Plan Review Notes
Plan Review Notes For Permit 07120350
Permit Number 07120350
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-19 11:14:09** DENIED **
  
  
 1) NOTE: PLEASE SUBMIT LIGHTING PHOTO-METRICS MEETING
 THE MINIMUM REQUIREMENTS OF NFPA-101 7.8.1.3 AND
 7.9.2.2.
 PLEASE SEE A MINIMUM OF 10FT CANDLES UNDER NORMAL ARE
 REQUIRED AND THEN IS PERMITTED DOWN TO 1FT CANDLE UNDER
 EMERGENCY.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-33.004 FOR
 REQUIRED LIGHTING LEVELS IN DESIGN.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  