| 2008-04-03 14:27:42 | ** DENIED 3RD REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE COMPLIANCE FOR LIGHTING PERFORMANCE |
| | CALCULATIONS STILL NEEDS TO BE MET. PLEASE SEE PLANS |
| | STILL SHOW METHOD *C* CALCULATIONS ON SHEETS E-0.3 AND |
| | E-0.4. THESE NEED TO BE SUBMITTED SEPARATELY. THESE |
| | NEED TO SHOW ALL LIGHTING AS SHOWN ON PLANS. PLEASE SEE |
| | THE NEW LIGHTING LEVELS PRINTED ON TABLE ON SHEET E-0.1 |
| | NOW CONTAINS LOWER DESIGN WATTAGE THAN THE DESIGN |
| | WATTAGE ON THE TWO SHEETS ABOVE. |
| | THE NEW LIGHTING PLANS SUBMITTED NOW HAVE NUMEROUS |
| | FIXTURES THAT WERE ON PREVIOUS PLANS NOW DELETED FROM |
| | NEW PLANS YET THE WATTAGE HAS ONLY DECREASED A SMALL |
| | AMOUNT FROM THE INFORMATION PREVIOUSLY SUBMITTED. |
| | PLEASE SEE BOTH THE EXISTING SHEETS LEFT IN SETS AND |
| | THE NEW INFORMATION AND PLEASE BE SURE TO COORDINATE |
| | ALL. |
| | PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2. |
| | |
| | 2) NOTE: PLEASE SEE THE ADDRESS OF THE PROJECT FOR |
| | SUITE/UNIT NUMBER STILL NEEDS TO BE DETERMINED. PLANS |
| | CALL FOR 10TH FLOOR YET IF THIS IS A SUITE/UNIT WHERE |
| | THE WORK IS BEING DONE THEN THE TITLE BLOCKS NEED TO |
| | SHOW THE SUITE OR UNIT. THERE ARE ALSO TWO TOWERS TO |
| | THIS SAME ADDRESS. IS THIS EAST OR WEST TOWER? PLEASE |
| | KNOW THAT ON ALL SHEETS WHICH DO NOT NEED TO BE |
| | CORRECTED OR CHANGED FOR ELECTRICAL COMMENTS THE TITLE |
| | BLOCKS MAY SIMPLY HAVE THE INFORMATION HAND WRITTEN IN |
| | A NEAT FASHION, STAMPED, PRINTED ETC. THIS IS REQUIRED |
| | OF ALL SHEETS AND ALL SETS WHETHER OR NOT COMMENT IS OR |
| | HAS BEEN MADE BY ANY OTHER TRADES. |
| | FOR EXAMPLE: |
| | SUITE #401, EAST TOWER. |
| | |
| | FAC 61G15-23.002, 61G1-16.004. |
| | |
| | 3) NOTE: PLEASE KNOW DUE TO REPEAT COMMENTS SOME |
| | ELECTRICAL SHEETS HAVE BEEN RETAINED BY THIS OFFICE. |
| | PLEASE BE SURE COMMENTS ARE ADDRESS AND PLANS ARE |
| | ADJUSTED. ** IF THERE ARE QUESTIONS OR COMMENTS PLEASE |
| | CONTACT THIS REVIEWER DIRECTLY AT THE CONTACT |
| | INFORMATION BELOW. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |