Plan Review Notes
Plan Review Notes For Permit 07120350
Permit Number 07120350
Review Stop B
Sequence Number 6
Notes
Date Text
2008-06-02 15:20:36BUILDING PLAN REVIEW
 PERMIT: 07120350
 ADD:223 CLEMATIS ST
 CONT: CASTLE FLORIDA
 TEL: (561)441-0492/ MARK
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: DENIED
 1) THIS REVISION INDICATES THAT HIGH HAT FIXTURES ARE
 GOING TO BE GOING THROUGH A 1 HR RATED CEILING, BUT NO
 INFORMATION WAS SUBMITTED TO THE BUILDING DEPARTMENT AS
 TO HOW TO MAINTAIN THE 1 HR RATING.
 711.5 PENETRATIONS.PENETRATIONS THROUGH
 FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLIES SHALL
 COMPLY WITH SECTION 712.
  
 712.4 HORIZONTAL ASSEMBLIES.
  
 PENETRATIONS OF A FLOOR, FLOOR/CEILING ASSEMBLY OR THE
 CEILING MEMBRANE OF A ROOF/CEILING ASSEMBLY SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 707 . PENETRATIONS
 PERMITTED BY EXCEPTIONS 3 AND 4 OF SECTION 707.2 SHALL
 COMPLY WITH SECTIONS 712.4.1 THROUGH 712.4.4 .
 EXCEPTION: PENETRATIONS LOCATED WITHIN THE SAME ROOM OR
 UNDIVIDED AREA AS FLOOR OPENINGS ARE NOT REQUIRED TO
 HAVE A SHAFT ENCLOSURE IN ACCORDANCE WITH EXCEPTION 1,
 2, 5, 7, 8 OR 9 IN SECTION 707.2 .
  
 712.4.1 THROUGH PENETRATIONS.
 THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED
 HORIZONTAL ASSEMBLIES SHALL COMPLY WITH SECTION
 712.4.1.1 OR 712.4.1.2 .
  
 712.4.1.1 FIRE-RESISTANCE-RATED ASSEMBLIES.
 PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN
 APPROVED FIRE-RESISTANCE-RATED ASSEMBLY.
  
 712.4.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM.
 THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLED AND
 TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A
 MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH
 (2.49 PA) OF WATER. THE SYSTEM SHALL HAVE AN F RATING
 AND A T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS
 THAN THE REQUIRED RATING OF THE FLOOR PENETRATED.
 EXCEPTION: FLOOR PENETRATIONS CONTAINED AND LOCATED
 WITHIN THE CAVITY OF A WALL DO NOT REQUIRE A T RATING.
  
  
 712.4.2 MEMBRANE PENETRATIONS.
 PENETRATIONS OF MEMBRANES THAT ARE PART OF A
 FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLY SHALL COMPLY
 WITH SECTION 712.4.1.1 OR 712.4.1.2 . WHERE
 FLOOR/CEILING ASSEMBLIES ARE REQUIRED TO HAVE A MINIMUM
 1-HOUR FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL
 BE INSTALLED SUCH THAT THE REQUIRED FIRE RESISTANCE
 WILL NOT BE REDUCED.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.