Plan Review Notes
Plan Review Notes For Permit 07120418
Permit Number 07120418
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-23 16:08:23** DENIEDREVIEW **
  
 SUITE(S) 500/510
  
 1) NOTE: PLEASE KNOW THE PLANS/PERMIT APPLICATION NEED
 TO COORDINATE. PLEASE SEE APPLICATION AND SCOPE ON
 PLANS APPEARS TO BE IN TWO SEPARATE SUITES/UNITS
 ALTHOUGH TITLE BLOCKS ON SHEETS ONLY INDICATE SUITE
 #500.?
 PLEASE ADJUST AS NEEDED.
 FBC 106.5, 106.1.2,
 FAC 61G15-23.002
  
 2) NOTE: PLEASE CORRELATE RISER AND PANELS.
 PLEASE SEE RISER SHOWS L1 WHICH CONTAINS A 400AMP MCB
 WITH 500MCM FEEDERS TO PANEL *L1A WHICH IS ONLY RATED
 AT 250AMP MLO. WHAT IS THE OVER CURRENT PROTECTION FROM
 L1 TO L1A?
 240.4, 310.16,ETC
 THE OCP IF 400AMP AT L1 IS TOO HIGH FOR THE 250AMP
 RATED PANEL.
 110.3, 90.7
  
 3) NOTE: PLEASE ALSO SEE PANEL L1A WHICH SHOWS THE
 FEEDERS AND FEED-THRU LUGS FROM THIS PANEL TO PANEL
 L1B. PANEL L1B IS ONLY RATED FOR 100AMPS AND IS A MLO
 PANEL AS SHOWN ON RISER.
 PLEASE SEE THE PANEL SCHEDULE SHOWN FOR L1B HOWEVER IS
 SHOWN AS 400AMP MLO??
 PLEASE CLARIFY ALL SERVICE AND RISER EQUIPMENT AND
 COORDINATE FOR MINIMUM CODE COMPLIANCE.
 PLEASE SEE 220,230,240,310.16,240.4, 90.7, 110.3 ETC
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION OF PLANS.
  
 4) NOTE: PLEASE SEE 700.12F AS EMERGENCY AND EXIT
 LIGHTS SHALL BE CIRCUITED TO THE LOCAL LIGHTING BRANCH
 CIRCUIT IN ANY ONE AREA.
  
 5) NOTE: PLEASE SHOW LIGHTING POWER DENSITIES FOR
 EXISTING AND NEW LIGHTING BEFORE NEW LIGHTING MAY BE
 ADDED.
 PLEASE SEE AREAS WHERE ALL NEW LIGHTING IS BEING ALSO
 NEEDS TO BE VERIFIED.
 PLEASE SEE 13-415.2.
 PLEASE KNOW AS THE SPACE ALREADY CONTAINS CONDITIONED
 SPACE, WE ONLY NEED THE LIGHTING PERFORMANCE
 CALCULATIONS.
  
 6)NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND
 PLACES NOTES ON PLANS ACCORDINGLY.
 THE NOTE ON E- #7 NEEDS TO BE EXPANDED UPON.
  
 7) NOTE: PLEASE INDICATE MAXIMUM TIMES ON OCCUPANCY
 DEVICES AS SHOWN ON PLANS ALONG WITH SWITCHING DEVICES
 SHOWN.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2.
 PLANS SYMBOL LEGEND CAN BE USED TO INCLUDE TIMES.
  
 8) NOTE: (ONLY NOTED FOR NEW DEVICES BEING RELOCATED OR
 INSTALLED NEW).
 PLEASE SEE FBC 11-4.28.1,.2 AND .3(4) FOR MINIMUM
 DEVICES AND LEVELS OF DEVICES FOR ADA COMPLIANCE.
 PLEASE INDICATE ON PLANS EVEN AS ANY FIRE ALARM SYSTEM
 WORK IS REQUIRED UNDER SEPARATE PERMIT.
 THE BASE PLANS ARE REQUIRED TO SHOW MINIMUM DESIGN.
  
 9) NOTE: PLEASE SEE NO PANEL SCHEDULE WAS SUBMITTING
 FOR PANEL L1A. DUE TO THE NOTES ON RISER AND
 COORDINATION PLEAS SUBMIT.
 408.4, 310.16, 240.4, 240.21 ETC
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION.
  
  
 *** IMPORTANT**
 AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR REVIEW,
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved