| Plan Review Notes For Permit 07120426 |
| Permit Number |
07120426 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-03-08 09:07:35 | | | | | | | | | | DENIED | | | | | | THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE 1ST | | | REVIEW | | | | | | | | | 1)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE, | | | AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE | | | INFORMATION. | | | | | | 2)NOTE: FEES ARE DUE IN THE AMOUNT OF $505.97 FOR | | | INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS | | | REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW | | | ******$10.00 WAS ADDED TO FEES FOR HISTORIC | | | REVIEW******* | | | | | | 4)SUBMIT TWO COPIES OF ENERGY CALC'S PLEASE NOTE | | | MECHANICAL REVIEWERS COMMENT | | | | | | NEW COMMENTS | | | | | | 1)PROVIDE THE SYSTEM THAT WILL BE USED FROM THE | | | MODIFIED BITUMEN ROOFING PRODUCT APPROVAL | | | | | | 2)HISTORIC APPROVAL STAMP IS REQUIRED ON THE | | | DUPLICATE PERMIT APPLICATION FORM | | | | | | 3)SHUTTER OPENING #5 IN THE SHUTTER SCHEDULE SHOULD | | | HAVE A DESIGN PRESSURE OF +49/-66 PSF PERTHE | | | COMPONENT AND CLADDING SCHEDULE ON SHEET S-4 | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|