| Date |
Text |
| 2007-12-23 16:08:23 | ** DENIEDREVIEW ** |
| | |
| | SUITE(S) 500/510 |
| | |
| | 1) NOTE: PLEASE KNOW THE PLANS/PERMIT APPLICATION NEED |
| | TO COORDINATE. PLEASE SEE APPLICATION AND SCOPE ON |
| | PLANS APPEARS TO BE IN TWO SEPARATE SUITES/UNITS |
| | ALTHOUGH TITLE BLOCKS ON SHEETS ONLY INDICATE SUITE |
| | #500.? |
| | PLEASE ADJUST AS NEEDED. |
| | FBC 106.5, 106.1.2, |
| | FAC 61G15-23.002 |
| | |
| | 2) NOTE: PLEASE CORRELATE RISER AND PANELS. |
| | PLEASE SEE RISER SHOWS L1 WHICH CONTAINS A 400AMP MCB |
| | WITH 500MCM FEEDERS TO PANEL *L1A WHICH IS ONLY RATED |
| | AT 250AMP MLO. WHAT IS THE OVER CURRENT PROTECTION FROM |
| | L1 TO L1A? |
| | 240.4, 310.16,ETC |
| | THE OCP IF 400AMP AT L1 IS TOO HIGH FOR THE 250AMP |
| | RATED PANEL. |
| | 110.3, 90.7 |
| | |
| | 3) NOTE: PLEASE ALSO SEE PANEL L1A WHICH SHOWS THE |
| | FEEDERS AND FEED-THRU LUGS FROM THIS PANEL TO PANEL |
| | L1B. PANEL L1B IS ONLY RATED FOR 100AMPS AND IS A MLO |
| | PANEL AS SHOWN ON RISER. |
| | PLEASE SEE THE PANEL SCHEDULE SHOWN FOR L1B HOWEVER IS |
| | SHOWN AS 400AMP MLO?? |
| | PLEASE CLARIFY ALL SERVICE AND RISER EQUIPMENT AND |
| | COORDINATE FOR MINIMUM CODE COMPLIANCE. |
| | PLEASE SEE 220,230,240,310.16,240.4, 90.7, 110.3 ETC |
| | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION OF PLANS. |
| | |
| | 4) NOTE: PLEASE SEE 700.12F AS EMERGENCY AND EXIT |
| | LIGHTS SHALL BE CIRCUITED TO THE LOCAL LIGHTING BRANCH |
| | CIRCUIT IN ANY ONE AREA. |
| | |
| | 5) NOTE: PLEASE SHOW LIGHTING POWER DENSITIES FOR |
| | EXISTING AND NEW LIGHTING BEFORE NEW LIGHTING MAY BE |
| | ADDED. |
| | PLEASE SEE AREAS WHERE ALL NEW LIGHTING IS BEING ALSO |
| | NEEDS TO BE VERIFIED. |
| | PLEASE SEE 13-415.2. |
| | PLEASE KNOW AS THE SPACE ALREADY CONTAINS CONDITIONED |
| | SPACE, WE ONLY NEED THE LIGHTING PERFORMANCE |
| | CALCULATIONS. |
| | |
| | 6)NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND |
| | PLACES NOTES ON PLANS ACCORDINGLY. |
| | THE NOTE ON E- #7 NEEDS TO BE EXPANDED UPON. |
| | |
| | 7) NOTE: PLEASE INDICATE MAXIMUM TIMES ON OCCUPANCY |
| | DEVICES AS SHOWN ON PLANS ALONG WITH SWITCHING DEVICES |
| | SHOWN. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2. |
| | PLANS SYMBOL LEGEND CAN BE USED TO INCLUDE TIMES. |
| | |
| | 8) NOTE: (ONLY NOTED FOR NEW DEVICES BEING RELOCATED OR |
| | INSTALLED NEW). |
| | PLEASE SEE FBC 11-4.28.1,.2 AND .3(4) FOR MINIMUM |
| | DEVICES AND LEVELS OF DEVICES FOR ADA COMPLIANCE. |
| | PLEASE INDICATE ON PLANS EVEN AS ANY FIRE ALARM SYSTEM |
| | WORK IS REQUIRED UNDER SEPARATE PERMIT. |
| | THE BASE PLANS ARE REQUIRED TO SHOW MINIMUM DESIGN. |
| | |
| | 9) NOTE: PLEASE SEE NO PANEL SCHEDULE WAS SUBMITTING |
| | FOR PANEL L1A. DUE TO THE NOTES ON RISER AND |
| | COORDINATION PLEAS SUBMIT. |
| | 408.4, 310.16, 240.4, 240.21 ETC |
| | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | |
| | *** IMPORTANT** |
| | AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR REVIEW, |
| | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH |
| | CAN NOT BE MADE AT THIS TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |