| Plan Review Notes For Permit 07120350 |
| Permit Number |
07120350 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-28 16:52:58 | *****DENIED***** | | | | | | 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 2.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE NEW | | | HANDRAILS AND/OR GUARDRAILS. | | | | | | 3.STAIRS SHALL HAVE HAVE HANDRAILS ON BOTH SIDES. | | | | | | 4.NEW HANDRAILS SHALL BE INSTALLED TO PROVIDE A | | | CLEARANCE OF NOT LESS THAN 2 1/4" BETWEEN THE HANDRAIL | | | AND THE WALL TO WHICH IT IS FASTENED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHEAL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|