Plan Review Notes
Plan Review Notes For Permit 07120434
Permit Number 07120434
Review Stop P
Sequence Number 1
Notes
Date Text
2007-12-26 14:54:02PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P101, ISOMETRIC SANITARY RISER DIAGRAM:
 CLEARLY INDICATE ALL PIPE SIZES PER THE FOLLOWING
 SECTION *106.3.5.1.3, PLUMBING AND SOVENT DESIGN MANUAL
 #802.
  
 A} SOVENT STACK = 4".
  
 B} AREATOR BOX (NEW & EXISTING) = 4" X 3".
  
 C} RELOCTED WASHING MACHINE HORIZONTAL BRANCH = 3".
  
 D} RELOCATED WASHING MACHINE VERTICAL DROP = 3".
  
 E} RELOCATED WASHING MACHINE TRAP = 2".
  
 2. SHEET P101, EXISTING FLOOR PLAN DETAIL: PLEASE
 CORRECT/ADD THE FOLLOWING PER SECTION *106.1.1,
 INFORMATION ON CONSTRUCTION DOCUMENTS AND SECTION
 *106.1.2, ADDITIONAL DATA.
  
 A} PLEASE CORRECT THE SPELLING OF "SOLVENT" TO
 "SOVENT".
  
 B} PLEASE ADD THE FOLLOWING TO THE EXISTING SINK
 LOCATION. "EXISTING SOVENT STACK".
  
 3. SHEET P101, NEW FLOOR PLAN DETAIL: WHERE THE
 "EXTEND EXISTING 2" BRANCH" IS LOCATED IS THAT
 RELOCATED FIXTURE A SINK OR A LAVATORY? PLEASE CLEARLY
 IDENTIFY ALL FIXTURES. PER SECTION *106.1.1,
 INFORMATION ON CONSTRUCTION DOCUMENTS AND SECTION
 *106.1.2, ADDITIONAL DATA.
  
 4. SHEET P101, NEW FLOOR PLAN DETAIL: WHERE EXISTING
 WASHING MACHINE WASTE IS LOCATED IT STATES "CAP
 EXISTING AT WALL". PER *704.5 DEAD ENDS.IN THE REMOVAL
 OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. PLEASE CLEARLY INDICATE THIS ON THE
 RESUBMITTAL.
  
 5. PLEASE CLARIFY HOW THE NEW WATER CLOSET WITH THE
 NEW AERATOR FITTING WILL BE INSTALLED TO MEET THE ROUGH
 IN REQUIREMENTS OF THE SPECIFIED KOHLER MODEL NUMBER
 K-3554 WHICH IS 4" A.F.F. AND HOW THE AERATOR FITTING
 WILL BE FIRE STOPPED. PLEASE REFERENCE THE AERATOR
 FITTING CUT SHEET WITH ROUGH-IN DIMENSIONS ATTACHED TO
 THESE COMMENTS. PER SECTION *106.1.1, INFORMATION ON
 CONSTRUCTION DOCUMENTS AND SECTION *713, FIRE RESISTANT
 JOINT SYSTEMS.
  
 6. NOTE: DETAIL REQUIRED ON HOW AERATOR FITTING WILL
 BE SUPPORTED. PER SECTION *308 PIPING SUPPORT.
  
 7. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS
 REQUIRED FOR THE PROPOSED NEW AND RELOCATED WORK FOR
 BOTH THE HOT AND COLD WATER INDICATING THE PIPE SIZES,
 VALVE LOCATIONS, AND LOCATION OF THE WATER-HAMMER
 ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED
 (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS)
 **604.9.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]