| 2007-12-31 09:49:56 | |
| | DENIED |
| | |
| | |
| | 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL |
| | COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 |
| | AMENDMENTS PER 106.1.1 FBC* |
| | |
| | 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC* |
| | |
| | 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON |
| | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER |
| | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE |
| | ADDED TO THE PERMIT APPLICATION FEES |
| | |
| | NOTE: FEES ARE DUE IN THE AMOUNT OF $3,782.59 FOR |
| | REMAINING FEES, INCREASED VALUE AND STATE RADON FEES |
| | THIS AMOUNT IS REQUIRED TO BE PAID PRIOR TO FURTHER |
| | PLAN REVIEW |
| | |
| | 4)SURVEY AND SITE PLAN SIDE AND REAR SETBACK |
| | MEASUREMENTS DO NOT MATCH EACH OTHER |
| | |
| | 5)PROVIDE CORRECT PROJECT ADDRESS ON THE DRAWINGS |
| | (USE OF LABEL IS ACCEPTABLE), ALSO CLARIFY BUILDER AND |
| | OWNER INFORMATION ON ENERGY CALC'S THEY STATE KOLTER |
| | HOMES AS THE BUILDER |
| | |
| | 6)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA |
| | STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE. |
| | THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG. |
| | WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE |
| | DENIED |
| | |
| | 7) SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT |
| | COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR |
| | BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND |
| | APPROVED BY THE DESIGNER OF RECORD ***PLEASE NOTE THAT |
| | FLORIDA SHEETS WERE NOT SUBMITTED FOR PGT AND WAYNE |
| | DALTON PRODUCTS AND THE FL#'S ARE WRITTEN AT THE TOP OF |
| | THESE PRODUCT NOA'S*** |
| | |
| | 8)PRODUCT APPROVALS WERE NOT SUBMITTED FOR MULLIONS |
| | THAT WILL BE USED ON SEVERAL DOOR AND WINDOW |
| | INSTALLATIONS, ALSO PRODUCT APPROVAL FOR CASEMENT |
| | WINDOWS WERE SUBMITTED BUT NONE ARE PRESENT ON THE |
| | DRAWINGS, PLEASE CLARIFY |
| | |
| | 9)THE FIXED WINDOW IN THE DINING ROOM AREA IS 51 SQ |
| | FT. AND EXCEEDS THE MAX ALLOWABLE SIZE OF 30.28 SQ FT. |
| | IN THE FIXED WINDOW PRODUCT APPROVAL |
| | |
| | 10)CORRECT SECTION AND COLUMN DESIGNATIONS ON SHEETS |
| | A/2 AND A/3 THAT REFER TO A SHEET 7 AND THAT ALSO HAVE |
| | DETAIL AND SHEET NUMBERS REVERSED |
| | |
| | 11)CLARIFYFOUNDATIONFOR SCREEN WALL, SCHEDULE ON |
| | A/2 STATES 12" X 24" FOOTING AND DETAIL OFBLOCK PIERS |
| | ON SHEET A/5 SHOWS 30" X 30" PAD |
| | |
| | 12)CLARIFY SECTION J-6 ON SHEET A/2 AT GARAGE WALL |
| | WITH DETAIL ON A/6 |
| | |
| | 13)CLARIFY DETAILS FOR FRAMED WALLS FROM MAIN ROOF AT |
| | FRONT PORCH TO RAISED ROOF, ARE THESEDETAILS J-6, O-6 |
| | AND N-6 IF SO SHOW THEORIENTATION OF SECTIONS ON THE |
| | FLOOR OR ROOF PLAN. SHOW THAT BEAM ABOVE IS FRAMED INTO |
| | ENTIRE PERIMETER WALL AS SHOWN ON ROOF FRAMING PLAN AND |
| | IS IT BOXED OUT ON THE INSIDE ALL THE WAY AROUND AS |
| | STATED ON SAME PLAN |
| | |
| | 14)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS |
| | OF NEW DRAWINGS WITH REVISIONS AND INCLUDE 1 COPY OF |
| | THE OLD PAGES ONLY FOR REFERENCE. PLEASE RE-SUBMIT ANY |
| | PAGES WITH THE IMPACT FEE STAMP |
| | |
| | 15)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO |
| | A PERMIT BEING ISSUED |
| | |
| | NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006 |
| | AMENDMENTS |
| | FBC* = WEST PALM BEACH ADMINISTRATIVE |
| | AMENDMENTS TO FBC |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | FBC RES. = FLORIDA BUILDING CODE |
| | RESIDENTIAL 2004 W/2006 AMENDMENTS |
| | |