| Plan Review Notes For Permit 07120290 |
| Permit Number |
07120290 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-31 08:47:13 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | GAS PLAN REVIEW: | | | DENIED: | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. TWO COPIES OF SURVEY AND SITE PLAN INDICATING THE | | | PROPOSED LOCATION OF THE GENERATOR. GIVE DIMENSIONS | | | FROM PROPRTY LINES AND ALL STRUCTURES. INDICATE ANY | | | EASEMENTS INVOLVED. CONTACT THE WPB ZONING DEPARTMENT | | | FOR DETAILS REGARDING DETBACKS. | | | | | | 2. TWO COPIES OF MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS WITH SETBACK RECOMMENDATIONS FROM | | | STRUCTURES. | | | | | | 3. THE WATER HEATER SUBMITTAL DOES NOT HAVE A LISTING | | | FROM A NATIONALLY RECOGNIZED TESTING LABORATORY | | | (EXAMPLE= CSA, AGA). PLEASE PROVIDE THIS INFORMATION ON | | | THE RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] | | | |
|