| Plan Review Notes For Permit 07120301 |
| Permit Number |
07120301 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-01-02 15:43:04 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.PROVIDE INFORMATION REGARDING THE EXISTING BUILDING | | | AND THE PURPOSE OF THIS EXISTING DOOR.WAS THIS A | | | REQUIRED ACCESSIBLE EXIT?WHAT IS THE OCCUPANT LOAD | | | OF THE AREA SERVED? | | | | | | 2.SEE FBC1008.1.4; THE FLOOR OR LANDING ON EACH SIDE | | | OF THE DOOR IS TO BE AT THE SAME ELEVATION. | | | | | | 3.HANDRAILS ARE TO COMPLY WITH FBC1009.11 AND, IF | | | REQUIRED TO BE ACCESSIBLE, FBC11-4.9.4.NOTE THE LACK | | | OF HANDRAIL EXTENSIONS, HANDRAILS NOT CONTINUOUS. | | | | | | 4.SPECIFY DESIGN STRENGTH CRITERIA FOR GUARDRAILS AND | | | HANDRAILS, FBC1607. | | | | | | 5.PROVIDE A GUARDRAIL AND STAIR RAIL DETAIL TO SHOW | | | COMPLIANCE WITH FBC1012.3. | | | |
|