| Date |
Text |
| 2008-03-04 18:56:58 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 CHAPTER 1 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY WPB MUNICIPAL CODE |
| | |
| | 1. SURVEY SHEET THE ADDRESS FOR WALLACE SURVEYING #4569 |
| | DOES NOT REFLECT THE STATE OF FLORIDA DBPR ADDRESS OF |
| | RECORD. PLEASE UPDATE THE TITLE BLOCKS OR THE DBPR |
| | WEBSITE PRIOR TO RESUBMITTING. FAC 61G16.004(1) & FS |
| | 481.306. |
| | |
| | 2. IRRIGATION PLANS & PERMIT REQUIRED. SECTION |
| | 106.3.5.1.3(9). |
| | |
| | 3. THE ADDRESS ON THE PLANS AND THE BINDER ARE |
| | DIFFERENT. 2501 N FLAGLER AND 2500 PONCE DE LEON AVE. |
| | PLEASE CORRELATE. FAC 61G1-16.004(3) & FS 481.2055. |
| | |
| | 4. SHT G-0.03 APPLICABLE CODE TO INCLUDE FHA-98 DESIGN |
| | MANUAL. |
| | |
| | 5. SHTS A-2.52 & A-2.53 DRAINS AROUND THE POOL ARE |
| | INDICATED AS FLOOR DRAINS. IF THEY ARE FOR DRAINING THE |
| | STORM WATER OFF THE DECK THEY SHOULD BE INDICATED AS |
| | DECK DRAINS.--ALSO SEE FLOOR DRAINS AT THE "TH |
| | UNITS". PLEASE CLARIFY WHAT IS BEING DRAIND. THEY |
| | APPEAR TO BE ROOF DRAINS AT THE SPA. SECTIONS 106.1.1 |
| | 106.2.1, TABLES 710.1(1), 710.1(2) & 1106.3. |
| | |
| | 6. SUBMIT CALCULATION FOR MINIMUM FACILITIES FOR THE |
| | COMMON AREAS, FITNESS, RECREATION, SOCIAL BAR, SOCIAL |
| | /LOUNGE OFFICE ETC. TABLES 1004.1.2 & 403.1. |
| | |
| | 7. SHT A-2.6.2 NO SECONDARY ROOF DRAINS/EOS SHOWN AT |
| | STAIR #9. SECTION 1107. |
| | |
| | 8. SHT A-2.6.3 NO SECONDARY ROOF DRAINS/EOS SHOWN AT |
| | STAIR #7. SECTION 1107. |
| | |
| | 9. SHTS A-3.10 THRU A-3.53 SHOW COMPLIANCE WITH |
| | REQUIREMENTS 6 & 7 FOR EACH UNIT, OR SHOW COMPLIANCE |
| | FOR A TYPICAL UNIT OF EACH TYPE. SHOW THE WATER CLOSET |
| | AT 18" OFF THE WALL TO THE CENTERLINE OF THEFIXTURE |
| | WHERE APPLICABLE, (PAGE 6.3) & SHOW A MINIMUM 33" |
| | OPENING FOR THE WATER CLOSETS. INDICATE 18" & 15" FROM |
| | THE CENTERLINE OF THE FIXTURE TO ADJACENT FIXTURES WHEN |
| | NOT NEXT TO A WALL. (PAGE 6.7). FHA-98 DESIGN MANUAL. |
| | --SEE PAGE 6.10 FOR REINFORCING AT NON CONVENTIONAL |
| | BATHTUBS. IF THIS TYPE OF TUB IS TO BE ADAPTABLE PLEASE |
| | SHOW THE BACKING. |
| | |
| | 10. SHTS A-3.10 THRU A-3.53 SHOW CLEAR FLOOR SPACE IN |
| | THE KITCHEN AS REQUIRED ON PAGES 7.3 & 7.4 FHA-98 |
| | HOUSING MANUAL.--SHOW MINIMUM CLEARANCE DIMENSION |
| | BETWEEN REFRIG, RANGE & BASE CABINETS AS REQUIRED ON |
| | PAGES 7.7 & 7.8 FHA-98 DESIGN MANUAL.--SHOW TURNING |
| | IN THE "U" SHAPED KITCHENS THAT HAVE A SINK, RANGE OR |
| | COOKTOP AT ITS BASEAS REQUIRED ON PAGE 7.9 OR SEE |
| | EXCEPTION ON PAGE 7.11. INDICATE ON PLANS IF EXCEPTION |
| | WILL BE USED AND SUBMIT A DETAIL FOR EXCEPTION. |
| | |
| | 11. SHTS A-3.10 THRU A-3.53 INDICATE ON PLANS WHICH |
| | SPECIFICATION, "A" OR "B" TO BE USED FOR EACH UNIT AS |
| | REQUIRED ON PAGES 7.34 & 7.35. SEE REQUIREMENTS FOR |
| | EACH.--SHOW THE CLEAR FLOOR SPACE, (SUPERIMPOSED |
| | ON THE FLOOR PLANS), FOR THE ACCESSIBLE FIXTURES FOR |
| | EACH UNIT. SEE PAGES 7.43 THRU 7.57. |
| | |
| | 12. SHT A-3.16 SHOW THE CLEAR FLOOR SPACE FOR THE |
| | ACCESSIBLE FIXTURES IN THE MEN'S AND WOMEN'S LOCKER |
| | ROOMS. SHOW THE TURNING AREA. SHOW THE CLEAR FLOOR |
| | SPACE FOR THE ACCESSIBLE DRINKING FOUNTAIN. SHOW THE |
| | ACCESSIBLE W/C'S TO BE 18" OFF THE WALL TO THE |
| | CENTERLINE OF THE FIXTURE AND THE LAV TO BE A MINIMUM |
| | 15" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. |
| | SECTIONS 11-4.16.2, 11-4.18.3, 11-4.19.3, 11-4.21.2 |
| | 11-4.22.3 & FIGURE 28 AS WELL AS SECTION 11-4.15.5 FOR |
| | THE DRINKING FOUNTAIN. |
| | |
| | 13 SHT A3.1.6 ACCESSIBLE STALLS SHALL COMPLY WITH |
| | FIGURE 30(E), FLUSH CONTROLS FOR WATER CLOSETS SHALL |
| | COMPLY WITH SECTION 11-4.16.5. LAVS SHALL COMPLY WITH |
| | SECTIONS 11-4.19.4 EXPOSED PIPES AND SURFACES AS WELL |
| | AS 11-4.19.5 FAUCETS. PLEASE SUBMIT DETAILS. |
| | |
| | 14. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING |
| | FOUNTAIN SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH |
| | ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A). |
| | |
| | 15. SHT A-3.28 MEN'S AND WOMEN'S TOILET ROOMS. SHOW THE |
| | CLEAR FLOOR SPACE FOR ACCESSIBLE FIXTURES PER SECTIONS |
| | 11-4.16.2 & 11-4.19.3. |
| | |
| | 16. SHT A-3-31 SHOW W/C'S TO BE 18" OFF THE WALL AND |
| | THE LAVS MINIMUM 15" OFF THE WALL. FIG 28.--STALLS |
| | TO COMPLY WITH FIG. 11-30(E). |
| | |
| | 17. SHT A-3.31 MORE INFORMATION REQUIRED. WILL THERE BE |
| | COOKING IN THE CATERING KITCHEN? SECTION 106.1.2. |
| | |
| | 18. SHTS A-7.04 & A-7.05 FINISH SCHEDULE FOR COMMON |
| | AREAS. PLEASE INDICATE WHERE THE LEGEND FOR THE FINISH |
| | TYPES CAN BE LOCATED. REMARKS STATE "REFER TO ID. |
| | DRAWINGS". PLEASE INDICATE THE SHEET NUMBER FOR ID |
| | DRAWINGS. SECTION 106.1.2. |
| | |
| | 19. SUBMIT CALCULATIONS FOR PRIMARY AND SECONDARY ROOF |
| | & DECK DRAINS FOR THE ROOF, GROUND FLOOR DECK AND |
| | SECOND FLOOR. SHOW SECONDARY DRAINS FOR SHEETS P-1.1 |
| | THRU P-1.5 AND SHTS P-2.1 THRU P-2.4. SECTIONS 1106 & |
| | 1107 WITH ALL SUBSECTIONS AND TABLES. SHOW THE AREA |
| | BEING DRAINED BY EACH ROOF DRAIN, DECK DRAIN AND 1/2 |
| | THE AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS FOR |
| | EACH DRAIN AFFECTED, AS WELL AS ANY AREA FROM A ROOF |
| | THAT DRAINS TO THE ROOF/DECK FROM ABOVE IN THE |
| | CALCULATIONS. |
| | |
| | 20. SHT P-00 NOTE STATES "2 INCH COLD WATER TO COOLING |
| | TOWER METER, FOR EXACT LOCATION SEE CIVIL ENGINEERING |
| | DRAWING" - COOLING TOWER METERWATER NOT SHOWN ON SHEET |
| | C3. PLEASE CLARIFY. SECTIONS 106.1.2 AND 608.13.2. |
| | |
| | 21. SHT P-00 IN ONE SET OF PLANS HAS DIFFERENT |
| | INFORMATION THAN THE SHT P-00 IN THE OTHER SET OF |
| | PLANS. ALSO THE DATE THAT THE SEAL AND SIGNATURE WERE |
| | AFFIXED IS DIFFERENT. WHY 2 SHEETS WITH P-00 |
| | DESIGNATIONS? PLEASE CLARIFY. SECTION 106.1.2. |
| | |
| | 22. SHTS P-001, P-002, P-00, P-01 & P-.2 ARE DRAWN AT |
| | 1/16TH PER FT. SCALE & HAS ALOT OF INFORMATION AND IS |
| | NOT LEGIBLE AS TO ITS INTENT. BLDG PLANS SHALL BE DRAWN |
| | TO A MINUMUM 1/8" PER FT SCALE PER SECTION 106.1.3. |
| | |
| | 23. SHT P-001 DOMESTIC PUMP ROOM A SHUT OFF VALVE IS |
| | REQUIRED FOR THE LINE TO THE HOSE BIBB. SECTION |
| | 606.2(2).--PIPING IS NOT SHOWN TO MANY DECK DRAINS. |
| | --SUMP PUMP #11 WAS NOT FOUND.--2 SUMP PUMPS HAVE |
| | THE # 20 SHOWN. PLEASE CLARIFY--MANY NOTES ON THE |
| | FLOOR PLAN ARE NOT LEGIBLE. (RISER DESIGNATION NUMBERS |
| | OVER THE TOP OF NOTES). PLEASE CLARIFY--SHOW ALL |
| | PIPE SIZES AND RISER DESIGNATIONS FOR STORM RISERS.-- |
| | INDICATE WHERE THE SANITARY PIPE CONTINUES TO WHEN |
| | INDICATING CONTINUATION OF PIPE. (WHAT SHEET DOES IT |
| | CONTINUE ON)?--TWO RISER 63 DESIGNATIONS. PLEASE |
| | CLARIFY--IDENTIFY FIXTURES BEHIND THE ELEVATORS AND |
| | INDICATE WHICH RISER THE VENT CONNECT TO AT ELEVATORS |
| | ONE THRU FIVE. SHOW VENT ON RISER. SECTIONS 106.1.1 & |
| | 106.1.2. TABLES 710.1(1), 710.1(2), 916.1, 1106.2 & |
| | 1106.3. |
| | |
| | 24. SHT P-002 ONE GAS RISER NOT CONNECTED TO GAS MAIN. |
| | -- SOME GAS RISERS ARE INDICATED AS RISING UP AND |
| | DROPING DOWN FROM THE LOWER LEVEL GARAGE. ARE THERE GAS |
| | APPLIANCES BELOW THE LOWER GARAGE? PLEASE CLARIFY.-- |
| | IDENTIFY RISERS AT THE BASE OF THE STACK SO COMMENTS |
| | CAN BE ADDRESSED TO SPECIFIC RISERS.--SOME NOTES |
| | ARE NOT LEGIBLE.--INDICATE GAS PIPE SIZES. SECTIONS |
| | 106.1.1, 106.1.2 TABLE 402.4(3). |
| | |
| | 25 INDICATE THE STORM RISER NUMBERS FOR EACH STORM |
| | RISER ON EACH SHEET THROUGH OUT THE BUILDING SO THE |
| | RISERS CAN BE TRACKED. SHEET WILL BE REVIEWED WHEN |
| | SUBMITTED TO ACCEPTABLE SCALE. SECTION 106.1.3. TABLES |
| | 1106.2 & 1106.3. |
| | |
| | 26. SHTS P-001 AND P-01 HAVE THE SAME INFORMATION. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 27. SHT P-1.1 SHOWS PIPING TO FIXTURES THAT ARE NOT ON |
| | THE FLOOR PLAN, EXAMPLE RISER #2. THE SHEET ALSO SHOWS |
| | FIXTURES WITH NO PIPING INDICATED, EXAMPLE RISER NUMBER |
| | 33. SHOW ALL PIPING TO THE FIXTURES. THE SANT. PIPING |
| | SHALL BE SHOWN ON THE SAME SHEET AS THE FIXTURES. THE |
| | STORM PIPING SHALL BE SHOWN ON THE SAME SHEET AS THE |
| | DECK DRAINS, PLANTER DRAINS ETC. (SEE SHT P-5.2 RISER |
| | 49 AS AN EXAMPLE).--WHAT RISER DOES THE SINK BY |
| | STAIR 1A CONNECT TO?--SANITARY RISER #4 DOES NOT |
| | REFLECT THE FLOOR PLAN.--IDENTIFY THE PIPE BY RISER |
| | 115 NOT SHOWN ON THE RISER.--INDICATE RISER NUMBERS |
| | FOR W/M'S BEHIND ELEVATORS 1, 2 & 3 AS WELL AS THE |
| | W/M'S BEHIND STAIR #2 & STAIR #3.--EXPLAIN THE |
| | NUMBER 5 IN THE RECTANGLE BY THE HOSE BIBB NEAR COL. |
| | LINE 3/D. SECTIONS 106.1.1 & 106.1.2. TABLE 1106.3. |
| | |
| | 28. SHTS P-1.2, P-1.3, P-1.4, P-1.5, P-2.1, P-2.2, |
| | P-2.3, P-2.4, P-3.1, P-3.4, P-4.1, P-4.2, P-4.3, P-4.4, |
| | P-5.1, P-5.4, P-6.1, P-6.2, P-7.1 & P-7.2SHOW PIPING |
| | TO FIXTURES, DECK DRAINS & PLANTER DRAINS ON THE SHEET |
| | THAT THE FIXTURES, DECK DRAIN & PLANTER DRAINS ARE |
| | LOCATED. SEE SHT P-2.3 RECREATION REST ROOM OR SHT |
| | P-3.3 SOCIAL ROOM BATHROOM AS EXAMPLES OF CORRECT |
| | INFORMATION. SECTIONS 106.1.1 & 106.1.3. |
| | |
| | 29. SHT P-1.2 IDENTIFY THE RISER NUMBERS FOR W/M'S |
| | BEHINDSTAIR NUMBER 4, STAIR NUMBER 5 AS WELL AS |
| | ELEVATORS NUMBERS 4, 5 & 6.--2 RISERS NUMBERED 63. |
| | PLEASE CLARIFY. SECTIONS 106.1.1 & 106.1.2 & TALBES |
| | 710.1(1), 710.1(2). |
| | |
| | 30. SHT P1.3 THE OVERFLOW FROM THE FOUNTAIN SHALL DRAIN |
| | TO THE STORM, NOT SANITARY AS SHOWN. (NOTE #3). -- |
| | WATER RISER 18 & CONDENSATE 17 IN THE SAME UNIT? SEE |
| | WATER RISER 17 & CONDENSATE 18ALSO.-- RECREATION |
| | BATHROOM SHOWS 1/2" COLD WATER SUPPLY TO THE BATHROOM |
| | THEN INCREASES TO 1-1/4". WATER ALSO SHOWS 2" SUPPLY |
| | DROPS BETWEEN THE SHOWERS. PLEASE CLARIFY. SECTIONS |
| | 106.1.1 & 106.1.2. TABLE 604.5.--SHOW RISER |
| | DESIGNATION NUMBERS FOR RISER 76, 77, 79 & 80 AS WELL |
| | AS RISERS 81, 82 & 87.--SHUT OFF VALVE IS REQUIRED |
| | ON THE SUPPLY LINE TO THE HOSE BIBB IN THE FOUNTAIN |
| | EQUIPMENT ROOM.SECTIONS 106.1.1, 106.1.2 & 606.2(2). |
| | |
| | 31. SHTS P2.1 THRU P2.4 SHOW THE SANITARY PIPING TO |
| | EACH FIXTURE THAT REFLECTS THE FLOOR PLAN. SECTION |
| | 106.1.1, 106.1.2 & 106.3.5.1.3. |
| | |
| | 32. SHT P-4.1 BRANCH LINE TO KITCHEN SINK MISSING FOR |
| | RISER #34. SECTION 106.1.1, 106.1.2 & TABLE 709.1. |
| | |
| | 33. SHT P-4.2 BRANCH LINE TO KITCHEN SINK MISSING FOR |
| | RISER #34. SECTION 106.1.1, 106.1.2 & TABLE 709.1. |
| | |
| | 34. SHT P-4.4 SHOWS TWO 2" LINES TO THE COOLING TOWER. |
| | ARE THERE TWO COOLING TOWERS? PLEASE CLARIFY. SECTION |
| | 106.1.2. |
| | |
| | 35. SHT P-5.2 INDICATE WHERE THE 1/4" SCALE TO THE |
| | TOILET ROOMS CAN BE LOCATED AS REFERENCED. INFORMATION |
| | AT THE RIGHT SIDE OF THE FLOOR PLAN IN NOT COMPLETE. |
| | PLEASE SHOW ALL INFORMATION INTENDED. SECTIONS 106.1.1 |
| | & 106.1.2. |
| | |
| | 36. SHT P-5.3 VENT 87 IS NOT SHOWN AND VENT 91A |
| | INDICATED IS NOT SHOWN ON THE LOWER LEVELS. PLEASE |
| | CORRELATE. SECTION 106.1.1 & TABLE 916.1. |
| | |
| | 37. SHT P-5.4 VENTS 105 & 107 ARE SHOWN CONNECTING TO |
| | THE EAST VENT ON SHT P-4.4. PLEASE CLARIFY.-- |
| | COOLING TOWER WATER SUPPLY PIPING DOES NOT REFLECT THE |
| | FLOOR PLAN AS THE HOSE BIBB IS MISSING. PLEASE |
| | CORRELATE. SECTION 106.1.1 & TABLE 916.1. |
| | |
| | 38. SHT P-6.2 SHOW THE VTR FOR RISERS 70 & 71. SECTIONS |
| | 106.1.1 & 903.3. |
| | |
| | 39. SHT P-7.1 INDICATE THE RISER NUMBER FOR THE 7TH |
| | FLOOR TOILET ROOMS SANITARY. SECTION 106.1.1 & TABLES |
| | 710.1(1) & 710.1(2). |
| | |
| | 40. SHT P-7.2 UNABLE TO REVIEW INFORMATION ON THE NORTH |
| | END, (LEFT SIDE),OF SHEET WITHOUT TAKING PLANS APART. |
| | SECTION 106.1.3. PLEASE SEE THAT ALL INFORMATION IS |
| | AVAILABLE FOR REVIEW.--SHOW ALL RISER NUMBERS AT |
| | THE TOILET ROOMS. SECTIONS 106.1.1 106.1.2 & TABLES |
| | 710.1(1) & 710.1(2). |
| | |
| | 41. SHT P-8 LINE TO THE ICE MAKER NOT SHOWN ON THE |
| | FLOOR PLAN FOR BOTH A UNITS. PLEASE CORRELATE. SECTION |
| | 106.1.1. |
| | |
| | 42. SHT P-9 UNIT "B" FLOOR PLAN DOES NOT SHOW THE WATER |
| | LINE TO THE ICE MAKER TO REFLECT THE ISO. RISER |
| | DIAGRAM. PLEASE CORRELATE. SECTION 106.1.1.--UNIT |
| | "B" GROUND FLOOR PLAN SHOWS THE WATER LINE TO THE ICE |
| | MAKER UNDER THE SLAB ON THE FLOOR PLAN, BUT NOT ON THE |
| | ISOMETRIC RISER DIAGRAM. PLEASE CORRELATE. SECTION |
| | 106.1.1. |
| | |
| | 43. SHT P-10 UNIT"C" WATER RISER DOES NOT REFLECT THE |
| | FLOOR PLAN WHERE THE WASH MACHINE CONNECTS TO THE |
| | HOT/COLD WATER MAIN. PLEASE CORRELATE. SECTIONS 106.1.1 |
| | & 604. |
| | |
| | 44. SHT P-11 UNIT "B" FLOOR PLAN DOES NOT SHOW THE |
| | WATER LINE TO THE ICE MAKER TO REFLECT THE ISOMETRIC |
| | RISER DIAGRAM.--UNIT "B" GROUND FLOOR PLAN |
| | INDICATES THE ICE MAKER SUPPLY LINE IN THE SLAB, BUT |
| | THE RISER DIAGRAM SHOWS THE ICE MAKER LINE IN THE WALL. |
| | CORRELATE. SECTION 106.1.1. |
| | |
| | 45. SHT P-12 UNIT "C" WATER RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN WHERE THE WASH MACHINE CONNECTS |
| | TO THE WATER MAIN. PLEASE CORRELATE. SECTIONS 106.1.1 & |
| | 604. |
| | |
| | 46. SECOND SHT P-11 UNIT "C" DOUBLE RISER DIAGRAM |
| | MISLABELED A LAV FOR A TUB & A LAV FOR A BIDET AND DOES |
| | NOT REFLECT THE PIPING AT THE TUB/LAV IN THE MASTER |
| | BATH.--PIPING AT THE TUB & LAV DOES NOT REFLECT THE |
| | FLOOR PLAN.--TUB INDICATED AS LAV IN TUB BATH BY |
| | WASH MACHINE.PLEASE CORRELATE. SECTION 106.1.1 & |
| | TABLE 709.1. |
| | |
| | 47. SECOND SHT P-12 INDICATES UNIT "CH" MOD. 1& 2 |
| | FIRST, SECOND & THIRD FLOORS, BUT THE RISER DIAGRAM IS |
| | FOR MOD. 3. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 48. THE SEQUENCE OF SHEETS SUBMITTED IS AS FOLLOWS: |
| | P-11, P-12, P-11, P-12, P-13, P-14 & P-15. PLEASE |
| | NUMBER SHEETS IN A SEQUENCE THAT CAN BE LOGICALLY |
| | FOLLOWED. SECTIONS 106.1.3 & 106.1.3. |
| | |
| | 49. SHT P-15 SHOWS THE SAME INFORMATION THAT SHEET P-13 |
| | SHOWS. PLEASE CLARIFY. SECTIONS 106.1.1 & 106.1.3. |
| | |
| | 50. SHT P-14 UNITS "E" FLOOR PLANS & "E" GROUND FLOOR |
| | PLANS DO NOT SHOW THE WATER LINES TO THE ICE MAKERS |
| | THAT REFLECT THE FLOOR PLAN. PLEASE CORRELATE.-- |
| | UNIT "E" GROUND FLOOR PLAN SHOWS HOT & COLD WATER |
| | SUPPLY TO THE WATER CLOSET IN THE 2ND BATHROOM. PLEASE |
| | CORRELATE. SECTIONS 106.1.1 & 601.1. |
| | |
| | 51. SECOND SHT P-15 UNIT "F" FLOOR PLAN DOES NOT SHOW |
| | THE WATER LINE TO THE ICE MAKER THAT REFLECTS THE RISER |
| | DIAGRAM.--UNIT "F" GROUND FLOOR PLAN WATER RISER |
| | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN AT THE 2ND |
| | BATHROOM. PLEASE CORRELATE. SECTIONS 106.1.1 & 601.1. |
| | |
| | 52. SHT P-16 UNIT H FLOOR PLAN. PLEASE SHOW PIPING TO |
| | THE HOSE BIBB TO REFLECT THE RISER DIAGRAM. SECTIONS |
| | 106.1.1 601.1. |
| | |
| | 53. SHT P-17 ALL "J" UNITS THE WATER RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN AT THE WATER LINES TO THE |
| | ICE MAKERS.--UNIT "J" GROUND WATER RISER DIAGRAM |
| | DOES NOT REFLECT THE FLOOR PLAN AT THE WASH MACHINE. |
| | --UNIT "J" FLOOR PLAN SHALL REFLECT THE RISER |
| | DIAGRAM. NO HOSE BIBB LINE SHOWN, NO ICE MAKER LINE |
| | SHOWN.--NO UNIT "J" GROUND MOD 2 FLOOR PLAN |
| | SUBMITTED.PLEASE CORRELATE. SECTIONS 106.1.1 & |
| | 601.1. |
| | |
| | 54. SHT P-19 UNIT "R" RISER DIAGRAM DOES NOT REFLECT |
| | THE FLOOR PLAN AT THE WATER LINE TO THE ICE MAKER.-- |
| | UNIT "P" WATER RISER DIAGRAM DOES NOT REFLECT THE FLOOR |
| | PLAN AT THE WATER LINE TO THE ICE MAKER, AND WHERE THE |
| | SHOWER IN THE MASTER BATH CONNECTS TO THE MAIN & OFFSET |
| | BY THE REFR.--UNIT "U" REV WATER RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN WHERE THE COLD & HOT RISERS |
| | CONNECT TO THE WATER MAIN. PLEASE CORRELATE. SECTIONS |
| | 106.1.1 & 6011.1. |
| | |
| | 55. SHT P-20 UNIT "TH" MOD REV 3RD FLOOR PLAN DOES NOT |
| | SHOW THE WATER PIPING TO THE MASTER BATH THAT REFLECTS |
| | THE RISER DIAGRAM.--UNIT "TH" R MOD 1 & MOD WATER |
| | RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN WHERE THE |
| | RISER TO THE 5TH FLOOR POWDER ROOM CONNECTS AT THE 4TH |
| | FLOOR. LAV SHOULD BE ON THE OTHER SIDE OF THE RISER 4TH |
| | FLOOR. PLEASE CORRELATE. SECTIONS 106.1.1 & 601.1. |
| | |
| | 56. SHT P-21 UNITS "TH" & "TH" REV WATER RISER DIAGRAM |
| | DO NOT REFLECT THE FLOOR PLANS AT THE 4TH FLOOR. RISER |
| | IS SHOWN BEHIND THE W/C NOT TO THE LEFT SIDE OF THE LAV |
| | AS INDICATED ON THE RISER DIAGRAM.--UNITS "TH" & |
| | "TH" REV FLOOR PLANS DO NOT SHOW THE WATER PIPING TO |
| | THE MASTER BATH. PLEASE SHOW ALL PIPING. SECTIONS |
| | 106.1.1 & 601.1. |
| | |
| | 57. SHT P-22WATER RISERS 1 THRU 14 INDICATE WHERE THE |
| | CONTINUATION OF RISER CAN BE FOUND TO REFLECT THE |
| | PIPING ON THE 7TH FLOOR. ALSO THE OFFSETS SHOWN ON THE |
| | 6TH FLOOR FOR ALL RISERS BUT RISER 14IS NOT SHOWN ON |
| | THE RISER DIAGRAMS.--RISERS 4, 6, 8 & 10 INDICATE |
| | 1" HW (TYP) BUT SHOW 34" BELOW.--RISERS 5. 7. 9 & |
| | 11SHOWS 3/4 HW FROM THE COLD WATER RISER AT THE 7TH |
| | FLOOR.--RISER 13 SHOWS 3/4" HW (TYP) BUT SHOW 1" |
| | BELOW.--RECREATION MEN'S BATHROOM DOES NOT REFLECT |
| | THE FLOOR PLAN AT THE LAV/URINAL.--PLEASE CLARIFY |
| | 1/2" DESIGNATIONS BY THE SHOWERS. PLEASE CORRELATE. |
| | SECTIONS 106.1.1 & 601.1. |
| | |
| | 58. SHT P-23 INDICATE THE LOCATION OF THE WATER RISERS |
| | 1C THRU 7C AND WATER RISERS 1T THRU 15T. UNABLE TO |
| | LOCATE.--UNABLE TO READ/REVIEW INFORMATION AT THE |
| | FAR LEFT SIDE OF THE SHEET WITHOUT TAKING THE PLANS |
| | APART. PLEASE MAKE ALL INFORMATION AVAILABLE.--PIPE |
| | SIZING AT THE GANG TOILETS SUPPLY, (1-1/2") DOES NOT |
| | REFLECT THE FLOOR PLAN, (2"). SECTIONS 106.1.1, 106.1.2 |
| | & 601.1. |
| | |
| | 59. SHT P-24 RISERS 2, 4 & 6 DO NOT REFLECT THE FLOOR |
| | PLAN AT THE GROUND FLOOR.--RISER 11 DOES NOT |
| | REFLECT THE FLOOR PLAN.--RISER 16CLEANOUTS ARE |
| | REQUIRED ON THE VENT PRIOR TO CONNECTING TO THE VENT |
| | STACK ON ISLAND VENTS. SECTION 913.3 (SEE FIG. 913.2). |
| | --RISER 19 SHOWS A SHOWER ON THE FIRST FLOOR BUT THE |
| | FLOOR PLAN SHOWS A TUB.--RISERS 20, 29, 38 & 47 DO |
| | NOT REFLECT THE FLOOR PLAN AT THE 5TH FLOOR. --RISERS |
| | 21, 30, 39 & 48 THREE INCH PIPE REQUIRED ON THE BRANCH |
| | LINE TO THE WASH MACHINES. SECTION 406.3.--RISERS |
| | 23, 32 & 41 DO NOT REFLECT THE FLOOR PLAN AT THE 5TH |
| | FLOOR.PLEASE CORRLEATE. SECTIONS 106.1.1, 701.1 & |
| | TABLES 710.1(1), 710.1(2). |
| | |
| | 60. SHT P-25 RISERS 25, 34 & 43 CLEANOUTS ARE REQUIRED |
| | ON THE VENT PRIOR TO CONNECTING TO THE VENT STACK ON |
| | ISLAND VENTS. SECTION 913.3 (SEE FIG. 913.2). RISERS |
| | SHOW SHOWERS ON THE 6TH FLOOR, BUT FLOOR PLAN SHOWS |
| | TUBS.--RISERS 28, 37, 46 DO NOT REFLECT THE FLOOR |
| | PLAN. RISER SHOWS SHOWERS 1ST FLOOR BUT FLOOR PLAN |
| | SHOWS TUBS.--RISER 55 DOES NOT REFLECT THE FLOOR |
| | PLAN 1ST FLOOR. FLOOR PLAN SHOWS TUB/SHOWER IN BOTH |
| | BATHROOMS.--RISERS 52 & 65 CLEANOUTS ARE REQUIRED |
| | ON THE VENT PRIOR TO CONNECTING TO THE VENT STACK ON |
| | ISLAND VENTS. SECTION 913.3 (SEE FIG. 913.2).-- |
| | RISER 52 DOES NOT REFLECT THE FLOOR PLAN AT THE 5TH & |
| | 6TH FLOORS.--RISERS 67 & 68 DO NOT REFLECT THE |
| | FLOOR PLAN AT THE 2ND FLOOR FOR RISER 68 AND FOR THE |
| | OFFSET ABOVE THE FIRST FLOOR ON RISER 67 PLUS RISER 67 |
| | SHOWS TUBS BUT THE FLOOR PLAN SHOWS SHOWERS.-- |
| | RISER 70 TOILET ROOM 4TH FLOORWILL REVIEW FOR CODE |
| | COMPLIANCE WHEN 1/4" FLOOR PLAN IS FOUND. (SEE NOTE |
| | P-5.2).--BOILER ROOM DETAIL SHOWS A FLOOR DRAIN FOR |
| | INDIRECT WASTE. FLOOR DRAINS ARE NOT APPROVED WASTE |
| | RECEPTORS. A FLOOR SINK OR HUB DRAIN WILL BE REQUIRED |
| | PER SECTIONS 802.3 & 802.3.2. ALSO THE INDIRECT WASTE |
| | SHALL BE LOCATED TO NOT BECOME A TRIPPING HAZARD. |
| | PLEASE CORRELATE.SECTIONS 106.1.1, 701.1 & TABLES |
| | 710.1(1), 710.1(2). |
| | |
| | 61. SHT P-26. RISER 18 INDICATES NOTE TWO WHICH STATES |
| | "FOR CONTINUATION REFER TO VENTILATION PIPING. SEE |
| | HORIZONTAL DIAGRAM ON SHT P-28". SHT P-28 AS SUBMITTED |
| | IS STORM RISERS. PLEASE CLARIFY. SECTION 106.1.1-- |
| | RISER 114 DOES NOT REFLECT THE FLOOR PLAN AT THE 5TH |
| | LEVEL. (DRINKING FOUNTAINS NOT SHOWN).--ALL "C" AND |
| | "T" RISERS HAVE NOT BEEN REVIEWED AT THIS TIME BECAUSE |
| | THE PIPING ON THE FLOOR PLANS IS NOT SHOWN ON THE FLOOR |
| | WITH THE FIXTURES AND IS VERY HARD TO FOLLOW. PUT |
| | PUPING ON THE FLOOR PLAN WITH THE FIXTURES. (SEE POOL |
| | BATH PIPING LAYOUT ON SHT P-5.1 AS AN EXAMPLE). |
| | SECTIONS 106.1.1 &701.1. TABLES 710.1(1) & 710.1(2). |
| | |
| | 62. SHTS P-24, P-25 & P-26 INDICATE THE TOTAL DFU'S AND |
| | TOTAL DEVELOPED LENGTH FOR COMBINED VENTS SUCH AS |
| | RISERS 1 THRU 5, RISERS 6 THRU 13, RISERS 14 THRU 19 |
| | ETC. TABLE 916.1. |
| | |
| | 63. SHT P-27A DOES NOT REFLECT THE FLOOR PLAN AT RISERS |
| | 89, 93 & 94.--TWO RISERS NUMBERED 63. (ALSO SEE SHT |
| | P-001) PLEASE CORRELATE/CLARIFY SECTIONS 106.1.1 & |
| | 701.1. |
| | |
| | 64. SUBMIT MANUF SPECIFICATION FOR THE SUMP PUMPS. SHOW |
| | LISTING. (SEE SHT P-30). SECTION 303.4. |
| | |
| | 65. SHT P-27B RISER DIAGRAM INDICATES 5 SUMP PUMPS. |
| | MORE INFORMATION IS REQUIRED. PLEASE INDICATE WHAT |
| | LEVEL THESE SUMP PUMPS ARE LOCATED, INDICATE WHAT WILL |
| | BE PUMPED OUT AND SHOW COMPLIANCE WITH SECTION 712.2. |
| | IS THERE A LEVEL LOWER THAN THE LOWER GARAGE? PLEASE |
| | CLARIFY. SECTION 106.1.2.--RISER DOES NOT REFLECT |
| | THE FLOOR PLAN AT RISERS 1T, 2T, C8, C10, 27T, 25T, |
| | C12, 29T & CT1. PLEASE CORRELATE. SECTIONS 106.1.1 & |
| | 701.1. |
| | |
| | 66. SHT P28 MOST INFORMATION IS NOT LEGIBLE WITHOUT THE |
| | AID OF A MAGNIFYING GLASS. SECTIONS 106.1.1 & 106.1.2. |
| | PLEASE SUBMIT INFORMATION THAT IS OF SUFFICIENT |
| | CLAIRTY. |
| | |
| | 67. SHTS P28A THRU P-28D. INDICATE THE RISER NUMBERS SO |
| | THE RISERS CAN BE TRACKED THRU THE BUILDING. INDICATE |
| | WHERE THE RISER CONTINUES THAT IS NOT SHOWN ON THE |
| | SHEET. SOME OF THE INFORMATION CONTINUES AT THE TOP OF |
| | THE SHEET, SOME TO THE SIDE, AND SOME INFORMATION |
| | CONTINUES AT THE BOTTOM OF THE SHEET BUT DOES NOT |
| | INDICATE WHERE THE CONTINUED PIPE CAN BE LOCATED. |
| | UNABLE TO TRACK THE PIPING TO VERIFY PIPE SIZE OR |
| | SQUARE FOOTAGE BEING DRAINED. SECTIONS 106.1.1, 106.1.2 |
| | & 1101.1. ALSO TABLES 1106.2 & 1106.3. |
| | |
| | 68. SHT P-28E INDICATE RISER NUMBER RISER TO TRACK THE |
| | RISER THRU THE BUILDING AND TO VERIFY PIPE SIZE AND |
| | SQUARE FOOTAGE BEING DRAINED.--CLARIFY CONNECTION |
| | THAT INDICATES 12"-1970, 12"-25610, 1-1/4" CD & 1-1/2" |
| | CD.--CONDENSATE TO DRAIN SEPARATELY FROM THE |
| | BUILDING.--NUMEROUS PIPE SIZES THAT ARE NOT |
| | INDICATING WHAT THEY ARE ASSOCIATED WITH. PLEASE |
| | CLARIFY. SECTIONS 106.1.1, 106.1.2 & 1101.1. ALSO TABLE |
| | 1106.3. |
| | |
| | 69. SHT P-28F HORIZONTAL GARAGE PIPING ISOMETRIC |
| | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN TO THE 4" |
| | TRENCH DRAINS/SUMP PUMPS 21 & 22. PLEASE CORRELATE. |
| | SECTIONS 106.1.1 & 1101.1. |
| | |
| | 70. SHT P-29 THE FOLLOWING INFORMATION IS REQUIRED FOR |
| | THE SEPARATE GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. - THE ISOMETRIC RISER DIAGRAM SUBMITTED |
| | DOES NOT SHOW ALL LENGTHS OF PIPE, ALL SECTIONS OF |
| | PIPE, ALL RISERS AND DOES NOT REFLECT THE FLOOR PLAN. |
| | SOME BRANCH LINES DO NOT IDENTIFY THE APPLIANCES |
| | CONNECTING TO THE BRANCH LINE. DELETE ALL UNIONS FROM |
| | THE FUTURE LINES IN THE KITCHENS. FOR ALL FUTURE |
| | APPLIANCES, A SHUT OFF VALVE, A NIPPLE AND A CAP ARE |
| | REQUIRED. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. - NOT ALL PIPE |
| | SIZES SHOWN. |
| | |
| | C. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). - NOT ALL BTU LOADS ARE INDICATED. |
| | |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED WHEN |
| | COMMENT "A" IS ADDRESSED. |
| | |
| | E. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | F. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | H. SHOW ALL CUT SECTIONS AND CORRESPONDING LENGTHS AS |
| | WELL AS THE TOTAL DEVELOPED LENGTH DOWNSTREAM OF EACH |
| | REGULATOR. |
| | |
| | I. RISER DOES IT MEET CODE REQUIREMENTS. REGULATORS ARE |
| | REQUIRED AT ALL FIXTURES OR GROUP OF FIXTURES. MANY |
| | INDIVIDUAL FIXTURES FIXTURES SHOW NO REGULATORS. A SHUT |
| | OFF VALVE IS REQUIRED UPSTREAM OF EACH REGULATOR WITH A |
| | UNION DOWNSTREAM OF EACH SHUT OFF VALVE. SECTION |
| | 409.4. |
| | |
| | J. NOTE ON SHT P-29 INDICATES "3/4 INCH GAS UP & DOWN" |
| | PLEASE CLARIFY DOWN TO WHERE? SECTION 106.1.1. |
| | |
| | K.RISER DOES NOT REFLECT THE FLOOR PLAN. RISERS SHOWN |
| | FOR THE GAS BBQ GRILL SHOWN ON THE 7TH FLOOR SHOW THE |
| | FUTURE CONNECTIONS FOR THE KITCHEN OF THE UNITS. |
| | RISERS FOR THE KITCHEN SHOW THE BBQ GRILLS. PLEASE |
| | CORRELATE RISERS AND FLOOR PLAN. SECTION 106.1.1 & |
| | TABLE 402.4(3). |
| | |
| | L. SUBMIT MANUF SPECIFICATION SHEETS FOR THE |
| | REGULATORS. SHEETS SHALL SHOW LISTING AND THE MODEL |
| | NUMBER OF THE REGULATOR SHALL BE INDICATED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |