2008-01-17 14:27:30BUILDING PLAN REVIEW
 PERMIT: 07120421
 ADD: 1700 PBL BLVD. #8TH FL.
 CONT: HOLT LEE CONST.
 TEL: (954)725-4881
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2)FBC 1013.4.1 THE CLEAR AISLE WIDTH SHALL NOT BE
 LESS THAN 36 INCHES. SEE SHEET A1 IN THE AREA OF 24C
 WHERE THE COLUMN IS BLOCKING MORE THAN HALF THE AISLE
 WIDTH.
  
 3)THE DRAWINGS SUBMITTED HAVE TO BE DONE BY AN
 ARCHITECT OR ENGINEER. THE SCOPE OF WORK INDICATED ON
 THE DRAWINGS SUBMITTED IS NOT IN THE SCOPE OF AN
 INTERIOR DESIGNER PER FS 481.2131. SEE INFORMATION
 ATTACHED.
  
 4)PROVIDE ARCHITECTURAL DRAWINGS SHOWING ALL WALLS TO
 BE DEMOED AND ALL WALLS TO BE CONSTRUCTED. A WALL
 LEGEND SHALL BE SUBMITTED INDICATING THE NEW WALLS,
 DEMOED WALLS, CONNECTION DETAIL, STUD SPACING AND ALL
 MATERIALS. PROVIDE INFORMATION SHOWING HOW THE CEILING
 WILL BE ATTACHED TO THE STRUCTURE ABOVE. CONSTRUCTION
 DOCUMENTS SHALL BE DIMENSIONED AND BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS. FBC 106.1.1.
  
 5)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY.
  
 6)61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
 NOTE: SOME PAGES ARE MISSING THE INFORMATION ABOVE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]