| Plan Review Notes For Permit 07120346 |
| Permit Number |
07120346 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-05-14 15:51:27 | REVISION TO MECHANICAL PLANS M-1, M-2, AND M-3. | | | | | | *** PROVISO *** | | | 1) 603.15 REGISTERS, GRILLES AND DIFFUSERS. | | | DUCT REGISTERS, GRILLES AND DIFFUSERS SHALL BE | | | INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S | | | INSTALLATION INSTRUCTIONS, AND SHALL HAVE A FLAME | | | SPREAD RATING NOT OVER 25 WITHOUT EVIDENCE OF CONTINUED | | | PROGRESSIVE COMBUSTION AND A SMOKE-DEVELOPED RATING NOT | | | OVER 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84. | | | BALANCING DAMPERS OR OTHER MEANS OF SUPPLY AIR | | | ADJUSTMENT SHALL BE PROVIDED IN THE BRANCH DUCTS OR AT | | | EACH INDIVIDUAL DUCT REGISTER, GRILLE OR DIFFUSER. | | | (PB-1). | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 |
|