| 2007-12-26 11:59:19 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07120384 |
| | ADD: 2800 N. FLAGLER DR. #412 |
| | CONT: R.W. MORRELL |
| | TEL: (561)714-8216 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)THE CERTIFICATE OF AUTHORIZATION IS MISSING FROM |
| | THE DRAWINGS. ANY PERSON PRACTICING UNDER A FICTITIOUS |
| | NAME, OFFERING ARCHITECTURAL SERVICES TO THE PUBLIC |
| | SHALL DISPLAY THEIR CERTIFICATE OF AUTHORIZATION NUMBER |
| | ON SAID INFORMATION. FLORIDA STATUTES 481.219 AND |
| | F.A.C. 61G1-16.004. |
| | |
| | 3)THE DIMENSION OF THE WINDOW SHALL BE INDICATED ON |
| | THE DRAWINGS PER FBC 106.1.1. |
| | |
| | 4)106.3.3* PRODUCT APPROVALS- 2004 |
| | THOSE PRODUCTS THAT ARE REGULATED BY DCA RULE 9B-72 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. THE PRODUCT APPROVALS ARE |
| | MISSING THE APPROVAL SIGNATURE OF THE DESIGNER OF |
| | RECORD. |
| | |
| | NOTE: SEE MIAMI DADE NOA #05-1018-01 WHICH HAS MORE |
| | INFORMATION THE WINDOW SUBMITTED. YOU MAY ALSO SUBMIT |
| | NOA ALONG THE FL#2769.FROM THE NOA CIRCLE THE WINDOW |
| | WHICH WILL BE INSTALLED AND ALL INFORMATION PERTAINING |
| | TO THE INSTALLATION. |
| | |
| | 5) THE DESIGN PRESSURES FOR ALL BUILDINGS OVER 60 FEET |
| | SHALL BE CALCULATED BY A PROFESSIONAL ENGINEER USING |
| | ASCE 7 AND EXPOSURE A, B OR C DEPENDING ON THE LOCATION |
| | OF THE BUILDING. THE DESIGN PROFESSIONAL SHALL INDICATE |
| | THE DESIGN PRESSURES FOR THE WINDOWS. THE MEAN ROOF |
| | HEIGHT AND EXPOSURE CATEGORY SHALL BE STATED ON THE |
| | PLANS PER FBC 1609. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |