2008-04-03 09:32:26REVISION TO MECHANICAL PLANS M-1, M-2, AND M-3.
  
 *** PROVISO ***
 1) 603.15 REGISTERS, GRILLES AND DIFFUSERS.
 DUCT REGISTERS, GRILLES AND DIFFUSERS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS, AND SHALL HAVE A FLAME
 SPREAD RATING NOT OVER 25 WITHOUT EVIDENCE OF CONTINUED
 PROGRESSIVE COMBUSTION AND A SMOKE-DEVELOPED RATING NOT
 OVER 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84.
 BALANCING DAMPERS OR OTHER MEANS OF SUPPLY AIR
 ADJUSTMENT SHALL BE PROVIDED IN THE BRANCH DUCTS OR AT
 EACH INDIVIDUAL DUCT REGISTER, GRILLE OR DIFFUSER.
  