Plan Review Notes
Plan Review Notes For Permit 07120185
Permit Number 07120185
Review Stop E
Sequence Number 4
Notes
Date Text
2008-07-03 15:51:05 
  
 ** DENIED **
  
 1) NOTE:PLEASE SEE THE ELECTRICAL PLANS WHICH WERE
 PREVIOUSLY STAMPED AND PASSED ARE NOW COMPLETELY
 REVISED. NEW LIGHTING/WATTAGES ETC WHICH HAS BEEN
 CHANGED DID NOT INCLUDE REVISED ENERGY CALCULATIONS.
 PLEASE SEE THE PREVIOUS STAMPED ENERGY CALCULATIONS
 HAVE NOW BEEN VOIDED. WE ARE NOT ABLE TO REVIEW AT THIS
 TIME.
 PREVIOUS CALCULATIONS INDICATED 175W FIXTURES NOW PLANS
 HAVE BEEN REVISED TO SHOW 400W FIXTURES.
 PLEASE REVISE AND SUBMIT.
 FBC 13-415.2, 13-415.2.ABC.1.1, .1.2, .1.3. 13-400.3.B
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]