Plan Review Notes
Plan Review Notes For Permit 07120427
Permit Number 07120427
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-23 17:08:20** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE KNOW THE PLANS/PERMIT APPLICATION NEED
 TO COORDINATE. PLEASE SEE APPLICATION DOES NOT INDICATE
 WHICH TOWER SCOPE OF WORK WILL BE DONE. PLEASE SEE
 PLANS CALL FOR WEST TOWER.
 AS THE SCOPE OF WORK DOES FALL UNDER A TENANT SPACE AND
 NOT THE ENTIRE FLOOR PLEASE KNOW THE PERMIT APPLICATION
 DOCUMENTATION WILL BE ROUTED TO THE ADDRESSING REVIEWER
 FOR SUITE/UNIT NUMBER DETERMINATION. PLEASE SE AWARE OF
 ANY POSSIBLE CHANGES
 PLEASE SEE THE OWNER INFORMATION ON PERMIT APPLICATION
 ALSO NEEDS TO BE ADJUSTED. THE TENANT IS LISTED AS
 OWNER OF BUILDING WHICH IS NOT THE CASE. PLEASE SEE
 SPACE FOR TENANT INFORMATION.
 PLEASE ADJUST AS NEEDED.
 FBC 106.5, 106.1.2,
 FAC 61G15-23.002
  
 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 FOR ARCHITECTURAL FIRM AS REQUIRED PER FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004 AND FLORIDA STATUTES
 481.219.
 PLEASE BE SURE THE PRINTED NAME, PRINTED LICENSE NUMBER
 OF ARCHITECT ALONG WITH THE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER IS PLACED ON ALL SHEETS WHICH
 CONTAIN THE TITLE BLOCKS FOR THE ARCHITECTURAL FIRM
 LISTED.
  
 3) NOTE: PLEASE SEE FS 471.025 AS THE PLANS ARE ALSO
 REQUIRED TO BE DATED WHEN SIGNING AND SEALING SAID
 DOCUMENTS.
 ELECTRICAL PLANS ARE NOT DATED.
  
 4) NOTE: PLEASE SEE THE FOLLOWING CODES ARE TO BE
 STATED ON PLANS AS THE LATEST ADOPTED EDITIONS BY THE
 STATE OF FLORIDA. SOME ARE ALREADY SHOWN, HOWEVER THIS
 IS REQUIRED ON ARCHITECTURAL AND ELECTRICAL SHEETS FOR
 THIS REVIEWER.
 PLEASE SEE SOME CODES LISTED ARE NOT YET ADOPTED BY THE
 STATE.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72 (SHOWS 2006)
 2003 NFPA-101 (SHOWS 2005)
  
 5) NOTE:PLEASE SHOW LIGHTING POWER DENSITIES FOR
 EXISTING AND NEW LIGHTING BEFORE NEW LIGHTING MAY BE
 ADDED.
 PLEASE SEE 13-415.2.
 PLEASE KNOW AS THE SPACE ALREADY CONTAINS CONDITIONED
 SPACE, WE ONLY NEED THE LIGHTING PERFORMANCE
 CALCULATIONS.
  
 6)NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND
 PLACES NOTES ON PLANS ACCORDINGLY.
 THE NOTE ON E- #7 NEEDS TO BE EXPANDED UPON.
  
 7) NOTE: PLEASE INDICATE MAXIMUM TIMES ON OCCUPANCY
 DEVICES AS SHOWN ON PLANS ALONG WITH SWITCHING DEVICES
 SHOWN.
 PLEASE VERIFY ANY NEW CONTROLS FOR BATHROOMS. PLEASE
 PROVIDE MORE INFORMATION AND DETAILS FOR NEW LUTORN
 GRAFIK EQUIPMENT.
 SCHEDULING TIMES ETC.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2.
 PLANS SYMBOL LEGEND CAN BE USED TO INCLUDE TIMES.
  
 8) NOTE: PLEASE SEE BASED ON PLANS AND PANEL SCHEDULES
 SUBMITTED PLEASE SEE BOTH PANEL *IG* AND PANEL *P*
 REQUIRE MAINS WITH OVER CURRENT PROTECTION ON THE
 SECONDARY SIDE OF THE TRANSFORMERS AS SHOWN. PLEASE
 KNOW THIS WAS REQUIRED IN THE NEC EVEN WHEN THE
 BUILDING WAS ORIGINALLY BUILT. PLEASE VERIFY IF THESE
 PANELS ALREADY CONTAIN MAINS AND THE PANELS WHICH ARE
 SHOWN AS MLO ARE ONLY A MISPRINT.
 PLEASE KNOW IF THESE PANELS DO NOT CONTAIN OVER CURRENT
 PROTECTION ON THE SECONDARY SIDE OF THE TRANSFORMER
 THIS IS A LIFE SAFETY AND FIRE HAZARD AND MAIN CIRCUIT
 BREAKERS OR DISCONNECTS WITH OCP WILL BE REQUIRED TO BE
 INSTALLED.
 PLEASE SEE NEC 240.21, 408.36, 310.16, 240.4, 90.4. **
 PLEASE VERIFY IN FIELD BEFORE RESUBMITTING PLANS.A
 FILED INSPECTION MAY BE SET UP TO VERIFY THESE BEFORE
 PERMIT ISSUANCE.
  
 9) NOTE: PLEASE SEE NOTES ON SHEET E-0.2 WIRING NOTE 3
 3.02 (D) AS ANY COLOR CODING FOR ANY NEW WIRING SHALL
 BE BROWN, PURPLE, YELLOW FOR 277/480V SYSTEMS. ORANGE
 PER THE NEC IS MARKING FOR A HIGH-LEG DELTA SYSTEM
 WHICH 277/480V IS NOT.
 PLEASE KNOW LOCAL COLOR CODING FOR DECADES WAS DONE BY
 LOCAL AMENDMENTS AND AS THE NEC DOES NOT PROVIDE COLOR
 CODING THE ABOVE COLORS WERE DETERMINED ON A CITY AND
 COUNTY WIDE BASIS. EVEN AS TECHNICAL AMENDMENTS ARE NO
 LONGER IN AFFECT, THESE COLORS WILL STILL BE ADHERED TO
 AS NEC DOES NOT PROVIDE.
 NEC 90.4
  
 10) NOTE: PLEASE PROVIDE NOTES FOR ALL DEVICES WHICH
 ARE NOTED FOR ACCESS CONTROLS AND DOORS LOCKING DEVICES
 WHICH ARE REQUIRED TO MEET NFPA-101 2003 7.2 PLEASE
 KNOW THAT NO DEVICES SHALL IMPEDED EGRESS DURING AN
 EMERGENCY OR POWER FAILURE.
 PLEASE SEE 7.2.1.5, 7.2.1.6.2 ETC
 PLEASE SEE POSSIBLE COMMENTS FROM FIRE MARSHAL
  
  
 *** IMPORTANT**
 AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR REVIEW,
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  