Plan Review Notes
Plan Review Notes For Permit 07120421
Permit Number 07120421
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-23 15:45:21** DENIEDREVIEW **
  
 8TH FLOOR/SUITE # 800
  
  
 1) NOTE: PLEASE KNOW THE PLANS/PERMIT APPLICATION HAS
 BEEN ROUTED TO THE ADDRESSING REVIEWER FOR CONFORMATION
 OF SUITE/UNIT # SHOWN ON PLANS.
 THE APPLICATION STATES 8TH FLOOR HOWEVER AS SCOPE OF
 WORK IS NOT FOR COMMON AREA AND FOR A TENANT, THE
 SUITE/UNIT NUMBER WILL BE ASSIGNED.
  
 2) NOTE: PLEASE SEE POSSIBLE NOTES FROM BUILDING WITH
 RESPECT TO ANY DESIGNS BY LICENSED INTERIOR DESIGNER
 UNDER FS 481.2131
  
 3) NOTE: PLEASE SEE PLANS SUBMITTED ARE NOT SIGNED,
 DATED OR SEALED BY THE ELECTRICAL ENGINEER OF RECORD AS
 REQUIRED PER FAC 61G15-23.002, FS 471.025
  
 4) NOTE: PLEASE SHOW AND INDICATE ALL ROOM AND AREA
 DESIGNATIONS ON PLANS. PLEASE KNOW THAT SOME ITEMS CAN
 NOT BE REVIEWED FOR MINIMUM CODE AT THIS TIME.
 240.4, 408.17, 110.26 ETC
 FBC 106.1.2 ADDITIONAL INFORMATION.
  
 5) NOTE: PLEASE BE SURE ONCE ALL ROOMS AND AREAS ARE
 SHOWN TO PLEASE BE SURE ALL CIRCUITS ON PANEL SCHEDULES
 ARE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED.
 PLEASE SEE 408.4 OFTHE 2005 NEC.
 FBC 106.3.5.1.2
  
 6) NOTE: PLEASE SHOW LIGHTING POWER DENSITIES FOR
 EXISTING AND NEW LIGHTING BEFORE NEW LIGHTING MAY BE
 ADDED.
 PLEASE SEE 13-415.2.
 PLEASE KNOW AS THE SPACE ALREADY CONTAINS CONDITIONED
 SPACE, WE ONLY NEED THE LIGHTING PERFORMANCE
 CALCULATIONS.
  
 7)NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND
 PLACES NOTES ON PLANS ACCORDINGLY.
 THE NOTE ON E- #7 NEEDS TO BE EXPANDED UPON.
  
 8) NOTE: PLEASE INDICATE MAXIMUM TIMES ON OCCUPANCY
 DEVICES AS SHOWN ON PLANS ALONG WITH SWITCHING DEVICES
 SHOWN.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2.
 PLANS SYMBOL LEGEND CAN BE USED TO INCLUDE TIMES.
  
 9) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3(4) FOR
 MINIMUM DEVICES AND LEVELS OF DEVICES FOR ADA
 COMPLIANCE.
 PLEASE INDICATE ON PLANS EVEN AS ANY FIRE ALARM SYSTEM
 WORK IS REQUIRED UNDER SEPARATE PERMIT.
 THE BASE PLANS ARE REQUIRED TO SHOW MINIMUM DESIGN.
  
 10) NOTE: PLEASE SEE NO PANEL SCHEDULE WAS SUBMITTING
 FOR PANEL L4D. PLEASE SEE NOTES 4 AND 5 ABOVE AND
 COORDINATE.
 408.4, 310.16, 240.4 ETC
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION.
  
 11) NOTE: PLEASE SEE PANEL SCHEDULE FOR PANEL L4C
 INDICATES THIS AS 400AMP MLO, WHEN THE RISER SHOWS THIS
 AS 225AMP MLO.
 PLEASE COORDINATE AND ADJUST.
 FBC 106.1.2
  
 12) NOTE: PLEASE VERIFY PLANS SHOWING AN *IT ROOM*. IF
 THIS ROOM MEETS THE DEFINITIONS OF AN IT AS STATED IN
 645.4, PLEASE SHOW. IF THIS DOES NOT PLEAS ADJUST
 DESIGNATION AS ROOM WILL BE REQUIRED TO BE COMPLY WITH
 MORE STRINGENT WIRING METHODS PER CHAPTERS 1-4 OF THE
 NEC.
  
 13) NOTE: PLEASE SEE PLANS ON E-2 IN TRAINING ROOM 21
 SHOWS A MDF, DISCONNECT AND TRANSFORMER YET THE RISER
 AND PANEL SCHEDULES DO NOT INCLUDE ANY OF THESE.
 PLEASE COMPLETE PLANS.
 310.16, 240.4, 240.21, 408.4, 110.26, ETC
 FBC 106.3.5.1.2
  
  
  
 *** IMPORTANT**
 AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR REVIEW,
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  