| 2009-03-05 08:49:46 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLANS ON RECORD ARE UNDER THE DESIGN OF AGILE |
| | ENGINEERING INC. SIGNED, DATED AND SEALED BY MR. JOHN |
| | SYLVIA PE. PLEASE SEE FAC 61G15-23, FS 471.025 |
| | PLANS MUST BE REVISED BY THE DESIGNER OF RECORD OR |
| | PLEASE PROVIDE DOCUMENTATION AS REQUIRED BY THE FLORIDA |
| | ADMINISTRATIVE CODE FOR TAKING OVER THE RESPONSIBILITY |
| | OF ANOTHER DESIGN PROFESSIONALS WORK. |
| | A LETTER FROM THE ORIGINAL ENGINEERING RELEASING |
| | HIMSELF WOULD ALSO BE AN OPTION. |
| | |
| | 2) NOTE: THERE ARE SEVERAL ITEMS WHICH WERE ON PREVIOUS |
| | PLANS WHICH ARE NOW MISSING. |
| | DISCONNECTS, WATER HEATER, PANELS ETC. |
| | FOR EXAMPLE: GUEST HOUSE WATER HEATER, GUEST HOUSE |
| | ELECTRICAL PANEL, MAIN HOUSE DISCONNECT, MISSING |
| | REQUIRED GFI IN BATH AT GUEST HOUSE ETC. |
| | |
| | PLEASE GO THROUGH ORIGINAL PLANS. ITEMS MAY BE DELETED |
| | WHICH ARE NOT REQUIRED BY NFPA-70 ( NEC) HOWEVER BOTH |
| | MAIN HOUSE AND GUEST HOUSE MUST SHOW THE MINIMUM |
| | REQUIRED BY CODE. |
| | PLEASE SEE |
| | 4220.13,240.24,110.26,215.5,225.31-225.39,210.8A2, |
| | 210.52D ETC |
| | |
| | 3) NOTE: PLEASE PROVIDE REVISED PANEL SCHEDULE, RISER |
| | AND LOAD CALCULATIONS. 408.4,215.5,250,220 |
| | |
| | 4) NOTE: KITCHEN IN MAIN HOUSE NOW SHOWS RECEPTACLES |
| | WHICH WERE NOT ON ORIGINAL PERMITTED PLANS. ALL |
| | RECEPTACLES SERVICE KITCHEN COUNTER SPACE SHALL BE GFI/ |
| | GFI PROTECTED. 210.8A6 |
| | |
| | 5) NOTE: PLANS MISSING WALL RECEPTACLE REQUIRED PER |
| | 210.52 WHICH WAS ON ORIGINAL PLANS. SEE KITCHEN WALL IN |
| | GUEST HOUSE. |
| | |
| | 6) NOTE: PLANS INDICATE A NEW MINI LIFT STATION HOWEVER |
| | THERE IS NO ELECTRICAL SHOWN ON THE E-SHEETS FOR ANY |
| | SUCH ITEM. NO ELECTRICAL DETAIL, NO DISCONNECT, NO |
| | REVISE PANEL, NO INCREASED LOAD. |
| | NEC 2005 220,215,430,ETC |
| | FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND |
| | CLARITY. |
| | |
| | |
| | *** THESE ITEMS ABOVE ARE SOME EXAMPLES THAT HAVE |
| | CHANGED THE PLANS SUBSTANTIALLY WHICH NEED TO SHOW CODE |
| | COMPLIANCE. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |