| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | |
| | CITY OF WEST PALM BEACH RESIDENTIAL GENERATOR PLAN |
| | REVIEW |
| | |
| | |
| | ALL PERMIT APPLICATIONS MUST BE SUBMITTED TOGETHER TO |
| | EXPEDITE THE REVIEW PROCESS.TWO COPIES OF ALL PLANS, |
| | SURVEYS AND SPECIFICATIONS ARE REQUIRED. THE COST OF |
| | ALL EQUIPMENT AND LABOR MUST BE ENTERED AS VALUE PER |
| | 108.3 WPB AMENDMENTS. |
| | |
| | 1} SURVEY AND SITE PLANS INDICATING THE PROPOSED |
| | LOCATION OF THE GENERATOR. GIVE DIMENSIONS FROM |
| | PROPERTY LINES AND ALL STRUCTURES. INDICATE ANY |
| | EASEMENTS INVOLVED.CONTACT THE WPB ZONING DEPARTMENT |
| | FOR DETAILS REGARDING SETBACKS. |
| | |
| | 2} AN APPLICATION FOR AN ELECTRICAL PERMIT MUST INCLUDE |
| | THE FOLLOWING: |
| | |
| | A) SITE PLAN INDICATING THE PHYSICAL LOCATION OF THE |
| | EQUIPMENT WITH REGARD TO THE SERVICE AND SEPARATE |
| | STRUCTURES. NOTE: DISCONNECT REQUIRED TO BE SERVICE |
| | RATED PER 225.36. THIS INCLUDES THE TRANSFER SWITCH IF |
| | LOCATED AS A MAIN SERVICE DISCONNECTING MEANS. ALSO |
| | 110.9 FOR AIC RATING. |
| | |
| | B) MANUFACTURER SETBACK RECOMMENDATIONS FROM |
| | STRUCTURES. |
| | |
| | C) LOADS MUST NOT EXCEED GENERATOR OUTPUT. ONLY SUBMIT |
| | PANEL SCHEDULE AND CALCULATIONS FOR THE LOADS FED FROM |
| | THE GENERATOR. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |