| Date |
Text |
| 2007-12-24 13:06:35 | ** DENIEDREVIEW ** |
| | |
| | *** IMPORTANT** |
| | AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR REVIEW, |
| | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH |
| | CAN NOT BE MADE AT THIS TIME. |
| | |
| | ** THE FOLLOWING COMMENTS ARE BASED ON PLANS SUBMITTED |
| | ONLY. |
| | |
| | 1) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN |
| | THE FOLLOWING ADOPTED CODES BY THE STATE. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE THE TITLE BLOCK FOR THE ENGINEERING |
| | FIRM IS MISSING THE PRINTED NAME AND PRINTED LICENSE |
| | NUMBER OF THE ENGINEER AS REQUIRED BY THE FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002 |
| | |
| | 3) NOTE: PLEASE SEE THE NEW SERVICE RISER AS SUBMITTED |
| | NEEDS SEVERAL ITEMS TO BE ADDRESSED: |
| | |
| | A) PLEASE SEE THE NEW MAIN DISCONNECT AND NEW PANEL FOR |
| | THE NEW GUEST HOUSE SHOWS 75AMP MAIN AND PANEL, HOWEVER |
| | THIS DOES NOT CORRELATE WITH THE STANDARD OVER CURRENT |
| | PROTECTION DEVICES OR EQUIPMENT AS STATED IN THE NEC |
| | 240.6. |
| | PLEASE ALSO SEE 110.3, 90.7 AND ADJUST. |
| | |
| | B) PLEASE INCLUDE THE SIZE (AMPERAGE) OF NEW METER. |
| | 90.7, 230.70, 230.71, 230.90 ETC |
| | |
| | C) PLEASE INCLUDE THE TAPPED CONDUCTORS FROM NEW |
| | SERVICE GUTTER TO NEW MAIN. 240.21, 240.4, 310.16 ETC |
| | |
| | D) PLEASE SEE MISSING REQUIRED DISCONNECTING MEANS AT |
| | THE MAIN HOUSE PER 225.31-225.39. |
| | |
| | E) PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM AT THE |
| | MAIN HOUSE PER 250.32, 250.50. |
| | |
| | F) PLEASE COMPLETE GROUNDING ELECTRODE AT THE SERVICE |
| | LOCATION. THE GROUNDING DETAIL ON E-2 NOTES GROUND RODS |
| | PER 250.83, AND 250.84 HOWEVER PLEASE SEE THE 2005 NEC, |
| | AS 250.83 DOES NOT EXIST AND 250.84 IS NOT FOR GROUND |
| | RODS. PLEASE ADJUST SYSTEM AND NOTES. |
| | |
| | 4) NOTE: PLEASE CLARIFY THE SMOKE DEVICES ON PLANS. |
| | PLEASE SEE THE SYMBOL AS SHOWN WHICH IS THE *S* IN THE |
| | BOX IS NOTED AS A DUCT DETECTOR ON SYMBOL LEGEND. |
| | PLEASE SEE R313 AND NFPA-72 11.5.1.1.1 AND 11.8.3 AS |
| | THESE SHOULD BE NOTED AS SA FOR SMOKE ALARMS. |
| | PLEASE SEE MISSING SA OUTSIDE BEDROOM AT THE GUEST |
| | HOUSE. |
| | PLEASE ADJUST NOTES AND PLANS. |
| | |
| | 5) NOTE: PLEASE SUBMIT PANEL SCHEDULES FOR BOTH THE NEW |
| | PANEL AT GUEST HOUSE AND THE NEW PANEL AT THE MAIN |
| | HOUSE. PLEASE SHOW ALL NEW MINIMUM CIRCUITS REQUIRED BY |
| | THE NEC ALONG WITH THE ADDITIONAL AND EXISTING |
| | CIRCUITS. PLEASE PROVIDE THE BRANCH CIRCUIT SIZE, OVER |
| | CURRENT PROTECTION RATING AND CONDUCTORS. |
| | PLEASE SEE SOME COMMENTS BELOW AS THE *LOAD SUMMARY* |
| | SUBMITTED CONTAIN ITEMS WHICH DO NOT MEET THE MINIMUM |
| | PER NEC. |
| | 408.4, 240.4, 310.16, ETC |
| | FBC 106.3.5.4 |
| | |
| | 6) NOTE: PLEASE SEE THE WATER HEATER AS SHOWN ON LOAD |
| | SUMMARY DOES NOT MEET 422.1AND422.13. PLEASE SEE THE |
| | LOAD IS SHOWN AT 6KW YET THE OVER CURRENT PROTECTION IS |
| | SHOWN AS A 20AMP BREAKER. |
| | ** PLEASE ALSO SEE THE PLAN WHICH SHOWS 60AMP FOR THE |
| | WATER HEATER? |
| | ** IS THERE ARE WATER HEATER AT THE MAIN HOUSE? |
| | |
| | 7) NOTE: PLEASE SEE THE MINIMUM LOAD WHICH THE CODE |
| | REQUIRES FOR THE DRYER SHALL BE 5KW. PLEASE SEE NEC |
| | 220.54. |
| | PLEASE ALSO SEE THE SIZE OF THE CIRCUIT SHALL BE BASED |
| | ON THE LOAD AND VOLTAGE SUPPLIED. (SHOWS 20AMPS BREAKER |
| | WHICH IS NOT RATED FOR 5KW AT 240V). PLEASE ADJUST |
| | |
| | 8) NOTE: PLEASE SUBMIT REVISED LOAD CALCULATIONS FOR |
| | EACH PANEL AND FOR SERVICE. PLEASE CORRECT AS PER NOTES |
| | ABOVE PER NEC 220. |
| | FBC 106.3.5.4 |
| | |
| | 9) NOTE: PLEASE SEE DISCONNECT(S) SHOWN FOR CONDENSING |
| | UNITS DO NOT COMPLIANCE FOR 110.26. |
| | PLEASE RE-LOCATE |
| | |
| | 10) NOTE: PLEASE VERIFY THE GFI SHOWN ON PLANS AT THE |
| | MAIN HOUSE MEETING 210.63/210.8A FOR THE OUTSIDE |
| | CONDENSING UNIT. PLAN SHOWS THIS FOR A PUMP. IF THIS IS |
| | FOR THE PUMP, THE SERVICE RECEPTACLE AS REQUIRED PER |
| | SECTIONS GIVEN WOULD BE IN ADDITION TO THE DEDICATE GFI |
| | SUPPLIED FOR THE PUMP. |
| | |
| | 11) NOTE: PLEASE SEE NEC 680.22 AS THE LIGHTING |
| | FIXTURES SHOWN ON MAIN HOUSE AND GUEST HOUSE DO NOT |
| | MEET THE MINIMUM DISTANCES PER SECTION GIVEN. |
| | |
| | 12) NOTE: PLEASE SEE THE EGRESS LIGHTING CONTROL AT THE |
| | GUEST HOUSE MUST BE INSIDE THE ROOM (OFFICE) AS SHOWN |
| | PER 210.70. |
| | |
| | 13) NOTE: PLEASE SEE NEC2005 210.12 WHICH REQUIRED |
| | AFCI PROTECTION FOR ALL OUTLETS IN BEDROOM/SLEEPING |
| | ROOMS. THIS INCLUDES ALL RECEPTACLES, LIGHTS, FANS, |
| | SMOKE ALARMS ETC. |
| | PLEASE SEE THE PLANS ONLY SHOW PROTECTION FOR |
| | RECEPTACLES WHICH WAS IN THE 2002 NEC. |
| | PLEASE LIST ON THE BRANCH CIRCUITS TO BE PROVIDED ON |
| | THE NEW PANEL SCHEDULES TO BE SUBMITTED. |
| | |
| | 14) NOTE: PLEASE SUBMIT AND SHOW THE REQUIRED AIC |
| | RATING FOR SERVICE MAINS AND EQUIPMENT PER 110.9. |
| | |
| | 15) NOTE: PLEASE PROVIDE NOTE FOR TYPE OF RECESSED |
| | LIGHTING FIXTURES PER 13-606.1.ABC.1.2.4 |
| | |
| | 16) NOTE: PLEASE SEE THERE ARE SEVERAL GFI RECEPTACLES |
| | ON PLAN WHICH SHOWS THE SYMBOL FOR HALF SWITCHED |
| | DEVICE. GFI RECEPTACLES CAN NOT BE HALF SWITCHED. |
| | 110.3 |
| | |
| | 17) NOTE: PLEASE SEE MISSING RECEPTACLE IN OFFICE ALONG |
| | 2FT OF WALL PER 210.52 |
| | |
| | 18) NOTE: PLEASE SEE REQUIRED DEDICATED CIRCUIT(S) FOR |
| | BATH ROOMS TO BE CONFIRMED ON NEW PANEL SCHEDULES. |
| | PLEASE SEE 210.11C3 AS THESE ARE REQUIRED TO BE 20AMP |
| | AND #12. |
| | |
| | ** AS NOTED ABOVE, PLEASE KNOW AS THERE ARE MANY ITEMS |
| | NOT SUBMITTED OR SHOWN, A COMPLETER REVIEW FOR CODE |
| | COMPLIANCE CAN NOT BE DONE AT THIS TIME.** IF THERE ARE |
| | QUESTIONS, PLEASE CALL. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |