| 2007-12-23 14:02:01 | ** DENIEDREVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE |
| | NEEDED AS FOLLOWS: |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SUBMIT COMPLETE PLANS FOR ALL MINIMUM |
| | CODE COMPLIANCE. |
| | PLEASE SUBMIT PANEL SCHEDULE SHOWING ALL CONDUCTORS, |
| | BRANCH CIRCUITS AND BREAKERS. |
| | PLEASE SUBMIT RISER DIAGRAM SHOWING ALL CONDUCTORS, |
| | OVER CURRENT PROTECTION, MAINS, GROUNDING ETC |
| | PLEASE SEENEC/ NFPA-70 408.4, 240.4, 310.16 ETC. |
| | PLEASE SHOW ALL MINIMUM CIRCUITS AS REQUIRED PER |
| | 210.52, 210.11, 220. |
| | PLEASE SUBMIT LOAD CALCULATIONS FOR NEW AND |
| | EXISTING.220.87 |
| | PLEASE SHOW ALL AFCI PROTECTED CIRCUITS PER 210.12. |
| | PLEASE SEE FBC R313 FOR REQUIRED SMOKE ALARMS DEVICES |
| | PLEASE COMPLETE THE SW LEGS FOR COMPLETION OF EGRESS |
| | LIGHTING CONTROLS PER 210.70,LS 101 7.8. |
| | PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS FOR NEW |
| | TANK-LESS WATER HEATER UNIT.90.7, 110.3 |
| | PLEASE SUBMIT COMPLETED PLANS. PLEASE KNOW PLANS ARE |
| | BEING ROUTED TO ZONING TO CONFIRM USE AS SHOWN. |
| | |
| | |
| | |
| | *** AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR |
| | REVIEW, THERE MAY BE NEW COMMENTS ON THE FOLLOWING |
| | REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |