| Plan Review Notes For Permit 07120341 |
| Permit Number |
07120341 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-22 14:18:39 | | | | | | | DENIED | | | | | | 1)PROVIDE THE CONFIGURATION OF ALL OPENINGS ON THE | | | DRAWING, SHOW WINDOW TYPES, SIZES AND IF ANY UNITS ARE | | | MULLED TOGETHER PROVIDE PRODUCT APPROVALS FOR THE | | | MULLIONS. | | | | | | 2)PROVIDE GLASS TYPE, KEEP IN MIND THAT THE DOOR AND | | | WINDOWS SHALL MEET THE DESIGN PRESSURE REQUIREMENTS OF | | | THE FOLLOWING COMMENT. | | | | | | 3)THE 2006 AMENDMENTS TO THE 2004 FBC REQUIRE | | | BUILDINGS LOCATED WITHIN EXP B TYPE TERRAIN THAT IS | | | DIRECTLY ADJACENT TO EXP C TYPE TERRAIN SUCH AS OPEN | | | GOLF COURSES AND BODIES OF WATER FOR A DISTANCE OF 600 | | | FEET OR MORE IN ANY QUADRANT TO BE IN AN EXP C | | | CATEGORY. | | | | | | 4)PROVIDE ENGINEERING FOR ANY NEW BUCK ATTACHMENT, | | | WHICH SHALL ALSO BE DESIGNED TO THE 140 MPH EXP C | | | CRITERIA | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|