| Plan Review Notes For Permit 07120418 |
| Permit Number |
07120418 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-01-05 23:51:26 | *****DENIED***** | | | | | | 1.THE PLANS SHOW WORK BEING DONE IN SUITE 500 AND | | | 510, HOWEVER THE SUITE NUMBER SHOWN IN THE TITLE BLOCK | | | OF EACH SUBMITTED PLAN SHEET IS FOR SUITE 500 ONLY. | | | PLEASE EXPLAIN. | | | | | | 2.ON SHEET A1 IN THE DATA FOR THE SCOPE OF | | | WORK/LOCATION MAP, OCCUPANCY CALC IS GIVEN FOR SUITE | | | 501.SHOULD THIS BE SUITE 510 INSTEAD? | | | | | | 3.COULD NOT LOCATE PLAN SHEET FP1 AS INDICATED IN THE | | | SHEET INDEX SECTION (SHEET A1). | | | | | | 4.SHOW THE LOCATION OF THE 2A:BC RATED FIRE | | | EXTINGUISHERS WHICH SATISFY THE 75' TRAVEL DISTANCE. | | | | | | 5.SPECIFY THE INTERIOR FINISH MATERIAL FOR THE WALLS | | | AND CEILING IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 6.SUBMIT A LAYOUT OF THE FIRE SPRINKLER SYSTEM AS IT | | | RELATES TO THE SCOPE OF WORK BEING CONDUCTED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDIATING WHERE/HOW EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|