| 2008-03-04 07:51:04 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE MANY COMMENTS FROM THE PREVIOUS REVIEW |
| | ARE STILL IN NEED OF ADDRESSING. |
| | |
| | |
| | 1) NOTE:PLEASE SUBMIT A COMPLETE PLANS INCLUDING |
| | PANEL SCHEDULE SHOWING ALL NEW CIRCUITS ALONG WITH |
| | EXISTING COMPLYING WITH THE 2005 NEC. |
| | NO PANEL SCHEDULE WAS SUBMITTED. |
| | THE LOAD CALCULATIONS CAN NOT BE VERIFIED WITH THE |
| | CIRCUITING TO BE SHOWN ON PANEL SCHEDULE. ALSO CAN NOT |
| | VERIFIY WITH MINIMUM REQUIRED CIRCUIT(S) FOR NEW AND |
| | EXISTING. |
| | DOES THE DWELLING ALREADY CONTAIN AN A/C SYSTEM? |
| | PLEASE SEE NEC FOR MISSING REQUIRED DEDICATED CIRCUITS. |
| | PLEASE BE SURE TO LIST ALL OVER CURRENT PROTECTION |
| | DEVICES, MINIMUM REQUIRED CONDUCTOR SIZES ETC 210.52, |
| | 210.11, 408.4, 240.4, 310.16 ETC |
| | FBC 106.3.5.4 |
| | |
| | 3) NOTE: PLEASE SEE 210.12 FOR MISSING REQUIRED ARC |
| | FAULT FOR ALL OUTLETS. THIS REQUIRES *CIRCUITS* IN |
| | PANEL TO BE LABELED. |
| | |
| | 4) NOTE: PLEASE SEE 210.11C3 FOR MISSING REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S). MUST BE 20AMP AND #12 |
| | AWG. |
| | THESE NEED TO BE LISTED ON PANEL SCHEDULE. * MAY NOT |
| | QUOTE THE CODE IN LIEU OF REQUIRED MINIMUM* |
| | |
| | 5) NOTE: PLEASE SEE MISSING SMOKE ALARMS IN EXISTING |
| | DWELLING AS WELL AND THE NEW ROOMS WHICH ARE SLEEPING |
| | ROOMS OR ADAPTABLE SLEEPING ROOMS PER FBC R313 AND |
| | NFPA-72 11.5.1.1.1, 11.8.3. |
| | THIS WAS NOT DONE. IN FACT THE NOTE ADDED TO PLANS |
| | MENTIONS *SMOKE DETECTORS* WHICH WOULD BE PART OF A LOW |
| | VOLTAGE FIRE ALARM PANEL AND SYSTEM. IF THESE ARE GOING |
| | TO BE SMOKE DETECTORS, PLEASE COMPLETE PLANS WITH ALL |
| | DEVICES FOR A FIRE ALARM SYSTEM WITH HORN ALARM |
| | DEVICES. PLEASE SEE NFPA-72 FOR DEFINITIONS FOR A SMOKE |
| | ALARM AND SMOKE DETECTOR. IF THESE ARE GOING TO BE |
| | SMOKE ALARMS, PLEASE INDICATE AND COMPLETE PLANS |
| | ACCORDINLY. |
| | THE PREVIOUS REVIEW REQUESTED TO SHOW EXISTING SHOWING |
| | CURRENT CODE COMPLIANCE OR NEW TO BE INSTALLED. PLANS |
| | SUBMITTED DO NOT SHOW EITHER. |
| | PLEASE SUBMIT AND SHOW A LAYOUT OF THE EXISTING |
| | DWELLING WHICH EXISTING ALREADY COMPLIES WITH THE |
| | CURRENT VERSION OF NFPA-72 11.5.1.1.1 OR NEW TO BE |
| | INSTALLED. |
| | *MAY NOT QUOTE CODE IN LIEU OF SHOWING MINIMUM DETAILS |
| | FOR CODE COMPLIANCE. |
| | |
| | 6) NOTE: THE A/C UNITS ARE NOW SHOWN HOWEVER PLEASE SEE |
| | 210.70, 210.63 FOR REQUIRED SERVICE OUTLETS IN ATTIC |
| | WHICH ARE NOT SHOWN ON PLANS. |
| | |
| | 7) NOTE: PLEASE SEE THE ELECTRICAL SHOWN ON SHEET 2 FOR |
| | REAR PORCH IS NOT THE SAME AS THE ELECTRICAL SHOWN ON |
| | A-SHEET. |
| | PLEASE COORDINATE PLANS. FBC 106.1.2, 106.3.5.4 |
| | ** THIS IS THE SAME COMMENT. RESPONSE MENTIONS |
| | |
| | 8) NOTE: PLEASE PLACE NOTE ON PLANS FOR NEW RECESSED |
| | LIGHTING PER FBC 13-606.ABC.1.2.4 |
| | THE NOTE WHICH WAS ADDED TO PLANS INDICATES A TYPE *IC* |
| | RATED RECESSED LUMINAIRE WHICH IS NOT THE SECTION OF |
| | THE CODE GIVEN IN PREVIOUS REVIEW. |
| | PLEASE ADJUST NOTE AND TYPE OF FIXTURE. |
| | |
| | 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR MINIMUM CODE COMPLIANCE. THIS IS |
| | ONLY A NOTICE GIVEN AT THIS TIME TO THE DESIGN |
| | PROFESSIONAL. |
| | |
| | |
| | *** AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR |
| | REVIEW, THERE MAY BE NEW COMMENTS ON THE FOLLOWING |
| | REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |