| Plan Review Notes For Permit 07120421 |
| Permit Number |
07120421 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-01-05 23:17:30 | *****DENIED***** | | | | | | 1.THE LIFE SAFETY PLAN (SHEET A1) DOES NOT SHOW THE | | | TRAVEL DISTANCES TO THE EXITS. | | | | | | 2.COULD NOT LOCATE PLAN SHEETS FP1 AND FP2 AS | | | INDICATED IN THE SHEET INDEX SECTION (SHEET A1). | | | | | | 3.PLAN SHEETS E-1, E-2, E-3, AC-1 AND AC-2 ARE NOT | | | SIGNED, SEALED, AND DATED IN ONE (OF TWO) SET OF | | | PLANS. | | | | | | 4.SHOW THE LOCATION OF THE 2A:BC RATED FIRE | | | EXTINGUISHERS WHICH SATISFY THE 75' TRAVEL DISTANCE. | | | SINCE A SYMBOL LEGEND IS ABSENT, NOT SURE IF THE | | | CIRCLED FE LOCATED IN THE PHONE/IT ROOM ON SHEET D3 | | | REPRESENTS A FIRE EXTINGUISHER. | | | | | | 5.SPECIFY THE INTERIOR FINISH MATERIAL FOR THE WALLS | | | AND CEILING IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 6.SUBMIT A LAYOUT OF THE FIRE SPRINKLER SYSTEM AS IT | | | RELATES TO THE SCOPE OF WORK BEING CONDUCTED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDIATING WHERE/HOW EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|