Date Text
2008-01-02 16:53:33BUILDING PLAN REVIEW
 PERMIT: 07120427
 ADD: 777 S FLAGLER DR 10TH FLOOR
 CONT: PAVARNI INTERIORS
 TEL: (561) 856-6655
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS * WEST PALM BEACH AMENDMENTS
 JAN. 02,2008
 1ST REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS. SHEET A00.00 UNDER
 THE BUILDING CODE SUMMARY INDICATES THE PLANS WERE
 PREPARED UNDER THE 2006 FBC SUPPLEMENTS, PLEASE
 CORRECT.
  
 2) .FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) ARCHITECT OF RECORD STERHEN TURNER SWICEGOOD IS
 MISSING HIS PRINTED NAME AND LICENSE NUMBER IN THE
 TITLE BLOCK. THE NAME OF THE ARCHITECTURAL FIRM GENSLER
 ARCHITECT APPEARS TO BE EITHER A FIRM REQUIRING A
 CERTIFICATE OF AUTHORIZATION.
 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE
 NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND DATE SEAL
 - INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE
 PLANS.
  
 4)SHEET A00.00 ALSO INDICATES THE WORK TO BE
 COMPLETED UNDER THIS PERMIT TO BE A LEVEL III
 ALTERATION. PLEASE SEE SSECTION 305.1 OF THE 2004
 EXISTING BUILDING CODE FBC. FOR A LEVEL III ALTERATION
 TO TAKE PLACE 50% OF THE AGGREGATE AREA OF THE BUILDING
 AND WITHIN ANY 12-MONTH PERIOD.EITHER THIS IS THE
 FIRST OF A LARGE BUILDING RENOVATION OR A LEVEL II
 ALTERATION. PLEASE CLARIFY THE INTENT?
  
 5) SHEET A00.00 BUILDING DATA: INDICATES THE BUILDING
 IS LOCATED IN A FIRE DISTRICT, THERE ARE NO LONGER ANY
 FIRE DISTRICTS IN THE CITY OF WEST PALM BEACH, THEY
 WERE REMOVED SOME YEARS AGO. PLEASE CORRECT.
 106.1.2 ADDTIONAL INFORMATION REQUIRED.
  
 6A)A00.31 INDICATES THE USE OF A WALL COVERING AND
 STRETCH FABRIC WALL SYSTEM BOTH USING KNOLL TEXTILE,
 SEQUELAS THE WALL FINISH, PLEASE PROVIDE ADDITIONAL
 MOUNTING INFORMATION OR THE STRETCH WALL SYSTEM,DOES
 THIS SYSTEM STRETCH THE FABRIC OVER A SOLID BACKING OR
 IS THE FABRIC MOUNTED INTO A FRAME, THEN STRETCHED THAT
 ALLOWA AIR BEHIND THE FABRIC? PLEASE SEE 803.6.1 FOR
 FLAME SPREAD CLASSIFICATION AND TEST PROTOCAL.
  
 6B)SHEET A11.01 VARIOUS ELEVATIONS HAVE A NOTE # 17
 INDICATING TACKABLE FABRIC WRAPPED PANELS AND A DETAIL
 OR CUT SECTION 4/ A12.01. WHEN REVIEWING THIS DETAIL IT
 IS OF A HEAD DETAIL OF TYPICAL DOOR, NOT THE PANELIZED
 WALL SYSTEM. PLEASE PROVIDE THE INFORMATION REQUESTED
 UNDER COMMENT 6A. SEE 803.6.1.
  
 7) A01.10NOTE # 13 INDICATES CORNER DETAILS FOUNDON
 DETAIL 9/A12.-00, THIS SHEET IS MISSING. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 8) A02.10 ROOMS 1026,1027 & CORRIDOR 10-H17 APPEAR TO
 BE MISSING THE 18" ON THE LATCH SIDE OF THE DOOR.
 11-4.13.5 DOORWAY MIN CLEAR WIDTH . DOORWAYS SHALL HAVE
 A MINIMUM CLEAR WIDTH OF 32" WITH THE DOOR OPEN
 90-DEGREES, MEASURED BETWEEN THE FACE OF THE DOOR AND
 OPPOSITE STOP. 11-4.13.6 MANEUVERING CLEARENCES AT
 DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE
 NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE CLEAR & LEVEL.
  
 9)SHEET A12.01 & A12.02 WOOD BUCK DETAILS DO NOT
 INDICATE THE USE OF FIRE RETARDANT TREATED WOOD, SEE
 SECTION 603.1.
  
 10)ASSUMPTIONS:
 10A) ROOM 10-37 NO WORK BEING COMPLETED, AND FLOOR
 SYSTEM IS ALREADY DESIGNED FOR HEAVY STORAGE.
 10B) ROOM 10-38 BREAK ROOM NO WORK BEING COMPLETED SINK
 ADA IS ALREADY CODE COMPLIANT.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved