| Date |
Text |
| 2008-02-01 09:44:41 | ** DENIED 2ND REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE THE OWNER INFORMATION ON PERMIT |
| | APPLICATION IS NOT CORRECT. PLEASE ALSO KNOW THE |
| | SUITE/UNIT NUMBER HAS NOT YET BEEN DETERMINED AND |
| | COMPLETED. ONCE THIS IS DONE THE SUITE/UNIT NUMBER |
| | NEEDS TO BE ON TITLE BLOCKS. THIS MAY BE DONE BY HAND |
| | WITH OUT HAVING RE-PRINT SHEETS. |
| | PLEASE SEE NOTES FROM ADDRESSING AND/OR BUILDING |
| | REVIEWER. |
| | PLEASE KNOW THIS IS BEING NOTED FOR INFORMATION AS |
| | THESE WILL NEED TO BE CORRECTED. |
| | |
| | 2) NOTE: PLEASE SUBMIT COMPLETED SEPARATE ENERGY |
| | CALCULATIONS. THESE ARE PRINTED ON SHEETS WHICH ARE OK; |
| | HOWEVER ALSO NEED SEPARATE FORMS SUBMITTED. |
| | PLEASE SEE THE FORMS REQUIRES OWNER/AGENT SIGNATURE, |
| | SIGNED, DATED AND SEALED BY THE DESIGNER OF RECORD. |
| | PLEASE SEE AT THIS TIME A NAME IS SHEET E-.03 WHICH |
| | INDICATES SOMEONE OTHER THAN THE DESIGNER OF RECORD AS |
| | THE PREPARER OF SAID DOCUMENTS. |
| | PLEASE KNOW AS THE SCOPE OF WORK IS REQUIRED TO BE DONE |
| | BY A LICENSED ARCHITECT/ENGINEER IN THE STATE OF |
| | FLORIDA; PLEASE PROVIDE INFORMATION FOR SAID PREPARER. |
| | IF THE PREPARER AS LISTED IS NOT A LICENSE ARCHITECT OR |
| | ENGINEER IN THE STATE PLEASE COMPLETE WITH THE DESIGNER |
| | OF RECORDS INFORMATION. |
| | FBC 13-103.1., FAC 61G15-23.002, FS 481.221, 471.025 |
| | ETC |
| | |
| | 3) NOTE: PLEASE SEE THE DESIGNATION ON THE INPUT DATA |
| | REPORT DOES NOT COORDINATE WITH THE ROOM/AREA |
| | DESIGNATIONS ON PLANS. |
| | PLEASE SEE FOR EXAMPLE: CONFERENCE ROOM IS NOTED, BUT |
| | IT IS UNCLEAR WHICH IS WHICH. THE IDR NOTES CONF #2, |
| | YET THE PLANS HAS OTHER DESIGNATIONS. |
| | PLEASE SEE THE IDR ALSO INDICATES *MANUAL ON/OFF* |
| | CONTROLS FOR MANY OF THESE ROOMS WHICH IS NOT POSSIBLE |
| | WHEN THESE ROOMS/LOCATIONS CONTAINS AUTOMATED TYPE |
| | DEVICES LISTED ON PLANS. |
| | 13-415.1.ABC.1.1, .1.2, 13-415.2, 13-415.1.C, |
| | PLEASE COORDINATE ALL. |
| | |
| | 4) NOTE: PLEASE CLARIFY THE CONF ROOM 10-19 WHICH SHOWS |
| | WHAT APPEARS AS CIRCUIT P1-29 TO THE EMERGENCY BATTERY |
| | BACK UP LIGHT? PLEASE CLARIFY THIS AS PLANS DO CONTAIN |
| | NOTES IN OTHER AREAS FOR THESE TYPES OF FIXTURES TO BE |
| | WIRED PER 700.12F. |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |