| Plan Review Notes For Permit 07120350 |
| Permit Number |
07120350 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-19 11:14:09 | ** DENIED ** | | | | | | | | | 1) NOTE: PLEASE SUBMIT LIGHTING PHOTO-METRICS MEETING | | | THE MINIMUM REQUIREMENTS OF NFPA-101 7.8.1.3 AND | | | 7.9.2.2. | | | PLEASE SEE A MINIMUM OF 10FT CANDLES UNDER NORMAL ARE | | | REQUIRED AND THEN IS PERMITTED DOWN TO 1FT CANDLE UNDER | | | EMERGENCY. | | | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-33.004 FOR | | | REQUIRED LIGHTING LEVELS IN DESIGN. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|