Plan Review Notes
Plan Review Notes For Permit 07120427
Permit Number 07120427
Review Stop E
Sequence Number 2
Notes
Date Text
2008-02-01 09:44:41** DENIED 2ND REVIEW **
  
 1) NOTE: PLEASE SEE THE OWNER INFORMATION ON PERMIT
 APPLICATION IS NOT CORRECT. PLEASE ALSO KNOW THE
 SUITE/UNIT NUMBER HAS NOT YET BEEN DETERMINED AND
 COMPLETED. ONCE THIS IS DONE THE SUITE/UNIT NUMBER
 NEEDS TO BE ON TITLE BLOCKS. THIS MAY BE DONE BY HAND
 WITH OUT HAVING RE-PRINT SHEETS.
 PLEASE SEE NOTES FROM ADDRESSING AND/OR BUILDING
 REVIEWER.
 PLEASE KNOW THIS IS BEING NOTED FOR INFORMATION AS
 THESE WILL NEED TO BE CORRECTED.
  
 2) NOTE: PLEASE SUBMIT COMPLETED SEPARATE ENERGY
 CALCULATIONS. THESE ARE PRINTED ON SHEETS WHICH ARE OK;
 HOWEVER ALSO NEED SEPARATE FORMS SUBMITTED.
 PLEASE SEE THE FORMS REQUIRES OWNER/AGENT SIGNATURE,
 SIGNED, DATED AND SEALED BY THE DESIGNER OF RECORD.
 PLEASE SEE AT THIS TIME A NAME IS SHEET E-.03 WHICH
 INDICATES SOMEONE OTHER THAN THE DESIGNER OF RECORD AS
 THE PREPARER OF SAID DOCUMENTS.
 PLEASE KNOW AS THE SCOPE OF WORK IS REQUIRED TO BE DONE
 BY A LICENSED ARCHITECT/ENGINEER IN THE STATE OF
 FLORIDA; PLEASE PROVIDE INFORMATION FOR SAID PREPARER.
 IF THE PREPARER AS LISTED IS NOT A LICENSE ARCHITECT OR
 ENGINEER IN THE STATE PLEASE COMPLETE WITH THE DESIGNER
 OF RECORDS INFORMATION.
 FBC 13-103.1., FAC 61G15-23.002, FS 481.221, 471.025
 ETC
  
 3) NOTE: PLEASE SEE THE DESIGNATION ON THE INPUT DATA
 REPORT DOES NOT COORDINATE WITH THE ROOM/AREA
 DESIGNATIONS ON PLANS.
 PLEASE SEE FOR EXAMPLE: CONFERENCE ROOM IS NOTED, BUT
 IT IS UNCLEAR WHICH IS WHICH. THE IDR NOTES CONF #2,
 YET THE PLANS HAS OTHER DESIGNATIONS.
 PLEASE SEE THE IDR ALSO INDICATES *MANUAL ON/OFF*
 CONTROLS FOR MANY OF THESE ROOMS WHICH IS NOT POSSIBLE
 WHEN THESE ROOMS/LOCATIONS CONTAINS AUTOMATED TYPE
 DEVICES LISTED ON PLANS.
 13-415.1.ABC.1.1, .1.2, 13-415.2, 13-415.1.C,
 PLEASE COORDINATE ALL.
  
 4) NOTE: PLEASE CLARIFY THE CONF ROOM 10-19 WHICH SHOWS
 WHAT APPEARS AS CIRCUIT P1-29 TO THE EMERGENCY BATTERY
 BACK UP LIGHT? PLEASE CLARIFY THIS AS PLANS DO CONTAIN
 NOTES IN OTHER AREAS FOR THESE TYPES OF FIXTURES TO BE
 WIRED PER 700.12F.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved