| 2008-06-02 15:20:36 | BUILDING PLAN REVIEW |
| | PERMIT: 07120350 |
| | ADD:223 CLEMATIS ST |
| | CONT: CASTLE FLORIDA |
| | TEL: (561)441-0492/ MARK |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVISIONREVIEW |
| | ACTION: DENIED |
| | 1) THIS REVISION INDICATES THAT HIGH HAT FIXTURES ARE |
| | GOING TO BE GOING THROUGH A 1 HR RATED CEILING, BUT NO |
| | INFORMATION WAS SUBMITTED TO THE BUILDING DEPARTMENT AS |
| | TO HOW TO MAINTAIN THE 1 HR RATING. |
| | 711.5 PENETRATIONS.PENETRATIONS THROUGH |
| | FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLIES SHALL |
| | COMPLY WITH SECTION 712. |
| | |
| | 712.4 HORIZONTAL ASSEMBLIES. |
| | |
| | PENETRATIONS OF A FLOOR, FLOOR/CEILING ASSEMBLY OR THE |
| | CEILING MEMBRANE OF A ROOF/CEILING ASSEMBLY SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 707 . PENETRATIONS |
| | PERMITTED BY EXCEPTIONS 3 AND 4 OF SECTION 707.2 SHALL |
| | COMPLY WITH SECTIONS 712.4.1 THROUGH 712.4.4 . |
| | EXCEPTION: PENETRATIONS LOCATED WITHIN THE SAME ROOM OR |
| | UNDIVIDED AREA AS FLOOR OPENINGS ARE NOT REQUIRED TO |
| | HAVE A SHAFT ENCLOSURE IN ACCORDANCE WITH EXCEPTION 1, |
| | 2, 5, 7, 8 OR 9 IN SECTION 707.2 . |
| | |
| | 712.4.1 THROUGH PENETRATIONS. |
| | THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED |
| | HORIZONTAL ASSEMBLIES SHALL COMPLY WITH SECTION |
| | 712.4.1.1 OR 712.4.1.2 . |
| | |
| | 712.4.1.1 FIRE-RESISTANCE-RATED ASSEMBLIES. |
| | PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN |
| | APPROVED FIRE-RESISTANCE-RATED ASSEMBLY. |
| | |
| | 712.4.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. |
| | THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED |
| | THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLED AND |
| | TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A |
| | MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH |
| | (2.49 PA) OF WATER. THE SYSTEM SHALL HAVE AN F RATING |
| | AND A T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS |
| | THAN THE REQUIRED RATING OF THE FLOOR PENETRATED. |
| | EXCEPTION: FLOOR PENETRATIONS CONTAINED AND LOCATED |
| | WITHIN THE CAVITY OF A WALL DO NOT REQUIRE A T RATING. |
| | |
| | |
| | 712.4.2 MEMBRANE PENETRATIONS. |
| | PENETRATIONS OF MEMBRANES THAT ARE PART OF A |
| | FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLY SHALL COMPLY |
| | WITH SECTION 712.4.1.1 OR 712.4.1.2 . WHERE |
| | FLOOR/CEILING ASSEMBLIES ARE REQUIRED TO HAVE A MINIMUM |
| | 1-HOUR FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL |
| | BE INSTALLED SUCH THAT THE REQUIRED FIRE RESISTANCE |
| | WILL NOT BE REDUCED. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |