| Date |
Text |
| 2007-12-28 14:21:24 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET P-1 PLUMBING PLAN, AND SHEET P-2 SANITARY |
| | RISER: THE HORIZONTAL DRY VENT FOR THE GUEST HOUSE |
| | SHOWER IS NOT ALLOWED PER THE FOLLOWING. |
| | |
| | 905.3 VENT CONNECTION TO DRAINAGE SYSTEM. |
| | EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL |
| | CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN |
| | PIPE. |
| | |
| | 905.4 VERTICAL RISE OF VENT. |
| | EVERY DRY VENT SHALL RISE VERTICALLY TO A MINIMUM OF 6 |
| | INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM OF THE |
| | HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. |
| | EXCEPTION: VENTS FOR INTERCEPTORS LOCATED OUTDOORS. |
| | |
| | 2. SHEET P-1 PLUMBING PLAN AND SHEET P-2 SANITARY |
| | RISER: TWO-WAY CLEANOUTS ARE REQUIRED FOR THE ADDITION |
| | AND GUEST HOUSE SANITARY SYSTEM PER THE FOLLOWING. |
| | |
| | 708.3.5 BUILDING DRAIN AND BUILDING SEWER JUNCTION. |
| | THERE SHALL BE A CLEANOUT NEAR THE JUNCTION OF THE |
| | BUILDING DRAIN AND THE BUILDING SEWER. THE CLEANOUT |
| | SHALL BE EITHER INSIDE OR OUTSIDE THE BUILDING WALL AND |
| | SHALL BE BROUGHT UP TO THE FINISHED GROUND LEVEL OR TO |
| | THE BASEMENT FLOOR LEVEL. AN APPROVED TWO-WAY CLEANOUT |
| | IS ALLOWED TO BE USED AT THIS LOCATION TO SERVE AS A |
| | REQUIRED CLEANOUT FOR BOTH THE BUILDING DRAIN AND |
| | BUILDING SEWER. THE CLEANOUT AT THE JUNCTION OF THE |
| | BUILDING DRAIN AND BUILDING SEWER SHALL NOT BE REQUIRED |
| | IF THE CLEANOUT ON A 3-INCH (76 MM) OR LARGER DIAMETER |
| | SOIL STACK IS LOCATED WITHIN A DEVELOPED LENGTH OF 10 |
| | FEET (3048 MM) OF THE BUILDING DRAIN AND BUILDING SEWER |
| | CONNECTION. THE MINIMUM SIZE OF THE CLEANOUT AT THE |
| | JUNCTION OF THE BUILDING DRAIN AND BUILDING SEWER SHALL |
| | COMPLY WITH SECTION 708.7 . |
| | |
| | 3. SHEET P-1 PLUMBING PLAN AND SHEET P-2 SANITARY |
| | RISER: PLEASE INDICATED THAT THE SANITARY CONNECTION |
| | FROM THE ADDITION AND GUEST HOUSE TO THE EXISTING |
| | SYSTEM SHALL CONNECT DOWNSTREAM OF THE EXISTING WET |
| | VENTED BATHROOM PER THE FOLLOWING. |
| | |
| | 909.1 WET VENT PERMITTED. |
| | ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS |
| | LOCATED ON THE SAME FLOOR LEVEL ARE PERMITTED TO BE |
| | VENTED BY A WET VENT. THE WET VENT SHALL BE CONSIDERED |
| | THE VENT FOR THE FIXTURES AND SHALL EXTEND FROM THE |
| | CONNECTION OF THE DRY VENT ALONG THE DIRECTION OF THE |
| | FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE |
| | DRAIN CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY |
| | THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY |
| | ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE |
| | WET VENT. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |
| | |
| | |
| | |