Plan Review Notes
Plan Review Notes For Permit 07120418
Permit Number 07120418
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-01-05 23:51:26*****DENIED*****
  
 1.THE PLANS SHOW WORK BEING DONE IN SUITE 500 AND
 510, HOWEVER THE SUITE NUMBER SHOWN IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET IS FOR SUITE 500 ONLY.
 PLEASE EXPLAIN.
  
 2.ON SHEET A1 IN THE DATA FOR THE SCOPE OF
 WORK/LOCATION MAP, OCCUPANCY CALC IS GIVEN FOR SUITE
 501.SHOULD THIS BE SUITE 510 INSTEAD?
  
 3.COULD NOT LOCATE PLAN SHEET FP1 AS INDICATED IN THE
 SHEET INDEX SECTION (SHEET A1).
  
 4.SHOW THE LOCATION OF THE 2A:BC RATED FIRE
 EXTINGUISHERS WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
 5.SPECIFY THE INTERIOR FINISH MATERIAL FOR THE WALLS
 AND CEILING IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 6.SUBMIT A LAYOUT OF THE FIRE SPRINKLER SYSTEM AS IT
 RELATES TO THE SCOPE OF WORK BEING CONDUCTED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDIATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW