| 2008-03-03 11:23:02 | 1. ON PAGE A-1.00 FIRST INFORMATION BOX OF EGRESS |
| | CAPACITY SHOULD READ 102 NOT 112. |
| | |
| | 2. WRONG LIFE SAFETY CODE LISTED ON G-0.03. IT SHOULD |
| | READ THE FLORIDA FIRE PREVENTION CODE, 2003 LIFE SAFETY |
| | CODE AND NFPA 1, 2003 EDITION. |
| | |
| | 3. WET FIRE HYDRANTS ARE REQUIRED PRIOR TO, DURING, AND |
| | AFTER CONSTRUCTION. |
| | |
| | 4. STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION. |
| | |
| | 5. SUITABLE ACCESS SHALL BE PROVIDED FOR FIRE AND |
| | PARAMEDICAL EQUIPMENT. |
| | |
| | 6. TEMPORARY STANDPIPE SYSTEM REQUIRED WHEN THE |
| | BUILDING REACHED THREE STORIES OR THIRTY FEET IN |
| | HEIGHT. |
| | |
| | 7. STAIRWELL IDENTIFICATION SIGNS REQUIRED IDENTIFYING |
| | FLOOR LEVEL, STAIR IDENTITY, AND TERMINUS TOP AND |
| | BOTTOM. |
| | |
| | 8. SITE PLAN A-0.01 DOES NOT ILLUSTRATE ANY EXISTING OR |
| | NEW FIRE HYDRANTS. |
| | |
| | 9. BUILDING ADDRESS REQUIRED. A MINIMUM OF AT LEAST 6" |
| | HIGH WITH AT LEAST 1" WIDE NUMBERS SHALL BE PROVIDED. |
| | |
| | 10. KNOX-BOXES WILL BE REQUIRED FOR THE BUILDING. |
| | |
| | 11. PLEASE INDICATE HOW THE PARKING CONTROL LIFT GATES |
| | COULD IMPACT EXISTING FROM THE GARAGE ON PAGE A-1.00. |
| | |
| | 12. ELEVATOR WARNING SIGNS "IN CASE OF FIRE, DO NOT USE |
| | THE ELEVATORS"ARE REQUIRED. |
| | |
| | 13. ALL TRASH CHUTES ARE TO COMPLY WITH NFPA 82. |
| | |
| | 14. SEVERAL AREAS NOT IDENTIFIED ON PAGE A-2.10. |
| | |
| | 15. ALL REQUIRED STAIRS ARE TO BE EQUIPPED WITH |
| | STANDPIPES. |
| | |
| | 16. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| | COMPLETE AUTOMATIC FIRE SPRINKLER SYSTEM. |
| | |
| | 17. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| | INSTALLATION OF THE COMPLETE AUTOMATIC FIRE ALARM |
| | SYSTEM. THE AUTOMATIC FIRE SPRINKLER AND FIRE ALARM |
| | SYSTEM ARE TO BE MONITORED BY A UL LISTED CENTRAL |
| | STATION APPROVED FOR CENTRAL STATION SERVICE. |
| | |
| | 18. ELECTRIC POWERED SMOKE DETECTORS ARE REQUIRED ON |
| | EVERY LEVEL OF THE RESIDENTIAL UNITS. |
| | |
| | 19. HOW WILL THE PRIVATE ELEVATOR LOBBIES BE ACCESSED |
| | BY FIRE RESCUE. |
| | |
| | 20. PLEASE INDICATE WHICH ELEVATORS WILL BE STRETCHER |
| | ACCESSIBLE. |
| | |
| | 21. WHAT IS ANY TYPES OF POOL CHEMICALS WILL BE STORED |
| | IN THE POOL EQUIPMENT ROOM ON PAGE A-2.5.3. |
| | |
| | 22. DOOR NOTES INFORMATION BOX ON PAGE A-3.10 AND OTHER |
| | SHEETS, NOTE # 2 IS INCORRECT. SHOULD READ SECTION 7 |
| | NOT 5. |
| | |
| | 23. DOORS APPEAR TO SWING OVER THE PROPERTY LINE ON |
| | PAGE A-3.16. |
| | |
| | 24. DOOR SCHEDULE ON PAGE A-3.16 CONTAINS NO |
| | INFORMATION. |
| | |
| | 25. WHAT TYPE OF FIREWALL SEPARATION EXISTS BETWEEN THE |
| | ONE CAR GARAGES AND OTHER PORTIONS OF THE BUILDING. |
| | |
| | 26. SOME AIR CONDITIONER DOORS LOCATED IN CORRIDORS DO |
| | NOT APPEAR ON THE DOOR SCHEDULE. |
| | |
| | 27. DETAILS REQUIRED ON EIFS MATERIAL DISPLAYED ON THE |
| | PLANS. EIFS NOTED ON EXTERIOR INSULATION AND FINISH |
| | SYSTEM AND MISCELLANEOUS DETAILS. |
| | |
| | 28. ELECTRONIC SWITCHES, CHAIN AND LOCK REQUIRED ON |
| | FIRE LINE BACKFLOW DEVICE. |
| | |
| | 29. WHAT METHODS ARE TO BE EMPLOYED ON THE EXTERIOR |
| | STAIRS FOR SLIP RESISTANT METHODS. |
| | |
| | 30. PLEASE PROVIDE MANUFACTURERS DETAILS FOR THE CARBON |
| | MONOXIDE DETECTORS. |
| | |
| | 31. ALL FIRE AND SMOKE DAMPERS AFTER INSTALLATION SHALL |
| | BE DROP TESTED TO ENSURE PROPER OPERATION. |
| | |
| | 32. ON SEVERAL ELECTRICAL SHEETS, GAS GRILLS ARE NOTED. |
| | THESE TYPES OF GRILLS ARE NOT PERMITTED. |
| | |
| | 33. ON SP-1 ONLY A SIX INCH WATER MAIN ENTERS THE |
| | BUILDING. PLEASE EXPLAIN HOW THIS IS ENOUGH WATER.WHAT |
| | SIZE IS THE FIRE PUMP. |
| | |
| | 34. KNOX-BOX LOCKING CAPS ARE TO BE PROVIDED FOR THE |
| | FIRE DEPARTMENT CONNECTIONS. |
| | |
| | 35. PLEASE EXPLAIN WHY THE OPEN AREA IS NOT CONSIDERED |
| | AN ATRIUM. |
| | |
| | 36. THE FLOOR PLANS APPEAR TO BE VERY CONFUSING. PLEASE |
| | CORRECT THE PLANS AS NECESSARY TO MAKE THEM NOT AS |
| | CONFUSING. |
| | |
| | 37. PLEASE DECLARE IF THE BUILDING WILL BE CONSIDERED A |
| | HIGH-RISE STRUCTURE. |
| | |
| | 38. ALL RATED FIRE WALLS NEED TO BE IDENTIFIED ON THE |
| | PLANS. |
| | |
| | 39. WHERE WILL THE STANDPIPE HOSE VALVES BE INSTALLED |
| | WHEN DOUBLE DOORS OPEN INTO THE STAIRWELLS. |
| | |
| | 40. PRESCRIPTIVE STRENGTH REQUIREMENTS SHALL BE NOTED |
| | FOR ALL HANDRAILS AND GUARDRAILS. |
| | |
| | 41. PLEASE ILLUSTRATE ALL PORTABLE FIRE EXTINGUISHER |
| | LOCATIONS. |
| | |
| | 42. PLEASE DECLARE OCCUPANCY TYPE AND USE OF THE |
| | BUILDING. APARTMENTS OR CONDOMINIUM AND WHAT CODE |
| | OCCUPANCY TYPE IS BEING ADHERED TO. |
| | |
| | |