Plan Review Notes
Plan Review Notes For Permit 07120290
Permit Number 07120290
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-28 10:36:25 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
  
 CITY OF WEST PALM BEACH RESIDENTIAL GENERATOR PLAN
 REVIEW
  
  
 ALL PERMIT APPLICATIONS MUST BE SUBMITTED TOGETHER TO
 EXPEDITE THE REVIEW PROCESS.TWO COPIES OF ALL PLANS,
 SURVEYS AND SPECIFICATIONS ARE REQUIRED. THE COST OF
 ALL EQUIPMENT AND LABOR MUST BE ENTERED AS VALUE PER
 108.3 WPB AMENDMENTS.
  
 1} SURVEY AND SITE PLANS INDICATING THE PROPOSED
 LOCATION OF THE GENERATOR. GIVE DIMENSIONS FROM
 PROPERTY LINES AND ALL STRUCTURES. INDICATE ANY
 EASEMENTS INVOLVED.CONTACT THE WPB ZONING DEPARTMENT
 FOR DETAILS REGARDING SETBACKS.
  
 2} AN APPLICATION FOR AN ELECTRICAL PERMIT MUST INCLUDE
 THE FOLLOWING:
  
 A) SITE PLAN INDICATING THE PHYSICAL LOCATION OF THE
 EQUIPMENT WITH REGARD TO THE SERVICE AND SEPARATE
 STRUCTURES. NOTE: DISCONNECT REQUIRED TO BE SERVICE
 RATED PER 225.36. THIS INCLUDES THE TRANSFER SWITCH IF
 LOCATED AS A MAIN SERVICE DISCONNECTING MEANS. ALSO
 110.9 FOR AIC RATING.
  
 B) MANUFACTURER SETBACK RECOMMENDATIONS FROM
 STRUCTURES.
  
 C) LOADS MUST NOT EXCEED GENERATOR OUTPUT. ONLY SUBMIT
 PANEL SCHEDULE AND CALCULATIONS FOR THE LOADS FED FROM
 THE GENERATOR.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  