| Plan Review Notes For Permit 07120427 |
| Permit Number |
07120427 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-01-08 10:27:09 | ***DENIED*** | | | | | | 1) THE ADOPTED CODE EDITION FOR FIRE PREVENTION CODE IS | | | 2004 EDITION. SHT A00.00 | | | | | | 2) NFPA 241, NOT 214 IS THE STANDARD FOR SAFEGUARDING | | | CONSTRUCTION, ALTERATION AND DEMOLITION. SHT A00.00 | | | | | | 3) MAXIMUM TRAVEL DISTANCE INFORMATION IS DIFFICULT TO | | | READ. SHT A00.20, 00.21, AND 00.22 NEXT TO COMM. RM. | | | | | | 4) PLEASE PROVIDE MINIMUM INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILING. | | | | | | 5) NFPA 101, AND NFPA 1, 2003 EDITION. SHT E-0.1. | | | | | | 6) ACCESS CONTROLLED EGRESS DOORS SHALL COMPLY WITH | | | NFPA 101, SEC. 7.2.1.6.2. | | | | | | 7) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|