| Date |
Text |
| 2008-07-03 15:51:05 | |
| | |
| | ** DENIED ** |
| | |
| | 1) NOTE:PLEASE SEE THE ELECTRICAL PLANS WHICH WERE |
| | PREVIOUSLY STAMPED AND PASSED ARE NOW COMPLETELY |
| | REVISED. NEW LIGHTING/WATTAGES ETC WHICH HAS BEEN |
| | CHANGED DID NOT INCLUDE REVISED ENERGY CALCULATIONS. |
| | PLEASE SEE THE PREVIOUS STAMPED ENERGY CALCULATIONS |
| | HAVE NOW BEEN VOIDED. WE ARE NOT ABLE TO REVIEW AT THIS |
| | TIME. |
| | PREVIOUS CALCULATIONS INDICATED 175W FIXTURES NOW PLANS |
| | HAVE BEEN REVISED TO SHOW 400W FIXTURES. |
| | PLEASE REVISE AND SUBMIT. |
| | FBC 13-415.2, 13-415.2.ABC.1.1, .1.2, .1.3. 13-400.3.B |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |