2008-01-07 17:26:11REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY SHALL
 BE PROVIDED WITH NATURAL OR MECHANICAL VENTILATION OR
 EXHAUST IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL PER FBC, EB 609.1. O.A. CALCULATIONS AS
 SHOWN ON PLANS REFERENCE ASHRAE 62-89. THE CURRENT AND
 CORRECT REFERENCE STANDARD IS ASHRAE 62.1-2004. THE
 CALCULATIONS MAY BE BASED ON THIS STANDARD OR FBC, M
 TABLE 403.3. IF ASHRAE 62.1-2004 IS USED, INDICATE
 WHETHER THE AIRFLOW RATE OR IAQ METHOD IS USED. ALSO,
 NOTE #1 INDICATES THE CALCULATIONS ARE BASED ON THE
 MAX. ESTIMATED OCCUPANT RATES PER ARCHITECTURAL PLANS.
 ARCHITECTURAL PLANS PUT THE OCCUPANCY AT 121 PERSONS.
 THE OCCUPANCY MAY BE FIGURED BASED ON ASHRAE OR TABLE
 403.3 RATHER THAN ARCHITECTURAL PLANS.
  
 2. AC-2: FIRE DAMPER INSTALLATION DETAIL DOES NOT
 APPEAR TO BE SPECIFIC TO ANY BRAND OR MANUFACTURER.
 FIRE DAMPERS LOCATED WITHIN AIR DISTRIBUTION SYSTEMS
 SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS AND LISTING.
 IF THE DETAIL ON PLANS DOES NOT CONFORM TO THE
 MANUFACTURER?S INSTRUCTIONS, PLEASE REMOVE AND REPLACE
 WITH THE APPROPRIATE DETAIL OR A NOTE MAY BE PROVIDED
 WHICH DEFERS TO THE FIRE DAMPER MANUFACTURER?S
 INSTALLATION INSTRUCTIONS. SEE FBC, M 607.2.
 MANUFACTURER?S INSTALLATION INSTRUCTIONS SHALL BE
 AVAILABLE ON THE JOB SITE AT THE TIME OF INSPECTION IN
 ACCORDANCE WITH FBC, M 304.1.
  
 3. AC-1 AND AC-2 ARE NOT SIGNED AND SEALED BY THE
 DESIGNER OF RECORD. A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL PLANS AND
 SPECIFICATIONS PROVIDED TO THE OWNER OR THE OWNER?S
 REPRESENTATIVE AND BEING FILED FOR PUBLIC RECORD. THE
 DATE THAT THE SIGNATURE AND SEAL IS AFFIXED AS PROVIDED
 HEREIN SHALL BE ENTERED ON SAID PLANS AND
 SPECIFICATIONS IMMEDIATELY UNDER THE SIGNATURE OF THE
 PROFESSIONAL ENGINEER IN ACCORDANCE WITH F.A.C. RULE
 61G15-23.002
  