Plan Review Notes
Plan Review Notes For Permit 07120233
Permit Number 07120233
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-23 14:02:01** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE
 NEEDED AS FOLLOWS:
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SUBMIT COMPLETE PLANS FOR ALL MINIMUM
 CODE COMPLIANCE.
 PLEASE SUBMIT PANEL SCHEDULE SHOWING ALL CONDUCTORS,
 BRANCH CIRCUITS AND BREAKERS.
 PLEASE SUBMIT RISER DIAGRAM SHOWING ALL CONDUCTORS,
 OVER CURRENT PROTECTION, MAINS, GROUNDING ETC
 PLEASE SEENEC/ NFPA-70 408.4, 240.4, 310.16 ETC.
 PLEASE SHOW ALL MINIMUM CIRCUITS AS REQUIRED PER
 210.52, 210.11, 220.
 PLEASE SUBMIT LOAD CALCULATIONS FOR NEW AND
 EXISTING.220.87
 PLEASE SHOW ALL AFCI PROTECTED CIRCUITS PER 210.12.
 PLEASE SEE FBC R313 FOR REQUIRED SMOKE ALARMS DEVICES
 PLEASE COMPLETE THE SW LEGS FOR COMPLETION OF EGRESS
 LIGHTING CONTROLS PER 210.70,LS 101 7.8.
 PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS FOR NEW
 TANK-LESS WATER HEATER UNIT.90.7, 110.3
 PLEASE SUBMIT COMPLETED PLANS. PLEASE KNOW PLANS ARE
 BEING ROUTED TO ZONING TO CONFIRM USE AS SHOWN.
  
  
  
 *** AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR
 REVIEW, THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]