| 2008-01-07 17:26:11 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY SHALL |
| | BE PROVIDED WITH NATURAL OR MECHANICAL VENTILATION OR |
| | EXHAUST IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, |
| | MECHANICAL PER FBC, EB 609.1. O.A. CALCULATIONS AS |
| | SHOWN ON PLANS REFERENCE ASHRAE 62-89. THE CURRENT AND |
| | CORRECT REFERENCE STANDARD IS ASHRAE 62.1-2004. THE |
| | CALCULATIONS MAY BE BASED ON THIS STANDARD OR FBC, M |
| | TABLE 403.3. IF ASHRAE 62.1-2004 IS USED, INDICATE |
| | WHETHER THE AIRFLOW RATE OR IAQ METHOD IS USED. ALSO, |
| | NOTE #1 INDICATES THE CALCULATIONS ARE BASED ON THE |
| | MAX. ESTIMATED OCCUPANT RATES PER ARCHITECTURAL PLANS. |
| | ARCHITECTURAL PLANS PUT THE OCCUPANCY AT 121 PERSONS. |
| | THE OCCUPANCY MAY BE FIGURED BASED ON ASHRAE OR TABLE |
| | 403.3 RATHER THAN ARCHITECTURAL PLANS. |
| | |
| | 2. AC-2: FIRE DAMPER INSTALLATION DETAIL DOES NOT |
| | APPEAR TO BE SPECIFIC TO ANY BRAND OR MANUFACTURER. |
| | FIRE DAMPERS LOCATED WITHIN AIR DISTRIBUTION SYSTEMS |
| | SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| | MANUFACTURER?S INSTALLATION INSTRUCTIONS AND LISTING. |
| | IF THE DETAIL ON PLANS DOES NOT CONFORM TO THE |
| | MANUFACTURER?S INSTRUCTIONS, PLEASE REMOVE AND REPLACE |
| | WITH THE APPROPRIATE DETAIL OR A NOTE MAY BE PROVIDED |
| | WHICH DEFERS TO THE FIRE DAMPER MANUFACTURER?S |
| | INSTALLATION INSTRUCTIONS. SEE FBC, M 607.2. |
| | MANUFACTURER?S INSTALLATION INSTRUCTIONS SHALL BE |
| | AVAILABLE ON THE JOB SITE AT THE TIME OF INSPECTION IN |
| | ACCORDANCE WITH FBC, M 304.1. |
| | |
| | 3. AC-1 AND AC-2 ARE NOT SIGNED AND SEALED BY THE |
| | DESIGNER OF RECORD. A PROFESSIONAL ENGINEER SHALL SIGN |
| | HIS NAME AND AFFIX HIS SEAL TO ALL PLANS AND |
| | SPECIFICATIONS PROVIDED TO THE OWNER OR THE OWNER?S |
| | REPRESENTATIVE AND BEING FILED FOR PUBLIC RECORD. THE |
| | DATE THAT THE SIGNATURE AND SEAL IS AFFIXED AS PROVIDED |
| | HEREIN SHALL BE ENTERED ON SAID PLANS AND |
| | SPECIFICATIONS IMMEDIATELY UNDER THE SIGNATURE OF THE |
| | PROFESSIONAL ENGINEER IN ACCORDANCE WITH F.A.C. RULE |
| | 61G15-23.002 |
| | |