106.1.1, |
| | INFORMATION ON CONSTRUCTION DOCUMENTS AND SECTION |
| | *106.1.2, ADDITIONAL DATA. |
| | |
| | A} PLEASE CORRECT THE SPELLING OF "SOLVENT" TO |
| | "SOVENT". |
| | |
| | B} PLEASE ADD THE FOLLOWING TO THE EXISTING SINK |
| | LOCATION. "EXISTING SOVENT STACK". |
| | |
| | 3. SHEET P101, NEW FLOOR PLAN DETAIL: WHERE THE |
| | "EXTEND EXISTING 2" BRANCH" IS LOCATED IS THAT |
| | RELOCATED FIXTURE A SINK OR A LAVATORY? PLEASE CLEARLY |
| | IDENTIFY ALL FIXTURES. PER SECTION *106.1.1, |
| | INFORMATION ON CONSTRUCTION DOCUMENTS AND SECTION |
| | *106.1.2, ADDITIONAL DATA. |
| | |
| | 4. SHEET P101, NEW FLOOR PLAN DETAIL: WHERE EXISTING |
| | WASHING MACHINE WASTE IS LOCATED IT STATES "CAP |
| | EXISTING AT WALL". PER *704.5 DEAD ENDS.IN THE REMOVAL |
| | OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE |
| | PROHIBITED. PLEASE CLEARLY INDICATE THIS ON THE |
| | RESUBMITTAL. |
| | |
| | 5. PLEASE CLARIFY HOW THE NEW WATER CLOSET WITH THE |
| | NEW AERATOR FITTING WILL BE INSTALLED TO MEET THE ROUGH |
| | IN REQUIREMENTS OF THE SPECIFIED KOHLER MODEL NUMBER |
| | K-3554 WHICH IS 4" A.F.F. AND HOW THE AERATOR FITTING |
| | WILL BE FIRE STOPPED. PLEASE REFERENCE THE AERATOR |
| | FITTING CUT SHEET WITH ROUGH-IN DIMENSIONS ATTACHED TO |
| | THESE COMMENTS. PER SECTION *106.1.1, INFORMATION ON |
| | CONSTRUCTION DOCUMENTS AND SECTION *713, FIRE RESISTANT |
| | JOINT SYSTEMS. |
| | |
| | 6. NOTE: DETAIL REQUIRED ON HOW AERATOR FITTING WILL |
| | BE SUPPORTED. PER SECTION *308 PIPING SUPPORT. |
| | |
| | 7. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3, |
| | PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS |
| | REQUIRED FOR THE PROPOSED NEW AND RELOCATED WORK FOR |
| | BOTH THE HOT AND COLD WATER INDICATING THE PIPE SIZES, |
| | VALVE LOCATIONS, AND LOCATION OF THE WATER-HAMMER |
| | ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED |
| | (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS) |
| | **604.9. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |