| Date |
Text |
| 2007-12-23 14:32:09 | ** DENIEDREVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE |
| | NEEDED AS FOLLOWS: |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SUBMIT A COMPLETE PLANS INCLUDING PANEL |
| | SCHEDULE SHOWING ALL NEW CIRCUITS ALONG WITH EXISTING |
| | COMPLYING WITH THE 2005 NEC. |
| | PLEASE SEE NEC FOR MISSING REQUIRED DEDICATED CIRCUITS. |
| | PLEASE BE SURE TO LIST ALL OVER CURRENT PROTECTION |
| | DEVICES, MINIMUM REQUIRED CONDUCTOR SIZES ETC 408.4, |
| | 240.4, 310.16 ETC |
| | FBC 106.3.5.4 |
| | |
| | 3) NOTE: PLEASE SEE 210.12 FOR MISSING REQUIRED ARC |
| | FAULT FOR ALL OUTLETS. |
| | |
| | 4) NOTE: PLEASE SEE 210.11C3 FOR MISSING REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S). MUST BE 20AMP AND #12 |
| | AWG. |
| | |
| | 5) NOTE: PLEASE SEE MISSING SMOKE ALARMS IN EXISTING |
| | DWELLING AS WELL AND THE NEW ROOMS WHICH ARE SLEEPING |
| | ROOMS OR ADAPTABLE SLEEPING ROOMS PER FBC R313 AND |
| | NFPA-72 11.5.1.1.1, 11.8.3 |
| | PLEASE SUBMIT AND SHOW A LAYOUT OF THE EXISTING |
| | DWELLING WHICH EXISTING ALREADY COMPLIES WITH THE |
| | CURRENT VERSION OF NFPA-72 11.5.1.1.1 OR NEW TO BE |
| | INSTALLED. |
| | |
| | 6) NOTE: PLEASE SEE MISSING DISCONNECTS FOR A/C |
| | CONDENSING UNITS PER 440.11. |
| | PLEASE ALSO SEE THE NEW AHU IS MISSING FROM ELECTRICAL |
| | PLANS. |
| | 440.11, 110.26 |
| | |
| | 7) NOTE: PLEASE SEE THE ELECTRICAL SHOWN ON SHEET 2 FOR |
| | REAR PORCH IS NOT THE SAME AS THE ELECTRICAL SHOWN ON |
| | A-SHEET. |
| | PLEASE COORDINATE PLANS. FBC 106.1.2, 106.3.5.4 |
| | |
| | 8) NOTE: PLEASE PLACE NOTE ON PLANS FOR NEW RECESSED |
| | LIGHTING PER FBC 13-606.ABC.1.2.4 |
| | |
| | |
| | *** AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR |
| | REVIEW, THERE MAY BE NEW COMMENTS ON THE FOLLOWING |
| | REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |