2007-12-19 17:03:44DENIED
 REFERENCE: FBC - 2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT ME1 SUBMIT ISOMETRIC RISER DIAGRAMS FOR THE
 SANITARY, WATER & STORM SYSTEMS. SHOW ALL PIPE SIZES,
 TRAPS, CLEANOUTS, VENTS FOR SANITARY. SHOW ALL PIPE
 SIZES, VALVES, RPZV BACKFLOW REQUIRED ON THE WATER
 SERVICE, ETC. FOR THE WATER SYSTEM. SHOW ALL PIPE SIZES
 & CLEANOUTS REQUIRED FOR THE STORM. TABLE 604.5.
 SECTIONS 106.3.5.1.3, 606.1, 606.2, 608.13.8. TABLES
 709.1, 710.1(1), 916.1, 1101.8.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  