| Plan Review Notes For Permit 07120185 |
| Permit Number |
07120185 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-31 11:03:45 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) PLEASE ADD TO THE ENERGY CALCULATIONS ADDENDUM THE | | | A/C SYSTEMS WITH SIZE AND SEER THAT MAY BE INSTALLED IN | | | THE FUTURE, SEE 2004 FBC 13-101.1.6 | | | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 3) PLEASE BE AWARE AND MAKE ANY NEEDED CHANGES TO BE | | | CERTAIN THE EXHAUST DUCTS AND VENT PIPES WILL NOT BE | | | WITHIN 10 FEET OF THE A/C UNITS FRESH-AIR INLETS, SEE | | | 2004 FBC 401.5.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|