| Date |
Text |
| 2008-03-03 16:02:33 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS REVIEW |
| | ARE STILL IN NEED OF ADDRESSING. |
| | ** PLEASE ALSO SEE THAT MANY COMMENTS ARE NEW AS THESE |
| | THINGS ARE JUST NOW BEING SHOWN. |
| | PLEASE ALSO SEE THE RISER HAS NOW BEEN COMPLETELY |
| | REVISED. SOME NEW COMMENTS HAVE NOW BEEN CREATED. MANY |
| | ITEMS WHICH WERE CODE COMPLIANT ON PREVIOUS REVIEW HAVE |
| | NOW COMPLETELY CHANGED AND ARE NOW NO LONGER CODE |
| | COMPLIANT. |
| | |
| | 1) NOTE: PLEASE SEE THE RISER HAS BEEN REVISED REMOVING |
| | A MAIN FOR GROUPING OF MAINS AS REQUIRED PER 230.72. ON |
| | THE PREVIOUS REVIEW A COMMENT WAS MADE THAT A MAIN |
| | DISCONNECT WAS MISSING AT THE MAIN HOUSE AS REQUIRED |
| | PER 225.31-225.39. THIS MAIN WHICH WAS ON PREVIOUS |
| | RISER GROUPED, HAS NOW BEEN MOVED. THE CODE REQUIRES |
| | MAINS FOR SERVICE TO BE GROUPED PER 230.72 AND A MAIN |
| | AT THE DETACHED STRUCTURE PER 225.31-225.39. PLEASE |
| | ADJUST RISER. |
| | |
| | 2) NOTE: PLEASE ALSO CORRELATE RISER AND PLANS. THE |
| | RISER SHOWS THE MAIN AT THE HOUSE AS 200AMPS AND THE |
| | PLANS CLEARLY SHOW A MAIN DISCONNECT RATED AT 125AMPS? |
| | PLEASE SEE THE PREVIOUS PLANS INDICATE 125AMPS FOR |
| | PANEL AND MAIN AND THESE NOW INDICATE 200AMP FOR |
| | BOTH?? |
| | 230, 225, 240.4, 310.16 ETC |
| | FBC 106.1.2 FOR COORDINATION. IT IS UNCLEAR AT THIS |
| | TIME WHAT MAINS AND PANELS ARE REALLY BEING DESIGNED. |
| | PLEASE ALSO SEE NEXT COMMENT AS SERVICE SIZE HAS NOW |
| | BEEN INCREASED. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS PLANS WHICH SHOWED ONE |
| | 125AMP MAIN AND ONE 75AMP MAIN WHICH WAS IN LINE WITH |
| | THE 200AMP RATED CONDUCTORS AND SERVICE. HOWEVER PLEASE |
| | NOW SEE AS THE SERVICE NOW SHOWS A NEW 200AMP MAIN AND |
| | A NEW 100AMP MAIN THE RATING OF THE SERVICE NEEDS TO |
| | COORDINATE AND BE SIZED FOR THE OVER CURRENT PROTECTION |
| | AND CONDUCTORS. THIS IS NOW SHOWN AS A 300AMP SERVICE. |
| | RISER SHOWS 3/0 CONDUCTORS TO THE 100AMP MAIN AND 3/0 |
| | CONDUCTORS TO THE 100AMP SUB PANEL? |
| | PLEASESEE 240.4, 310.16 ETC |
| | AS THERE ARE SEVERAL ITEMS WHICH WILL BE ADJUSTED, A |
| | FULL REVIEW OF ALL ITEMS CAN NOT BE DONE AT THIS TIME. |
| | FBC 106.3.5.4 |
| | **PLEASE ALSO SEE THE METER WOULD ALSO NOW NEED TO BE |
| | SHOWN AS 300AMPS. |
| | |
| | 4) NOTE: PLEASE SEE 240.4, 250.66, 310.15B6 AND 310.16. |
| | IF THE MINIMUM SERVICE IS NOW GOING TO BE 300AMPS, |
| | PLEASE ADJUST SERVICE ENTRANCE CONDUCTORS AND THE |
| | GROUNDING ELECTRODE CONDUCTOR AT THE MAIN SERVICE. IF |
| | SERVICE IS GOING TO BE 300AMPS, THEN BASED ON MINIMUM |
| | SERVICE ENTRANCE CONDUCTORS PER 310.15B6 AND THE |
| | SIZING ON TABLE 250.66 REQUIRES THE GEC AT #2 AWG AT |
| | MAIN SERVICE LOCATION. |
| | |
| | 5) NOTE: PREVIOUS REVIEW NOTE REQUESTED TO SHOW THE |
| | GROUNDING ELECTRODE SYSTEM AT BOTH GUEST HOUSE AND |
| | DETACHED STRUCTURE (MAIN HOUSE). THE RESPONSE MENTIONS |
| | THIS IS NOW SHOWN HOWEVER ONLY SHOWS A GROUNDOF SOME |
| | TYPE. THIS WILL REQUIRE FOOTER STEEL, (METAL) CWP AND |
| | BONDING OF ANY GAS PIPING PER 250.50, 250.56, 250.52, |
| | AND 250.104. |
| | |
| | 6) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO THE |
| | LIGHT FIXTURES OUTSIDE GUEST HOUSE AND MAIN HOUSE WHICH |
| | DID NOT MEET 680.22B1 |
| | THE PLANS HAVE NOW BEEN REVISED TO SHOW THESE FIXTURES |
| | AT 12FT AFF YET THIS WOULD PLACE THE FIXTURES ABOVE THE |
| | ROOF LINE BASED ON THE ELEVATIONS ON THE ARCHITECTURAL |
| | PLANS.??? |
| | PLEASE SEE THE LOCATIONS OF THE LIGHTING FIXTURES NEED |
| | TO BE REVISED. PLEASE ALSO SEE THAT BASED ON THE SCALE |
| | ON PLANS THE GFI RECEPTACLES ON BOTH THE MAIN HOUSE AND |
| | GUEST ARE SHOWN AT 5FT. THESE MUST BE MORE THAN 5FT |
| | FROM WATERS EDGE. THESE COULD BE REDLINED TO VIF |
| | HOWEVER BASED ON PLANS AT THIS TIME THIS NEEDS TO BE |
| | VERIFIED AS LIGHT FIXTURES NEED TO BE RELOCATED. |
| | |
| | 7) NOTE: PLEASE SEE AS PANEL SCHEDULES ARE NOW BEING |
| | SUBMITTED. PLEASE SEE THAT THESE ARE REQUIRED TO BE |
| | DETAILED FOR ALL ROOMS AND AREAS IN WHICH THEY FEED PER |
| | 408.4, 240.4, 310.16. |
| | IE; BEDRM #2 LTS, KITCHEN LTS. ETC |
| | FBC 106.1.2, 106.3.5.4, 106.5 |
| | |
| | 8) NOTE: PLEASE SEE MISSING RECEPTACLE ALONG KITCHEN |
| | WALL IN GUEST HOUSE AND NEW MASTER BEDROOM WALL PER |
| | 210.52. |
| | ONE WAS GIVEN ON PREVIOUS REVIEW AND CODE FOR 210.52. |
| | THE PREVIOUS EXAMPLE FOR MISSING WAS DONE BUT NOT ALL |
| | LOCATIONS FOR NEW WALLS 2FT OR MORE WHERE REQUIRED PER |
| | 210.52. |
| | |
| | 9) NOTE: PLEASE GO OVER LOAD CALCULATIONS AS THE SQ FT |
| | FOR GUEST HOUSE ON MAIN SERVICE LOAD SUMMARY DOES NOT |
| | COORDINATE WITH THE SQ FT ON GUEST HOUSE PANEL |
| | CALCULAITONS. |
| | NEC 220 |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |