2008-04-03 14:27:42** DENIED 3RD REVIEW **
  
 1) NOTE: PLEASE SEE COMPLIANCE FOR LIGHTING PERFORMANCE
 CALCULATIONS STILL NEEDS TO BE MET. PLEASE SEE PLANS
 STILL SHOW METHOD *C* CALCULATIONS ON SHEETS E-0.3 AND
 E-0.4. THESE NEED TO BE SUBMITTED SEPARATELY. THESE
 NEED TO SHOW ALL LIGHTING AS SHOWN ON PLANS. PLEASE SEE
 THE NEW LIGHTING LEVELS PRINTED ON TABLE ON SHEET E-0.1
 NOW CONTAINS LOWER DESIGN WATTAGE THAN THE DESIGN
 WATTAGE ON THE TWO SHEETS ABOVE.
 THE NEW LIGHTING PLANS SUBMITTED NOW HAVE NUMEROUS
 FIXTURES THAT WERE ON PREVIOUS PLANS NOW DELETED FROM
 NEW PLANS YET THE WATTAGE HAS ONLY DECREASED A SMALL
 AMOUNT FROM THE INFORMATION PREVIOUSLY SUBMITTED.
 PLEASE SEE BOTH THE EXISTING SHEETS LEFT IN SETS AND
 THE NEW INFORMATION AND PLEASE BE SURE TO COORDINATE
 ALL.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2.
  
 2) NOTE: PLEASE SEE THE ADDRESS OF THE PROJECT FOR
 SUITE/UNIT NUMBER STILL NEEDS TO BE DETERMINED. PLANS
 CALL FOR 10TH FLOOR YET IF THIS IS A SUITE/UNIT WHERE
 THE WORK IS BEING DONE THEN THE TITLE BLOCKS NEED TO
 SHOW THE SUITE OR UNIT. THERE ARE ALSO TWO TOWERS TO
 THIS SAME ADDRESS. IS THIS EAST OR WEST TOWER? PLEASE
 KNOW THAT ON ALL SHEETS WHICH DO NOT NEED TO BE
 CORRECTED OR CHANGED FOR ELECTRICAL COMMENTS THE TITLE
 BLOCKS MAY SIMPLY HAVE THE INFORMATION HAND WRITTEN IN
 A NEAT FASHION, STAMPED, PRINTED ETC. THIS IS REQUIRED
 OF ALL SHEETS AND ALL SETS WHETHER OR NOT COMMENT IS OR
 HAS BEEN MADE BY ANY OTHER TRADES.
 FOR EXAMPLE:
 SUITE #401, EAST TOWER.
  
 FAC 61G15-23.002, 61G1-16.004.
  
 3) NOTE: PLEASE KNOW DUE TO REPEAT COMMENTS SOME
 ELECTRICAL SHEETS HAVE BEEN RETAINED BY THIS OFFICE.
 PLEASE BE SURE COMMENTS ARE ADDRESS AND PLANS ARE
 ADJUSTED. ** IF THERE ARE QUESTIONS OR COMMENTS PLEASE
 CONTACT THIS REVIEWER DIRECTLY AT THE CONTACT
 INFORMATION BELOW.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  