| Plan Review Notes For Permit 07120191 |
| Permit Number |
07120191 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-13 15:14:28 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1) FBC-2004 SEC. 424.2.14.1, OR | | | FBCR-2004 SEC. R4101.14.1 SWIMMING POOL | | | WATER HEATERS SHALL BEAR THE LABEL OF A | | | RECOGNIZED TESTING AGENCY. (MANUFACTURE | | | SHEETS REQUIRED, PLEASE SUBMIT) | | | | | | 2) FBC-2004 SEC. 424.2.14.2, OR | | | FBCR-2004 SEC. R4101.14.2 WATER | | | RETENTION, PROVIDE A POSITIVE MEANS OF | | | RETAINING WATER IN THE HEATER WHEN PUMP | | | IS SHUT OFF.(MANUFACTURE SHEETS | | | REQUIRED, PLEASE SUBMIT) | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|