Plan Review Notes
Plan Review Notes For Permit 07120191
Permit Number 07120191
Review Stop B
Sequence Number 3
Notes
Date Text
2008-07-11 09:52:51THE POOL SPECIFICATIONS HAS TO REFLECT THE NEW CHANGES
 MADE THO THE POOL AND SPA. THE SPECIFICATION OS SHEET
 #2 HAS THE SAME INFORMATION BEFORE THE CHANGES WERE
 MADE.
  
 NOTE: POOL DECKS SHALL BE UNIFORMILY SLOPED AT A
 MINIMUM OF 2 PERCENT TO A MAXIMUM OF 4 PERCENT AWAY
 FROM THE POOL OR TH DECK DRAINS TO PREVENT STANDING
 WATER. FBC 424.1.3.1.2
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER