| Plan Review Notes For Permit 07120219 |
| Permit Number |
07120219 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-12-18 17:31:08 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | PREVIOUS LIST: | | | | | | 1.)TWO DIFFERENT ASSEMBLIES WERE SELECTED (PAGE 33, | | | PAGE 34).ENHANCED FASTENING WHICH YOU HAVE SPECIFIED, | | | 4" OC, IS NOT COMPLIANT FOR FASTENING 2 ON EITHER | | | SYSTEM.PLEASE INDICATE WHICH FASTENER YOU ARE USING | | | (MUST BE FASTENING #1 FOR SYSTEM E2 FOR 2 FIELD ROWS | | | 4"OC), SELECT ANOTHER SYSTEM, OR SPECIFY ADDITIONAL | | | ROWS FOR ENHANCED FASTENING. | | | | | | CONTRACTOR SELECTED SYSTEM 2.THERE ARE STILL TWO | | | DIFFERENT ASSEMBLIES IN THE PACKAGE.PLEASE CHOOSE | | | ONLY ONE ASSEMBLY.SPECIFY ENHANCED FASTENING FOR | | | ZONES 2 AND 3.YOU HAD SPECIFIED 4" OC, BUT THIS WAS | | | CROSSED OFF.THIS IS NOT COMPLIANT FOR THE ASSEMBLY | | | YOU HAVE SELECTED.PLEASE SPECIFY ENHANCED FASTENING. | | | |
|