| 2008-01-28 16:57:39 | BUILDING PLAN REVIEW |
| | PERMIT: 07120262 |
| | ADD:2501 N FLAGLER DR |
| | CONT: "PLAN REVIEW- MAJOR WORKING DRAWING REVIEW |
| | TEL: (954)965-3636 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE W/ 2007 FBC |
| | REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. |
| | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| | /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH |
| | ADMINISTRATIVE CODE. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE2007 SUPPLEMENTS PLEASE UPDATE PLANS |
| | TO REFLECT THE CURRENT 2004 FBC WITH 2007 SUPPLEMENTS. |
| | |
| | 1F) NOTE: THE FAIR HOUSING GUIDELINES AND ANSI A |
| | 117.1-1998 WILL BE USED IN THIS REVIEW FOR COMPLIANCE |
| | WITH THE FAIR HOUSING ACT. THE ANSI A 117.1 STANDARD |
| | CONTAINS ONLY THE TECHNICAL CRITERIA, WHEREAS THE FAIR |
| | HOUSING ACT, THE REGULATIONS AND THE GUIDELINES CONTAIN |
| | BOTH SCOPING AND TECHNICAL CRITERIA. NOTE IN THE FAIR |
| | HOUSING GUIDELINE WHEN THE GUIDELINE REFERENCES THE |
| | ANSI A 117.1 IT IS THE 1986 STANDARD, NOT THE ANSI A |
| | 117.1- 1998. |
| | |
| | 2 ) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| | OF OCCUPANCY: |
| | A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT |
| | IS DESIGNED UPDATE WITH THE 2007 SUPPLEMENTS. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. PLEASE SEE 310.1 CONDOMINIUMS |
| | ARE CLASSIFIED AS R2, PLEASE CORRECT. |
| | SHEET A-8.04 DETAILS 7& 8 BOTH INDICATE TOWNHOUSE |
| | OR TOWNHOUSE CABANA, PLEASE CORRECT, THESE UNITS ARE |
| | NOT FEE SIMPLE ARE THEY? |
| | C) THE TYPE OF CONSTRUCTION AS DEFINEDIN CHAPTER 6, |
| | TABLE 601. PLANS INDICATE A TYPE 1 BUILDING THERE IS NO |
| | DESIGNATION AS TO IA OR IB. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F) |
| | WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| | BUILDING PERMIT |
| | . |
| | 3) SHEET G-0.03 HEADINGS BOTH CLASSIFICATION AND |
| | RESIDENTIAL BOTH INDICATE THE OCCUPANCY CLASSIFICATION |
| | AS A R-1 PLEASE CORRECT TO R-2 , THE COVERSHEET |
| | INDICATES GRAMERCY COURT CONDOMINIUM, PLEASE CORRECT |
| | SEE 310.1. |
| | |
| | 4) SHEET G-0.03 RESIDENTIAL HEADING CODE SECTION 1203.2 |
| | INDICATES CEILING HEIGHTS WHILE THIS SECTION DEALS WITH |
| | ATTIC VENTILATION. |
| | |
| | 5) SHEET G-0.03 HEADING GARAGE AGAIN TYPE I BUILDING |
| | INDICATE "A OR B ". TABLE 503 & TABLE 601. |
| | |
| | 6) SHEET G-0.03 HEADING BUILDING INSULATION, MISSING |
| | SECTIONS (NEW TO THE 2004 FBC): |
| | A)1207.2 AIR BORNE SOUND- SHEET A-8.13 WALL |
| | RATINGS DO NOT PROVIDE THE (STC) RATING |
| | B)1207.3 STRUCTURE-BORNE SOUND, FLOOR/CEILING |
| | ASSEMBLIES (IIC) RATING FLOOR/CEILING ASSEMBLIES |
| | INDICATE CODE COMPLIANCE |
| | |
| | 6) SHEET G-002 HEADING SAFEGUARDS, WRONG CODES SECTION |
| | AND YEAR IN THE REFERENCED STANDARD.2004 FBC CHAPTER |
| | 35 REFERENCED STANDARDS RECOGNIZES ASCE 7-02 .ALSO |
| | 1603.1.4 WIND DESIGN DATA. |
| | 7)THRESHOLD INSPECTION PLANFL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA |
| | AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| | |
| | 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURALINSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 8) THRESHOLD INSPECTOR: |
| | WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL |
| | INSPECTOR PROGRAM AT (561)805-6711 FOR FURTHER |
| | INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 9) THRESHOLD BLDG, REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE |
| | BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY |
| | THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 10A)PLEASE PROVIDE (3) ORIGINAL SIGNED AND EMBOSSED |
| | SEAL SOILS REPORTS. 1802.2.1 QUESTIONABLE SOIL. WHERE |
| | THE SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR |
| | WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED |
| | IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL |
| | REQUIRE THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| | SECTIONS 1802.4 THROUGH 1802.6. |
| | |
| | 10B) 1802.2.3 GROUND-WATER TABLE. A SUBSURFACE SOIL |
| | INVESTIGATION SHALL BE PERFORMED TO DETERMINE WHETHER |
| | THE EXISTING GROUND-WATER TABLE IS ABOVE OR WITHIN 5 |
| | FEET (1524 MM) BELOW THE ELEVATION OF THE LOWEST FLOOR |
| | LEVEL WHERE SUCH FLOOR IS LOCATED BELOW THE FINISHED |
| | GROUND LEVEL ADJACENT TO THE FOUNDATION. |
| | EXCEPTION: A SUBSURFACE SOIL INVESTIGATION SHALL NOT BE |
| | REQUIRED WHERE WATERPROOFING IS PROVIDED IN ACCORDANCE |
| | WITH SECTION 1807 . |
| | 10C)SHEET S1.2 INDICATES THAT GROUND WATER MAY BE AN |
| | ISSUE IN TIMES OF STORM EVENTS. |
| | PLEASE SEE 1807.2 DAMPPROOFING, 1807.3. WATERPROOFING |
| | REQUIRED. |
| | |
| | 11) NOTE INFORMATIONAL,109.3.10* IMPACT OF |
| | CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY |
| | THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO |
| | ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY, |
| | UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID |
| | PROPERTY PURSUANT TO A CONSENT BY THE APPLICABLE |
| | PROPERTY OWNER, UNDER TERMS & CONDITIONS AGREEABLE TO |
| | THE APPLICABLE PROPERTY OWNER. THIS INCLUDES BUT IS NOT |
| | LIMITED TO THE CONTROL OF DUST, NOISE, WATER OR |
| | DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF |
| | CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL |
| | NOT ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE |
| | FLOWS SERVING ADJACENT PROPERTIES, & MAY REQUIRE |
| | SPECIAL DRAINAGE DESIGN COMPLYING WITH ENGINEERING |
| | STANDARDS TO PRESERVE THE POSITIVE PATTERNS OF THE |
| | AFFECTED SITES. ACCORDINGLY, DEVELOPERS, CONTRACTORS, |
| | AND OWNERS OF ALL NEW RESIDENTIAL DEVELOPMENT, |
| | INCLUDING ADDITIONS, POOLS, PATIOS, DRIVEWAYS, DECKS, |
| | OR SIMILAR ITEMS, ON EXISTING PROPERTIES RESULTING IN A |
| | DECREASE IN EXCESS OF 800SQ FT OF PERMEABLE LAND AREA |
| | ON ANY PARCEL SHALL AS A PERMIT CONDITION, PROVIDE A |
| | PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY |
| | INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON |
| | COMPLETION OF THE IMPROVEMENT, A CERTIFICATION FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO THE INSPECTOR |
| | IN ORDER TO RECEIVE APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 12) NOTE INFORMATIONAL, 109.3.10.1 HURRICANE |
| | PROTECTION. IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| | ALLOW CONSTRUCTION RELATED MATERIALS EQUIPMENT AND |
| | DEBRIS TO REMAIN LOOSE OR OTHERWISE UNSECURED AT A |
| | CONSTRUCTION SITE FROM 24 HRS. AFTER A HURRICANE WATCH |
| | HAS BEEN ISSUED UNTIL THE HURRICANE WATCH OR WARNING |
| | HAS BEEN LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED FROM THE |
| | CONSTRUCTION SITE OR SECURED IN SUCH A MANNER AS TO |
| | MINIMIZE THE DANGER OF SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS CAUSING DAMAGE TO PERSONS OR |
| | PROPERTY FROM HIGH WINDS. ANY PERSONS WHO FAILS TO |
| | COMPLY TO REMOVE OR SECURE THE CONSTRUCTION MATERIALS |
| | EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A HURRICANE |
| | WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| | EXCEED $500.00.IN ADDITION TO THE ABOVE, A LICENSED |
| | CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE SUBJECT |
| | TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 13) SHEET A-1.00: BASIC CRITERIA: |
| | 13A)BASIC CRITERIA, PLANS DO NOT INDICATE IF THIS TYPE |
| | I BUILDING IS A TYPE I-A OR I-B, |
| | TABLE 503/ TABLE 603. COMMON TO ALL LIFE SAFETY |
| | SHEETS PLEASE CORRECT. |
| | |
| | 13B) BASIC CRITERIA, PLANS INDICATE A R1 OCCUPANCY NOT |
| | A R2 OCCUPANCY SEE SECTION 310. |
| | CONDOMINIUMS ? R2. COMMON TO ALL LIFE SAFETY |
| | SHEETS, PLEASE CORRECT. |
| | |
| | 13C) LIFE SAFETY LEGEND, THE FIRE WALL RATINGS SYMBOLS |
| | ARE SO SMALL THEY ARE ILLEGIBLE AS TO THE HOUR RATING, |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. 706 AND 707. |
| | |
| | 14) SHEET A-1.01: |
| | 14A) THE FIRST FLOOR PLANS DOES NOT INDICATE A SECTION |
| | OR NOTE THAT WILL DEAL WITH STAIRS THAT CONTINUE BELOW |
| | GRADE AND REQUIRED BARRIER AND SIGNAGE (STAIR# 11). |
| | 1019.1.6 DISCHARGE IDENTIFICATION. A STAIRWAY IN AN |
| | EXIT ENCLOSURE SHALL NOT CONTINUE BELOW THE LEVEL OF |
| | EXIT DISCHARGE UNLESS AN APPROVED BARRIER IS PROVIDED |
| | AT THE LEVEL OF EXIT DISCHARGE TO PREVENT PERSONS FROM |
| | UNINTENTIONALLY CONTINUING INTO LEVELS BELOW. |
| | DIRECTIONAL EXIT SIGNS SHALL BE PROVIDED AS SPECIFIED |
| | IN SECTION 1006.3 . |
| | |
| | 14B) THE LIFE SAFETY PLAN DOES NOT INDICATE TO WHICH |
| | STAIR THE LOWER LEVEL PARKING GARAGE WAS FIGURED TO, |
| | JUST THE TOTAL ALLOWABLE LOADS THE STAIRS CAN HANDLE |
| | AND THE ACTUAL OCCUPANT LOAD. STAIR# 11 IS CONSIDERED A |
| | CONVERGING STAIR WHERE THE OCCUPANT LOAD FROM ABOVE AS |
| | WELL AS FROM BELOW WILL BE EXITING AT THE SAME TIME, |
| | PLEASE INDICATE THE OCCUPANT LOAD FROM BOTH THE LOWER |
| | LEVEL AND WORST CASE FLOOR LEVEL, MEZZANINE LEVEL, |
| | PLEASE INDICATE HOW YOU MEET CODE COMPLIANCE?1004.5 |
| | EGRESS CONVERGENCE. |
| | WHERE MEANS OF EGRESS FROM FLOORS ABOVE AND BELOW |
| | CONVERGE AT AN INTERMEDIATE LEVEL, THE CAPACITY OF THE |
| | MEANS OF EGRESS FROM THE POINT OF CONVERGENCE SHALL NOT |
| | BE LESS THAN THE SUM OF THE TWO FLOORS. |
| | |
| | 15) SHEET A-102: |
| | 15A) PLEASE PROVIDE THE SQUARE FOOT CALCULATIONS FOR |
| | THE FIRST FLOOR LOBBY AND THE MEZZANINE LEVEL, IT |
| | APPEARS TO BE OVER THE 1/3RD FLOOR AREA FOR A |
| | MEZZANINE. 505.2 AREA LIMITATION. |
| | |
| | 15B) THE AREA IN QUESTION, THE LOBBY & MEZZANINE, ARE |
| | OVER THE ALLOWABLE 1/3RD AREA THEN THIS AREA DOES |
| | QUALIFY AS A 2 STORY ATRIUM. THEN THE REQUIREMENTS OF |
| | 404 WOULD NEED TO BE MET. . CONVERGENCE |
| | |
| | 16) SHEET A-102 & A-2.2.2 THE RECREATION ROOM# 217 DOES |
| | NOT PROVIDE THE SQUARE FOOTAGE OR OCCUPANT LOAD FOR |
| | THIS ROOM, PLEASE PROVIDE.2,115 SQ FT / 7= 303 |
| | OCCUPANT LOAD. PLEASE SEE TABLE 1014.1 REQUIRING TWO |
| | MEANS OF EGRESS . |
| | |
| | 17)SHEET A-102 & A-2.22 THE RECREATION ROOM# 217 |
| | DOES NOT INDICATE WALL TYPE AND FIRE RATINGS WITH WALL |
| | TAGS, PLEASE PROVIDE FOR CODE COMPLIANCE. |
| | |
| | 18) SHEET A-101 & A-2.12 STAIR# 11DOOR 150 SWINGS |
| | AGAINST THE EGRESS PATTERN WITH AN OCCUPANT LOAD |
| | GREATER THAN 50. 108.1.2. PLEASE CORRECT. |
| | |
| | 19)SHEET A-2.10: |
| | |
| | 19A)THE HANDICAPPED RAMP THAT LEADS INTO THE CORRIDOR |
| | 101 PLEASE PROVIDE THE WIDTH OF THE RAMP AND DIMENSIONS |
| | FOR THE TOP LANDING, BOTTOM LANDING AND TURNING RADII |
| | LOCATED AT BOTH ENDS OF THE RAMP. PLANS INDICATE SEE |
| | A-2.12 FOR RAMP DETAILS AND DIMENSIONS. PLEASE SEE FAIR |
| | HOUSING GUIDELINES ANSI 4.8. 405.7.4 CHANGE IN |
| | DIRECTION. |
| | |
| | 19B) STAIR NUMBER (1) DETAILS FOUND ON A-5.01.1 DETAIL |
| | 2AT DOOR 105 DOES NOT DEPICT THE |
| | HANDRAIL ACCURATELY, IT EXTENDS PAST THE STEP THE |
| | REQUIRED 11? BUT DOES NOT PROJECT THE HORIZONTAL 12? |
| | SEE FIGURE 505.10.3.BOTTOM HANDRAIL EXTENSIONS AT |
| | STAIRS. THIS IS COMMON TO A LOT OF STAIRS WHERE AND |
| | DOORWAYS OCCUR. SEE SHEET A-5.10 THIS IS ONE SHEET |
| | WHERE THE 11? THAT EXTENDS BEYOND THE FIRST RISER DOES |
| | NOT EVEN HAVE ENOUGH ROOM. ALSO SEE 1009.11.5 CONTINUE |
| | TO SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM |
| | RISER. THIS COMMENT WILL NOT BE COPIED FOR EACH |
| | INSTANCE WHERE A CODE VIOLATION OCCURS. THIS SITUATION |
| | DOES OCCUR REPEATEDLY. |
| | |
| | 19C) SHEET A-5.10 STAIR 13 LOWER LEVEL ALSO HAS A |
| | COLUMN THAT STICKS INTO THE CLEAR WIDTH OF THE STAIR |
| | WAY REDUCING THE EFFECTIVE WIDTH OF THE STAIR, THE LIFE |
| | SAFETY PLAN DOES NOT INDICATE THE AMOUNT OF OCCUPANTS |
| | PER STAIR, 1003.3.3 HORIZONTAL PROJECTIONS. |
| | ELEMENTS CANNOT PROJECT OVER A WALKING SURFACE MORE |
| | THAN 4 INCHES (102 MM) WHEN THEY ARE LOCATED BETWEEN 27 |
| | AND 80 INCHES (686 AND 2032 MM) ABOVE THE FLOOR. |
| | HANDRAILS CAN PROJECT UP TO 4 ? INCHES (114 MM) FROM |
| | THE WALL. |
| | |
| | 19D) DETAILS A-5.02 STAIRWAYS DETAIL 3 & 6 DO NOT MEET |
| | THE FAIR HOUSING ANSI A-117.1 SECTION DOES NOT MEET THE |
| | REQUIREMENTS OF 404.2.6 TWO DOORS IN SERIES. THIS |
| | COMMENT WILL NOT BE COPIED FOR EACH INSTANCE WHERE A |
| | CODE VIOLATION OCCURS. THIS SITUATION DOES OCCUR |
| | REPEATEDLY. |
| | |
| | 20) SHEET A-3.10 |
| | 20A) SOME OF THE A/C CLOSETS IN THE EXIT ACCESS |
| | CORRIDORS ARE MISSING THE DOOR IDENTIFICATION NUMBER, |
| | AND OTHERS SUCH AS DOOR 11 & 16 DO NOT SHOW UP ON THE |
| | DOOR SCHEDULE FOR THE COMMON AREAS. 106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 20B) IN THE AREAS AROUND THE A/C CLOSETS IT CAN NOT BE |
| | DETERMINED WHERE THE RATED WALL IS LOCATED , NO WALL |
| | MARKERS AND THE DOORS DO NOT SHOW UP ON THE DOOR |
| | SCHEDULE TO INDICATE FIRE RATINGS, PLEASE PROVIDE BOTH |
| | THE DOOR IDENTIFICATION AND WALL RATINGS, 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, TABLE 1016 & TABLE |
| | 715.3. SHEET A-2.10 THERE ALSO THE DOOR TAGS ARE |
| | MISSING.. IN OTHER AREAS WHERE THERE ARE WALL MARKERS |
| | IT INDICATESA 2C TYPE WALL ON THE WALL COMMON TO THE |
| | INDIVIDUAL UNITS, THESE WALLS ARE TO BE FIRE RATED SEE |
| | TABLE 1016.THIS COMMENT WILL NOT BE COPIED FOR EACH |
| | INSTANCE WHERE A CODE VIOLATION OCCURS. THIS SITUATION |
| | DOES OCCUR REPEATEDLY ON THE FIRST FLOOR. |
| | |
| | 20C) THIS COMMENT WILL SERVE FOR ALL CASES WHERE THIS |
| | VIOLATION OCCURS. NOTICEABLY THERE IS A NUMBER OF |
| | VERTICAL EXITS THAT ARE LOCATED IN THE CENTER OF THE |
| | BUILDING AND EMPTY OUT INTO CORRIDORS THAT LEAD TO THE |
| | EXTERIOR OF THE BUILDING, THIS IS HOW THE PLAN IS |
| | CURRENTLY DEPICTED. |
| | |
| | 20C) 1) NOTE ONCE YOU ARE IN A 2 HR RATED VERTICAL EXIT |
| | THE SAME AMOUNT OF PROTECTION AS IF IN THE VERTICAL |
| | EXIT (1020.1), THIS MEANS 2 HR ENCLOSURE. |
| | |
| | 20C) 2) THE FLOOR, WALLS AND CEILING WILL ALL HAVE TO |
| | HAVE THE 2 HOUR RATING, IF THE WALLS GO ALL THE WAY UP |
| | TO THE FLOOR SLAB ABOVE THEN THE CEILING DOES NOT NEED |
| | TO BE RATED. SEE 1020.3, THERE CAN BE NO MECHANICAL |
| | SYSTEMS, PLUMBING, ELECTRICAL SYSTEMS IN THIS ENCLOSURE |
| | BUT THAT REQUIRED FOR THE ENCLOSURE JUST LIKE THE |
| | VERTICAL EXIT. |
| | |
| | 20C) 3)REMEMBER THIS IS CONSIDERED AN EXTENSION TO |
| | THE EXIT, THE OBJECTIVE IS TO MINIMIZE FIRE FROM |
| | SPREADING INTO THE EXIT PASSAGEWAY AND ENDANGERING THE |
| | OCCUPANTS OR EVEN PREVENTING THE USE OF THE EXIT AT A |
| | TIME WHEN IT IS NEEDED MOST. THE LIMITATION ON OPENINGS |
| | APPLIES REGARDLESS OF THE FIRE PROTECTION RATING OF THE |
| | OPENING PROTECTIVE. ROOMS THAT NORMALLY DO NOT OPEN |
| | INTO THE EXIT OR EXIT PASSAGEWAY ARE BUT NOT LIMITED TO |
| | TOILET ROOMS, ELECTRICAL/ MECHANICAL EQUIPMENT ROOMS |
| | AND JANITORIAL CLOSETS. ALSO NOTE THAT ELEVATORS CAN |
| | NOT OPEN DIRECTLY INTO AN EXIT PASSAGEWAY PLEASE SEE |
| | 1020.4 OPENINGS AND PENETRATIONS. |
| | |
| | 20C) 4) PENETRATIONS, INTO AND OPENINGS THROUGH AN EXIT |
| | PASSAGEWAY ARE PROHIBITED EXCEPT FOR THE REQUIRED EXIT |
| | DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR THE |
| | INDEPENDENT PRESSURIZATION, SPRINKLER PIPING, |
| | STANDPIPES, ELECTRICAL RACEWAY FOR THE FIREDEPARTMENT |
| | COMMUNICATION AND ELECTRICAL RACEWAY SERVING THE EXIT |
| | PASSAGEWAY AND TERMINATINGAT A STEEL BOX NOT |
| | EXCEEDING 16 SQ INCHES SUCHPENETRATIONS SHALL BE |
| | PROTECTED IN ACCORDANCE WITH 712. |
| | |
| | |
| | |
| | 20D) IN REVIEWING THE WALLIDENTIFICATION FOUND ON |
| | SHEETA-8.1.3 THE WALLS THAT SEPARATE THE CONDO UNITS |
| | FROM EACH OTHER AND THE COMMON AREAS ARE MISSING THE |
| | SOUND TRANSMISSION COEFFICIENT, PLEASE SEE 1207 |
| | AIR-BORNE SOUND. |
| | |
| | 20E) PLEASE ALSO PROVIDE CODE COMPLIANCE FOR 1207.3 |
| | STRUCTURAL-BORNE SOUND TRANSMISSION. |
| | |
| | 20F) A-3.10 PROVIDES THE WALL TYPES FOR THE SHAFT THAT |
| | ENCLOSES THE TRASH CHUTE. THERE IS NO WALL |
| | IDENTIFICATION TAGS FOR THE SHAFT WALL SURROUNDING THE |
| | TRASH CHUTE.707.4 REQUIRES A 2HR FIRE RATING, PLEASE |
| | CORRECT. THIS COMMENT WILL NOT BE COPIED FOR EACH |
| | INSTANCE WHERE A CODE VIOLATION OCCURS. THIS SITUATION |
| | DOES OCCUR REPEATEDLY. |
| | |
| | 21) SHEET A-3.13: |
| | 21A) CORRIDOR 101 DOES NOT PROVIDE ANY WALL RATINGS NOR |
| | ANY DOOR IDENTIFICATION. |
| | 707.4, TABLE 1016 & TABLE 715.3 |
| | |
| | 21B) STAIR# 9 AND ELEVATOR# 9 ARE MISSING WALL TAGS, |
| | SHAFTS, 707.4, TABLE 1016 & |
| | TABLE 715.3. |
| | |
| | 22) SHEET A-3.14: |
| | 22A) THERE ARE TWO RAMPS LOCATED ON THE EXTERIOR OF THE |
| | BUILDING, NO INFORMATION ON SLOPE OF RAMP OR HANDRAILS. |
| | FAIR HOUSING ANSI A117.1- 98405.7.1 SLOPE AND 405.8 |
| | HANDRAILS. |
| | |
| | 23) SHEET A3.15, PLEASE PROVIDE INFORMATION FOR THE |
| | WHEEL CHAIR LIFT PER FAIR HOUSING ANSI A 117.1- 408. |
| | |
| | 24SHEET A-3.16: |
| | 24A) PLANS DO NOT INDICATE WALL IDENTIFICATION TAGS FOR |
| | WALL RATINGS.TABLE 1016 & TABLE 715.3. |
| | |
| | 24B) PLANS DO NOT PROVIDE INFORMATION FOR THE RAMP |
| | LOCATED ON THE EXTERIOR OF THE BUILDING. FAIR HOUSING |
| | ACT ANSI A117.1 SEE SECTION 405.1- 405.10. |
| | |
| | 24C) PLEASE PROVIDE THE DIMENSION FROM THE EXIT DOOR TO |
| | THE PROPERTY LINE. 1023.3 EXIT DISCHARGE LOCATION. |
| | EXTERIOR BALCONIES, STAIRWAYS AND RAMPS SHALL BE |
| | LOCATED AT LEAST 10 FEET (3048 MM) FROM ADJACENT LOT |
| | LINES AND FROM OTHER BUILDINGS ON THE SAME LOT UNLESS |
| | THE ADJACENT BUILDING EXTERIOR WALLS AND OPENINGS ARE |
| | PROTECTED IN ACCORDANCE WITH SECTION 704 BASED ON FIRE |
| | SEPARATION DISTANCE. ALSO SEE 1023.5.2. |
| | |
| | 24D) PLEASE PROVIDE THE RATING OF THE EXTERIOR WALL |
| | NEXT TO THE PROPERTY LINE AND OPENING PROTECTIVE. TABLE |
| | 602 & TABLE 704.8. |
| | |
| | 24E) ON THE RIGHT SIDE OF THE SHEET WHAT APPEARS TO BE |
| | THE PROPERTY LINE THE EXTERIOR DOORS SWING OVER THE |
| | PROPERTY LINE. 3202.2. |
| | |
| | |
| | 25) SHEET A-3.18: |
| | 25A)DEPENDING ON THE OUT COME OF COMMENT 15A-B THE |
| | STAIR# 11 MAY NOT BE USED AS A VERTICAL EXIT ENCLOSURE |
| | SINCE THE STAIR DOES NOTCONTINUE TO THE EXTERIOR OF |
| | THE BUILDING AND DOES CONNECT WITH THE LOWER FLOOR. IF |
| | THE CALCULATIONS ON THE SO CALLED MEZZANINE LEVEL ARE |
| | OVER 30 5 OF THE FIRST FLOOR SQUARE FOOT AREA THEN IT |
| | WILL BE CONSIDERED A 2ND FLOOR AND EXCEPTION 8 AND 9 OF |
| | 1019.1 CAN NOT BE USED . |
| | |
| | 25B) PLEASE INDICATE HOW THE ACCESSIBLE ENTRANCE TO THE |
| | RESIDENCE LOBBY, PLEASE SHOW CHANGE IN GRADE. FAIR |
| | HOUSING ANSIA117.1 303.1. |
| | |
| | 25C) PLEASE PROVIDE INFORMATION ON THE PRIVATE |
| | ELEVATORS, SEE ANSI A117.1 1002.7 OR 1003.7. |
| | |
| | 26) SHEET A-3.20: |
| | 26A) PLEASE PROVIDE WALL TAGS FOR ELEVATOR# 1, TABLE |
| | 704.8 & 1016.1. |
| | |
| | 26B) PLEASE PROVIDE ADDITIONAL INFORMATION IT APPEARS |
| | THAT A WON DOOR IS BEING INSTALLED IN FRONT OF THE |
| | ELEVATOR PROVIDE RATING. |
| | |
| | 26C) TRASH CHUTE DOORS 204 &205, (THIS COMMENT WILL NOT |
| | BE COPIED FOR EACH INSTANCE WHERE A CODE VIOLATION |
| | OCCURS. THIS SITUATION DOES OCCUR REPEATEDLY FOR THE |
| | 2ND FLOOR AND FLOORS ABOVE), SEE 707.13.3. ? HR |
| | SELF-CLOSING OR AUTOMATIC-CLOSING UPON DETECTION OF |
| | SMOKE. |
| | |
| | 27) SHEET A-3.23: |
| | 27A) AT ELEVATOR# 9 THERE IS A SHAFT ENCLOSURE BUT NO |
| | WALL TAG INFORMATION IS PROVIDED.SEE 707.4. |
| | |
| | 27B) UNIT ?G? THE A/C CLOSET IS NOT SHOWN ON THE UNIT |
| | DOOR SCHEDULE, CLOSET # 11 IS MARKED ON THE DOOR |
| | SCHEDULE AS THE A/C CLOSET, DISCREPANCY 106.1. THIS |
| | SITUATION DOES OCCUR REPEATEDLY AND WILL NOT BE COPIED |
| | FOR EACH INSTANCE. |
| | |
| | 28) SHEET# A-3.26 PLEASE PROVIDE WALL IDENTIFICATION |
| | TAG FOR SHAFT NEXT TO STAIR# 10 AND ACROSS THE |
| | CORRIDOR. PLEASE SEE 707.4. |
| | |
| | 29) SHEET A-3.28: |
| | 29A) PLEASE PROVIDEFOR THE RECREATION RESTROOMS |
| | DIMENSIONS FOR BOTH DIRECTIONS IN THE DISABLED |
| | RESTROOMS AND PROVIDE THE TURNING RADIUS. FAIR HOUSING |
| | ACT, ANSI A117.1-303.4.1 TURNING RADIUS. |
| | |
| | 29B) THE MEZZANINE LEVEL, PLEASE PROVIDE A CUT SECTION |
| | THROUGH THE WHAT MAY BE A HAND RAIL OR GLASS WALL, |
| | PLANS ARE NOT CLEAR AS TO WHAT THIS ELEMENT MAY BE? |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED, 404.5, |
| | EXCEPTION# 1. |
| | |
| | 29C) PLEASE PROVIDE A SECTION THROUGH AND DETAILS OF |
| | WHAT MAY APPEAR AS A SERVING TABLE OR POSSIBLE GALLEY |
| | KITCHEN, 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 29D) PROVIDE SECTION THROUGH OF THE CURTAIN WALL SYSTEM |
| | AND TYPE OF GLAZING AND SAFETY GLAZING , PLEASE SEE |
| | 2406.3. |
| | |
| | 30) SHEET A3.30: |
| | 30A) PLEASE PROVIDE IF THE SHAFT ADJACENT TO THE A/C |
| | CLOSET IS FOR WITHIN THE UNIT OR FOR MORE THAN 2 |
| | FLOORS? ADDITIONAL INFORMATION REQUIRED 106.1.2. THIS |
| | ALSO HOLDS TRUE FOR THE SHAFT THAT IS LOCATED BETWEEN |
| | BEDROOMS. |
| | |
| | 31) SHEET A-3.31: |
| | 31A)PLEASE PROVIDE ADDITIONAL INFORMATION FOR THIS |
| | AREA, EITHER ON THE LIFE SAFETY PLAN OR THIS SHEET |
| | PROVIDE THE SQ FT OF THIS ROOM THE AREA IN SQ FT PER |
| | OCCUPANT AND THE OCCUPANT LOAD SEE TABLE 1004.1.2. WITH |
| | SIGNIFICANT DIFFERENCES IN SQUAREFEET AND OCCUPANT |
| | LOADING THAN SHEET A-1.03 A ROUGH CALCULATION OF THE |
| | EXTERIOR BALCONY, AND SOCIAL ROOM 5724 SQ FT / 7= 817 |
| | OCCUPANT LOAD NEITHER THE DOORWAYS NOR STAIRS WILL |
| | HANDLE THIS AMOUNT OF PEOPLE. TABLE 1018.1 WOULD ALSO |
| | REQUIRE A THIRD EXIT. PLANS DO NOT INCLUDE TABLE AND |
| | CHAIR LAYOUT SO THE MORE RESTRICTIVE OCCUPANT LOADING |
| | OF 7 SQ FT PER PERSON WILL BE USED TO DETERMINE |
| | OCCUPANT LOADING. |
| | |
| | 31B) THE RECREATION DECK BELOW THE FIRE RATINGS ON THE |
| | COLUMNS IS PROVIDED, THEY ARE MISSING ON THIS DECK, |
| | TABLE 601. |
| | |
| | 31C) ADDITIONAL COMMENTS MAY APPEAR FROM THE NEXT |
| | REVIEW, PLEASE PROVIDE CUT SECTIONS AND DETAILS OF THE |
| | BAR AND KITCHEN ELEMENTS SO THEY MAY REVIEWED FOR FAIR |
| | HOUSING REQUIREMENTS, ANSI A-117.1. |
| | |
| | 31D) PLANS ARE NOT CLEAR WHERE THE ROTUNDA PORTION OF |
| | THE SOCIAL ROOM, A HASHED LINE IN FRONT OF THE WINDOWS |
| | IS NOT CLEAR, IF THIS IS TRULY WHERE THE DECK STOPS AND |
| | THE GLASS WOULD ACTUALLY BE CURTAIN-WALL DESIGN? |
| | ADDITIONAL INFORMATION IS REQUIRED.106.1.2. |
| | |
| | 31E) PLEASE PROVIDEFOR THE SOCIAL ROOM RESTROOMS |
| | DIMENSIONS FOR BOTH DIRECTIONS IN THE DISABLED |
| | RESTROOMS AND PROVIDE THE TURNING RADIUS. FAIR HOUSING |
| | ACT, ANSI A117.1-303.4.1 TURNING RADIUS. |
| | |
| | 31F) THE CATERING KITCHEN INDICATES A FIRE RATED CHASE |
| | BUT NO WALL IDENTIFICATION TAGS ARE PROVIDED, SEE 707.4 |
| | SHAFTS. |
| | |
| | 31G) THE PLANS ARE MISSING INFORMATION ON WALL TAGS ON |
| | STAIR# 8, SHAFTS 707.4. |
| | |
| | 32)SHEET A3.41.PLEASE REFIGURE SQUARE FOOT AREA FOR |
| | THIS DECK, SHEET A-1.04 INDICATES 2160 SQ FT, PLEASE |
| | RECALCULATE IF TABLES AND CHAIRS ARE SHOWN THEN THE 15 |
| | SQ FT PER PERSON, NET IS ALLOWABLE, TABLE 1004.1.2 NET |
| | IS WALL LINE NOT CABINET LINE. |
| | |
| | 33)SHEETS A-3.70-A-3.72: |
| | 33A) INDICATE AN INTERIOR CORRIDOR WITH ELEVATOR |
| | LANDINGS BUT NO ELEVATOR LOBBY, PLEASE SEE 707.14.1. |
| | |
| | 33B) PLANS A-3.71 AND A-3.72 INDICATE THE INTERIOR |
| | CORRIDOR CONTINUES BUT THE MIDDLE 7 UNITS ARE NOT |
| | DEPICTED, 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 33C) UNIT DOORS ARE NOT FIRE RATED TABLE 715.3 CORRIDOR |
| | WALLS 1HR DOORS 20 MINUTES. |
| | |
| | 33D) ELEVATOR MACHINE ROOM WALLS 2 HR RATED, OPENING |
| | PROTECTIVES 1 ? HR TABLE 715.3. |
| | |
| | 33E) PLANS A-3.70- A-3.72 TRASH CHUTE WALLS DO NOT HAVE |
| | WALL IDENTIFICATION TAGS FOR FIRE RATING, 707.4. |
| | |
| | 33F) PLEASE PROVIDE THE MANUFACTURERS SPECIFICATION FOR |
| | THE BAR-B-Q GRILL, PLANSINDICATE THE USE OF GRILL |
| | UNDER ROOF IN SOME CABA?AS. ADDITIONAL INFORMATION |
| | REQUIRED 106.1.2/ |
| | 2801.1. BARBECUES SHALL COMPLY WITH THE FLORIDA |
| | BUILDING CODE, MECHANICAL. |
| | |
| | 34) UNIT KITCHENS: |
| | 34A) NOTE THE PLANS DO NOT PROVIDE THE CLEAR FLOOR |
| | SPACE AT EACH OF THE APPLIANCES. FAIR HOUSING ANSI |
| | A-117.1 804.7.1. CLEAR FLOOR OR GROUND SPACE. ON ALL OF |
| | THE KITCHEN UNITS |
| | PROVIDE THE CLEAR FLOOR SPACE REQUIRED FOR EACH |
| | APPLIANCE ON PLANS. IF THE PARALLEL APPROACH IS |
| | INDICATED, NOTE THIS APPROACH IS TO BE CENTERED ON THE |
| | APPLIANCE. |
| | |
| | 34B) PLEASE REVIEW KITCHENS FOR THE REQUIRED 40? CLEAR |
| | FOR GALLEY KITCHENS AND THE 60? FOR |
| | U-SHAPED KITCHENS NOTE THIS SPACE CAN BE REDUCED IF THE |
| | END OF THE U-SHAPED KITCHEN HAS A SINK AND REMOVABLE |
| | BASE CABINET OR A COOK TOP AND REMOVABLE BASE CABINET. |
| | A-3.10UNIT A-GRND INDICATES A OVEN AT THE END OF A |
| | U-SHAPED KITCHEN PLEASE SEE FAIR HOUSING GUIDELINES |
| | CHAPTER 7. |
| | |
| | 34C) SHEET A-3.20 UNIT A INDICATES A OVEN AT THE REAR |
| | OF A 40? WIDE U-SHAPED KITCHEN, PLEASE CORRECT. SEE |
| | FAIR HOUSING GUIDELINES CHAPTER 7. |
| | |
| | 34D) A-3.24 UNIT ?N? LESS THAN THE 40 INCHES REQUIRED |
| | BETWEEN COUNTERTOP AND ADJACENT WALL. ANSI A-117.1 |
| | 804.2.2/40INCHES REDUCED SPACE WITH REMOVAL BASE AT |
| | COUNTER COOK TOP. |
| | |
| | 34E) A-3.26 UNIT ?U? AND ?U-R? LESS THAN THE 40 INCHES |
| | REQUIRED BETWEEN COUNTERTOP AND ADJACENT WALL. ANSI |
| | A-117.1 804.2.2 SEE DISHWASHER AND ADJACENT WALL. |
| | |
| | 34F)A-3.31 SOCIAL ROOM BAR AND KITCHEN, THE PLANS DO |
| | NOT PROVIDE ANY ELEMENTS TO REVIEW |
| | FOR FAIR HOUSING GUIDELINES PERTAINING TO COMMON |
| | ACCESSIBLE AREAS. CHAPTER 2 OF THE FAIR HOUSING |
| | GUIDELINE. |
| | |
| | 34G) A-3.41 SOCIAL DECK- PLANS ARE INCOMPLETE AS TO THE |
| | BAR AND GRILL AREA. THE PLANS DO NOT PROVIDE ANY |
| | ELEMENTS TO REVIEW FOR FAIR HOUSING GUIDELINES |
| | PERTAINING TO COMMON ACCESSIBLE AREAS. CHAPTER 2 OF THE |
| | FAIR HOUSING GUIDELINE. |
| | |
| | 35) PLEASE PROVIDE THE DETAILS FOR COMPLIANCE FOR |
| | ELEVATOR CARS TOACCOMMODATE AMBULANCE |
| | STRETCHERS.3002.4. |
| | 36) THE 500 SERIES ARCHITECTURAL SHEETS FOR STAIRWELLS |
| | FAIL TO PROVIDE DETAILS FOR A STANDPIPE, PLEASE PROVIDE |
| | COMPLIANCE WITH:905.1 GENERAL STANDPIPE SYSTEMS SHALL |
| | BE PROVIDED IN ALL NEW BUILDINGS IN WHICH: |
| | 1.THE HIGHEST FLOOR IS GREATER THAN 30 FEET (9144 |
| | MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE |
| | ACCESS; OR |
| | 2.THE HIGHEST FLOOR IS MORE THAN THREE STORIES |
| | ABOVE GRADE; OR |
| | 3.THE LOWEST FLOOR IS MORE THAN ONE STORY BELOW |
| | GRADE; OR |
| | 4.THE LOWEST FLOOR IS MORE THAN 20 FEET (6.1 M) |
| | BELOW GRADE. |
| | |
| | 37)THE INDEX SHEET DOES NOT INDICATE THE PRESENCE OF |
| | FIRE SPRINKLERS.903.2.7 GROUP R |
| | AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE |
| | WITH SECTION 903.3 SHALL BE PROVIDED THROUGHOUT ALL |
| | BUILDINGS WITH A GROUP R FIRE AREA. |
| | 903.6.1 ANY BUILDING WHICH IS OF THREE STORIES OR MORE |
| | IN HEIGHT SHALL BE EQUIPPED WITH AN APPROVED AUTOMATIC |
| | SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION |
| | 903.1 . |
| | |
| | 38) SHEET S).1 |
| | 38A) PLEASE UPDATE THE FBC BASE CODE TO ACCOMPANY THE |
| | 2007 SUPPLEMENTS TO THE FBC BUILDING. |
| | |
| | 38B) WIND LOADS ARE INDICATED AS FROM VARYING MEAN ROOF |
| | HEIGHTS, PLEASE SEE THERE CAN ONLY BE ONE MEAN ROOF |
| | HEIGHT OF THE BUILDING, SEE DEFINITIONS FOR MEAN ROOF |
| | HEIGHT. IN AS SUCH THE BUILDING MEAN ROOF HEIGHT |
| | (HIGHEST ROOF) WILL BE USED FOR THE NEGATIVE PRESSURES |
| | ON THE BUILDING. THE POSITIVE PRESSURES DO BUILD FROM |
| | THE GRADE AND BUILD AS THE HEIGHT OF THE BUILDING |
| | INCREASES. |
| | |
| | 39) S1.1B PLEASE PROVIDE ADDITIONAL INFORMATION AS TO |
| | THE SHEET PILE LOCATED ON THIS SHEET. |
| | PLANS INDICATE SHEET PILE BY OTHERS. PLEASE PROVIDE |
| | INFORMATION 106.1.2. 1808.2.21 PIER OR PILE LOCATION |
| | PLAN. A PLAN SHOWING THE LOCATION AND DESIGNATION OF |
| | PIERS OR PILES BY AN IDENTIFICATION SYSTEM SHALL BE |
| | FILED WITH THE BUILDING OFFICIAL PRIOR TO INSTALLATION |
| | OF SUCH PIERS OR PILES. DETAILED RECORDS FOR PIERS OR |
| | INDIVIDUAL PILES SHALL BEAR AN IDENTIFICATION |
| | CORRESPONDING TO THAT SHOWN ON THE PLAN. |
| | |
| | 40) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE |
| | DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2.GLAZED OPENINGS LOCATED |
| | MORE THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE |
| | PROVISIONS OF THE SMALL MISSILE TEST. |
| | |
| | 41)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, |
| | 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING |
| | REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| | A) FIXED GLASS |
| | B) STOREFRONT |
| | C) OPERABLE WINDOWS |
| | D) MULLIONS |
| | E) GLAZED SWING DOORS SINGLE AND PAIRS |
| | F) GLAZED DOORS W EITHER SIDELIGHTS AND OR TRANSOMS |
| | NOTE PRODUCT APPROVAL MAY OR MAY |
| | NOT INCLUDE MULLIONS |
| | F) GLAZED AUTOMATIC BYPASS DOORS |
| | G) EXTERIOR METAL EXTERIOR DOORS |
| | H)OVERHEAD GARAGE DOORS |
| | I) LOUVERS |
| | J) EFIS WALL SYSTEMS |
| | K) ROOF TOP A/C PRE-ENGINEERED STANDS |
| | L) WOOD CONNECTORS AND ANCHORS |
| | M) ROOFING ASSEMBLIES |
| | |
| | 42)PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 43) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 44) 1714.5.5 MULLIONS OCCURRING BETWEEN INDIVIDUAL |
| | WINDOW AND GLASS DOOR ASSEMBLIES. 1714.5.5.1 MULLIONS. |
| | MULLIONS, OTHER THAN MULLIONS WHICH ARE AN INTEGRAL |
| | PART OF A WINDOW OR GLASS DOOR ASSEMBLY TESTED AND |
| | LABELED IN ACCORDANCE WITH SECTION 1714.5.2.1 , SHALL |
| | BE TESTED BY AN APPROVED TESTING LABORATORY OR BE |
| | ENGINEERED IN ACCORDANCE WITH ACCEPTED ENGINEERING |
| | PRACTICE. BOTH METHODS SHALL USE PERFORMANCE CRITERIA |
| | CITED IN SECTIONS 1714.5.5.2 , 1714.5.5.3 AND |
| | 1714.5.5.4 . |
| | |
| | 45)THE PRODUCT APPROVALS NOW REQUIRE MULLIONS TO BE |
| | ATTACHED TO THE STRUCTURE. |
| | 1714.5.5.2 LOAD TRANSFER. MULLIONS SHALL BE DESIGNED TO |
| | TRANSFER THE DESIGN PRESSURE LOADS APPLIED BY THE |
| | WINDOW AND DOOR ASSEMBLIES TO THE ROUGH OPENING |
| | SUBSTRATE. |
| | 1714.5.5.4 STRUCTURAL SAFETY FACTOR. |
| | MULLIONS SHALL BE CAPABLE OF RESISTING A LOAD OF |
| | ONE-AND-ONE-HALF TIMES THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW AND DOOR ASSEMBLIES TO BE |
| | SUPPORTED WITHOUT EXCEEDING THE APPROPRIATE MATERIAL |
| | STRESS LEVELS. IF TESTED BY AN APPROVED LABORATORY, THE |
| | ONE AND ONE-HALF TIMES THE DESIGN PRESSURE LOAD SHALL |
| | BE SUSTAINED FOR 10 SECONDS, AND THE PERMANENT |
| | DEFORMATION SHALL NOT EXCEED 0.4 PERCENT OF THE MULLION |
| | SPAN AFTER THE ONE-AND-ONE-HALF TIMES DESIGN PRESSURE |
| | LOAD IS REMOVED. |
| | |
| | 46) SHEET A-8.01 DETAIL# 19 INDICATES A WOOD BUCK WITH |
| | A BEVELED SIDE, PLEASE SEE 1714.5.4.2BUCKS SHALL |
| | EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW OR DOOR |
| | FRAME SUCH THAT FULL SUPPORT OF THE FRAME IS PROVIDED. |
| | SHIMS SHALL BE MADE FROM MATERIALS CAPABLE OF |
| | SUSTAINING APPLICABLE LOADS, LOCATED AND APPLIED IN A |
| | THICKNESS CAPABLE OF SUSTAINING APPLICABLE LOADS. |
| | ANCHORS SHALL BE PROVIDED TO TRANSFER LOAD FROM THE |
| | WINDOW OR DOOR FRAME ASSEMBLY TO THE SECURED WOOD BUCK. |
| | |
| | |
| | |
| | 47)BEFORE ISSUANCE OF A PERMIT THE CONTRACTOR WILL |
| | NEED TO SUPPLY THE FOLLOWING INFORMATION FOR A BUILDING |
| | (ROOF) PERMIT.THIS ROOF IS MISSING OR NOT IN |
| | COMPLIANCE WITH THE FOLLOW ITEMS: |
| | ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. |
| | ___ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO |
| | BE USED. |
| | ___ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE |
| | _2&3__ . |
| | ___ THE SYSTEM PROVIDED STATESLIMITATION# 7, |
| | SHOULD THE FASTENERRESISTANCE BE LESS THAN THAT |
| | REQUIRED, AS DETERMINED BY THE BUILDING OFFICIAL, A |
| | REVISEDFASTENER SPACING, PREPARED , SIGNED AND SEALED |
| | BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER, |
| | REGISTERED |
| | ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE |
| | SUBMITTED. |
| | ___ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO |
| | ENHANCED FASTENING ALLOWED. |
| | |
| | 48)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |