Plan Review Notes
Plan Review Notes For Permit 07120350
Permit Number 07120350
Review Stop E
Sequence Number 4
Notes
Date Text
2008-06-02 15:01:36** DENIEDREVISION**
  
  
 1) NOTE: PLEASE SUPPLY INFORMATION WITH RESPECT TO
 COVERING THE RECESSED LIGHTING AS SHOWN ON PLANS.
 PLEASE SUPPLY INFORMATION ON HOW THESE MATS WILL BE
 INSTALLED AND HOW THEY WILL AFFECT HEAT DISSIPATION.
 PLEASE SUPPLY FIXTURE SPECS ON RATING OF RECESSED
 FIXTURE WITH RESPECT TO HEAT AND AUTOMATIC SHUT OFF.
 PLEASE KNOW INSTALLING A RECESSED LIGHT FIXTURE IN
 AREAS OTHER THAN INTENDED DESIGN SPECIFICATIONS WILL
 CREATE A FIRE/LIFE SAFETY HAZARD.
 PLEASE REVIEW THE MANUFACTURES MINIMUM SPECIFICATIONS
 AND PLEASE REVISE WITHIN ELECTRICAL PLANS. NEC 110.3,
 410 PART VII (ALL).
 PLEASE SEE FBC CHAPTER 7 AND BUILDING REVIEW COMMENTS
 FOR MAINTAINING CEILING RATINGS WITH RECESSED LIGHTING.
 THIS IS ONLY NOTED AS BUILDING REVIEWER WILL NOTE.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  