| Plan Review Notes For Permit 07120434 |
| Permit Number |
07120434 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-22 15:34:58 | REDLINED PLANS. | | | | | | PLANS DO NOT SHOW ANY NEW CIRCUITS AND ALL ARE EXISTING | | | OR EXISTING TO BE RE-LOCATED. PLEASE SUBMIT A REVISED | | | PANEL SCHEDULE SHOWING ANY *NEW* CIRCUITS SHOWING OVER | | | CURRENT PROTECTION, AND CONDUCTOR SIZES IF NEW ARE | | | INSTALLED. NO INFORMATION IS NEEDED AT THIS TIME. | | | 408.4, 240.4, 310.16 | | | FBC 106.3.5.1.2, 106.1.2 |
|