| 2008-04-16 15:43:06 | ** DENIED3RD REVIEW** |
| | |
| | ** PLEASE SEE SEVERAL NOTES FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW NOTES |
| | DUE TO NEW ITEMS ONLY NOW BEING SUBMITTED FOR THE FIRST |
| | TIME FOR REVIEW. |
| | |
| | 1) NOTE: PLEASE SEE MISSING SMOKE ALARMS INSIDE AND |
| | OUTSIDE ALL SLEEPING ROOMS PER NFPA-72 11.5.1.1, |
| | 11.8.3. |
| | PLEASE ALSO SEE R313. |
| | PLEASE SEE THE NEW LAYOUT OF THE EXISTING DWELLING |
| | STILL SHOWS SD FOR SMOKE DETECTORS WHICH ARE NOT SMOKE |
| | ALARMS. |
| | PLEASE SEE DEFINITIONS IN NFPA-72 |
| | PLEASE SEE NEW ADDITION AREA IS STILL MISSING THE |
| | REQUIRED DEVICES. |
| | |
| | 2) NOTE: PLEASE SEE MISSING ARC FAULT PROTECTED |
| | CIRCUITS PER 210.12. PLEASE LIST ON PANEL AS PREVIOUSLY |
| | REQUESTED. |
| | |
| | 3) NOTE: PLEASE SEE THE WRONG TYPE OF RECESSED FIXTURE |
| | IS STILL BEING SHOWN ON PLANS. |
| | PLEASE SEE FBC 13-606.ABC.1.2.4 |
| | |
| | 4) NOTE: PLEASE SEE NEW MECHANICAL PLANS INDICATE 5KW |
| | HEAT FOR ONE AC SYSTEM YET THE NEW PANEL SCHEDULE ONLY |
| | NOW SUBMITTED INDICATES TWO 10KW HEAT STRIPS/ AC |
| | SYSTEMS. |
| | IN EITHER CASE NEITHER THE MECHANICAL PLANS NOR THE |
| | ELECTRICAL PLANS COORDINATE. |
| | M-SHEETS:SHOWS ONE 5KW, |
| | SHEET -1 SHOWS ONE 10KW, |
| | SHEET- B SHOWS TWO 10KW. |
| | |
| | PLEASE COMPLETE ELECTRICAL AND MECHANICAL COORDINATION |
| | AND PLEASE SEE 220.83B FOR CORRECTED LOAD |
| | CALCULATIONS. |
| | |
| | 5) NOTE: PLEASE SEE ONE SET OF THE NEW PLANS SUBMITTED |
| | ARE NOT SIGNED, DATED OR SEALED BY THE DESIGNER OF |
| | RECORD AS SHOWN ON TITLE BLOCKS AS REQUIRED UNDER FAC |
| | 61G15-23.002, FS 471.025. |
| | PLEASE ALSO SEE THAT SEVERAL OF THE SHEETS WHICH |
| | CONTAIN ELECTRICAL ARE SHOWN WITH A TITLE BLOCK FOR THE |
| | ENGINEER HOWEVER NOT ALL SHEETS FOR THE SAME SCOPE OF |
| | WORK IS DONE BY THE SAME DESIGNER. |
| | |
| | 6) NOTE: PLEASE SEE FS 553.80(2)(B). PLEASE SEE THAT |
| | THE FEE AS REQUIRED PER STATUTES WILL BE CHARGED IF THE |
| | SAME CODE COMPLIANT COMMENTS ARE NOT ADDRESSED ON NEXT |
| | RE-SUBMISSION. |
| | THERE ARE CODE COMMENTS WHICH ARE NOW BEING REPEATED |
| | MORE THAN ONCE AND THIS IS BEING GIVEN AS A NOTICE AT |
| | THIS TIME. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |