| Date |
Text |
| 2007-12-23 17:08:20 | ** DENIEDREVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THE PLANS/PERMIT APPLICATION NEED |
| | TO COORDINATE. PLEASE SEE APPLICATION DOES NOT INDICATE |
| | WHICH TOWER SCOPE OF WORK WILL BE DONE. PLEASE SEE |
| | PLANS CALL FOR WEST TOWER. |
| | AS THE SCOPE OF WORK DOES FALL UNDER A TENANT SPACE AND |
| | NOT THE ENTIRE FLOOR PLEASE KNOW THE PERMIT APPLICATION |
| | DOCUMENTATION WILL BE ROUTED TO THE ADDRESSING REVIEWER |
| | FOR SUITE/UNIT NUMBER DETERMINATION. PLEASE SE AWARE OF |
| | ANY POSSIBLE CHANGES |
| | PLEASE SEE THE OWNER INFORMATION ON PERMIT APPLICATION |
| | ALSO NEEDS TO BE ADJUSTED. THE TENANT IS LISTED AS |
| | OWNER OF BUILDING WHICH IS NOT THE CASE. PLEASE SEE |
| | SPACE FOR TENANT INFORMATION. |
| | PLEASE ADJUST AS NEEDED. |
| | FBC 106.5, 106.1.2, |
| | FAC 61G15-23.002 |
| | |
| | 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS |
| | FOR ARCHITECTURAL FIRM AS REQUIRED PER FLORIDA |
| | ADMINISTRATIVE CODE 61G1-16.004 AND FLORIDA STATUTES |
| | 481.219. |
| | PLEASE BE SURE THE PRINTED NAME, PRINTED LICENSE NUMBER |
| | OF ARCHITECT ALONG WITH THE MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER IS PLACED ON ALL SHEETS WHICH |
| | CONTAIN THE TITLE BLOCKS FOR THE ARCHITECTURAL FIRM |
| | LISTED. |
| | |
| | 3) NOTE: PLEASE SEE FS 471.025 AS THE PLANS ARE ALSO |
| | REQUIRED TO BE DATED WHEN SIGNING AND SEALING SAID |
| | DOCUMENTS. |
| | ELECTRICAL PLANS ARE NOT DATED. |
| | |
| | 4) NOTE: PLEASE SEE THE FOLLOWING CODES ARE TO BE |
| | STATED ON PLANS AS THE LATEST ADOPTED EDITIONS BY THE |
| | STATE OF FLORIDA. SOME ARE ALREADY SHOWN, HOWEVER THIS |
| | IS REQUIRED ON ARCHITECTURAL AND ELECTRICAL SHEETS FOR |
| | THIS REVIEWER. |
| | PLEASE SEE SOME CODES LISTED ARE NOT YET ADOPTED BY THE |
| | STATE. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 (SHOWS 2006) |
| | 2003 NFPA-101 (SHOWS 2005) |
| | |
| | 5) NOTE:PLEASE SHOW LIGHTING POWER DENSITIES FOR |
| | EXISTING AND NEW LIGHTING BEFORE NEW LIGHTING MAY BE |
| | ADDED. |
| | PLEASE SEE 13-415.2. |
| | PLEASE KNOW AS THE SPACE ALREADY CONTAINS CONDITIONED |
| | SPACE, WE ONLY NEED THE LIGHTING PERFORMANCE |
| | CALCULATIONS. |
| | |
| | 6)NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND |
| | PLACES NOTES ON PLANS ACCORDINGLY. |
| | THE NOTE ON E- #7 NEEDS TO BE EXPANDED UPON. |
| | |
| | 7) NOTE: PLEASE INDICATE MAXIMUM TIMES ON OCCUPANCY |
| | DEVICES AS SHOWN ON PLANS ALONG WITH SWITCHING DEVICES |
| | SHOWN. |
| | PLEASE VERIFY ANY NEW CONTROLS FOR BATHROOMS. PLEASE |
| | PROVIDE MORE INFORMATION AND DETAILS FOR NEW LUTORN |
| | GRAFIK EQUIPMENT. |
| | SCHEDULING TIMES ETC. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2. |
| | PLANS SYMBOL LEGEND CAN BE USED TO INCLUDE TIMES. |
| | |
| | 8) NOTE: PLEASE SEE BASED ON PLANS AND PANEL SCHEDULES |
| | SUBMITTED PLEASE SEE BOTH PANEL *IG* AND PANEL *P* |
| | REQUIRE MAINS WITH OVER CURRENT PROTECTION ON THE |
| | SECONDARY SIDE OF THE TRANSFORMERS AS SHOWN. PLEASE |
| | KNOW THIS WAS REQUIRED IN THE NEC EVEN WHEN THE |
| | BUILDING WAS ORIGINALLY BUILT. PLEASE VERIFY IF THESE |
| | PANELS ALREADY CONTAIN MAINS AND THE PANELS WHICH ARE |
| | SHOWN AS MLO ARE ONLY A MISPRINT. |
| | PLEASE KNOW IF THESE PANELS DO NOT CONTAIN OVER CURRENT |
| | PROTECTION ON THE SECONDARY SIDE OF THE TRANSFORMER |
| | THIS IS A LIFE SAFETY AND FIRE HAZARD AND MAIN CIRCUIT |
| | BREAKERS OR DISCONNECTS WITH OCP WILL BE REQUIRED TO BE |
| | INSTALLED. |
| | PLEASE SEE NEC 240.21, 408.36, 310.16, 240.4, 90.4. ** |
| | PLEASE VERIFY IN FIELD BEFORE RESUBMITTING PLANS.A |
| | FILED INSPECTION MAY BE SET UP TO VERIFY THESE BEFORE |
| | PERMIT ISSUANCE. |
| | |
| | 9) NOTE: PLEASE SEE NOTES ON SHEET E-0.2 WIRING NOTE 3 |
| | 3.02 (D) AS ANY COLOR CODING FOR ANY NEW WIRING SHALL |
| | BE BROWN, PURPLE, YELLOW FOR 277/480V SYSTEMS. ORANGE |
| | PER THE NEC IS MARKING FOR A HIGH-LEG DELTA SYSTEM |
| | WHICH 277/480V IS NOT. |
| | PLEASE KNOW LOCAL COLOR CODING FOR DECADES WAS DONE BY |
| | LOCAL AMENDMENTS AND AS THE NEC DOES NOT PROVIDE COLOR |
| | CODING THE ABOVE COLORS WERE DETERMINED ON A CITY AND |
| | COUNTY WIDE BASIS. EVEN AS TECHNICAL AMENDMENTS ARE NO |
| | LONGER IN AFFECT, THESE COLORS WILL STILL BE ADHERED TO |
| | AS NEC DOES NOT PROVIDE. |
| | NEC 90.4 |
| | |
| | 10) NOTE: PLEASE PROVIDE NOTES FOR ALL DEVICES WHICH |
| | ARE NOTED FOR ACCESS CONTROLS AND DOORS LOCKING DEVICES |
| | WHICH ARE REQUIRED TO MEET NFPA-101 2003 7.2 PLEASE |
| | KNOW THAT NO DEVICES SHALL IMPEDED EGRESS DURING AN |
| | EMERGENCY OR POWER FAILURE. |
| | PLEASE SEE 7.2.1.5, 7.2.1.6.2 ETC |
| | PLEASE SEE POSSIBLE COMMENTS FROM FIRE MARSHAL |
| | |
| | |
| | *** IMPORTANT** |
| | AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR REVIEW, |
| | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH |
| | CAN NOT BE MADE AT THIS TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |