2008-01-29 09:10:56****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1. ADDRESSED.
  
 2.SEE FBC1008.1.4; THE FLOOR OR LANDING ON EACH SIDE
 OF THE DOOR IS TO BE AT THE SAME ELEVATION.
  
 2ND REVIEW, PLANS HAVE BEEN REVISED TO STATE THAT THE
 FLOOR WILL BE LEVEL, BUT PROPOSED LANDING PLAN SHOWS A
 4" ELEVATION CHANGE.THIS DIMENSION IS IN CONFLICT
 WITH OTHER DETAILS AND LANGUAGE ON THE PLAN, AND IS IN
 CONFLICT WITH OUR TELEPHONE CONVERSATION.WITH THE
 ARCHITECT'S PERMISSION, THIS CAN BE REDLINED.
  
 3.ADDRESSED.
  
 4.ADDRESSED.
  
 5.PROVIDE A GUARDRAIL AND STAIR RAIL DETAIL TO SHOW
 COMPLIANCE WITH FBC1012.3.
  
 2ND REVIEW, RAMP SECTION "A", SHOWS A 2'8" DIMENSION
 AND IS LABELED HANDRAIL.THE HANDRAIL IS NOTED AS 42".
 IT IS NOT CLEAR WHAT THIS 2'8" DIMENSION IS FOR AS NO
 HANDRAIL IS SHOWN GRAPHICALLY AT THIS LOCATION.AS THE
 42" HANDRAIL/GUARDRAIL IS CODE COMPLIANT, AN NO OTHER
 HANDRAIL IS REQUIRED, THIS ITEM CAN BE REDLINED IF
 REQUESTED BY ARCHITECT.