| 2008-11-21 09:29:09 | |
| | |
| | |
| | ** FAILED REVISION ** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE ITEM REDLINED ON ISSUED PLANS FROM |
| | 1/28/08 THE 2005 NEC WAS REVISED TO REQUIRE ALL |
| | RECEPTACLES IN LAUNDRY ROOMS TO BE GFI/GFI PROTECTED |
| | WITHIN 6FT OF THE LAUNDRY SINK EVEN IF THESE ARE |
| | DEDICATED RECEPTACLES. |
| | THE PLANS WERE REDLINED FOR THE IRONING BOARD |
| | RECEPTACLE TO MEET 210.8A7 |
| | |
| | 2) NOTE: PLEASE LIST/IDENTIFY THE ARC FAULT BREAKERS ON |
| | PANEL SCHEDULES. |
| | 210.12,408.4 |
| | |
| | 3) NOTE: PLEASE VERIFY THE CONDUITS FROM METER TO |
| | MAINS. ARE THESE OVERHEAD AS SHOWN ON RISER OR |
| | UNDERGROUND? |
| | IF OVER HEAD THEN OCP IS REQUIRED ON THE OUTSIDE. |
| | IF IN SLAB PLEASE SHOW. |
| | 230.70 |
| | |
| | 4) NOTE: PLEASE SEE 210.11C2, 220.52 |
| | |
| | 5) NOTE: PLEASE SEE THE INCORRECT NFPA-72 IS STATED ON |
| | PLANS. SHOWS 2005 AND NEEDS TO 2002. THIS WAS REDLINED |
| | ON ORIGINAL PLANS. |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |