Plan Review Notes For Permit 07120185
Permit Number 07120185
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-12 16:58:30 
 ** DENIED **
  
 ** APPLIED SHELL FOR FUTURE RETAIL.
  
  
 1) NOTE: PLEASE BE SURE THE ELECTRICAL SHEETS CONTAIN
 THE RELEVANT CODES FOR DESIGN. PLEASE LIST THE
 FOLLOWING.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE BE SURE THE APPLIED ADDRESS AND
 LOCATION IS LISTED IN TITLE BLOCKS. APPLIED ADDRESS FOR
 THIS LOCATION IS 8196 OKEECHOBEE BLVD.
 FAC 61G15-23.002, FBC 106.5, 106.1.2
  
 3) NOTE: PLEASE CLARIFY CONTINUOUS LOADS ARE SHOWN AT
 125% OR ALREADY FIGURED INTO CALCULATIONS FOR HOUSE PER
 215.3, 230.42
  
 4) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED CONTAIN AN ADDENDUM TO THE CALCULATIONS.
 PLEASE KNOW THAT ANY CHANGES TO THE REPORT MUST BE
 INCLUDED IN THE FLA-COM PROGRAM.
 PLEASE BE SURE TO COORDINATE ALL ELECTRICAL LIGHTING ON
 PLANS WITH THAT OF THE LIGHTING IN THE INPUT DATA
 REPORTS.
 PLEASE COMPLETE FIXTURE LEGEND WITH INFORMATION FOR
 FIXTURE *B*. DOES NOT SHOW TYPE, WATTAGE ETC.
 PLEASE CLARIFY WHERE SITE LIGHTING IS BEING FED FROM.
 PLANS SUBMITTED SHOWS SITE LIGHTING (NOT BY CHANE
 ENGINEERING) YET NEITHER SHELL BUILDING ELECTRICAL
 PLANS/ENERGY CALCULATIONS SUBMITTED UNDER THIS PERMIT
 OR 07120184 HAVE THESE SHOWN.
 PLEASE BE SURE TO MAKE ADJUSTMENTS.
 THE INTERIOR LIGHTING ON THE IDR IS ASSUMPTIONS AT THIS
 TIME.
 13-415.2, 13-415.B.1
  
 5) NOTE: PLEASE BE SURE TO ADD NOTES ON PLANS FOR
 13-413.1.ABC.1.1 AND .2.2. (PART OF THIS SEEMS TO BE ON
 ME2 HOWEVER PART OF THE NOTE IS UNCLEAR)
  
 6) NOTE: PLEASE BE SURE THE OWNER AGENT IS SIGNED ON
 THE CERTIFICATION SHEETS ON THE ENERGY CALCULATIONS.
 PLEAS ALSO BE SURE THE ENGINEER SIGNS, DATES AND SEALS
 THE CERTIFICATION SHEET. (PAGE 3).
 13-103.1.1.1, FS 471.025
  
 7) NOTE: PLEASE CLARIFY LOCATIONS FOR A/C DISCONNECTS
 REQUIRED PER 440.11.
  
 8) NOTE: PLEASE SEE POSSIBLE COMMENTS FOR THE APPLIED
 VALUE AS THE VALUE SEEMS LOW PER FBC 108.3.
 THE APPLIED VALUE IS TO INCLUDE ALL LABOR, MATERIALS,
 EQUIPMENT, DESIGN COST, EVEN IF ANY OF THESE ITEMS ARE
 OWNER SUPPLIED.
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES.
  
  
  
  
 ** PLEASE KNOW AS THERE IS SOME INFORMATION NOT YET
 SUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS ON THE
 FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-12-12 12:57:561-SETOF PLANS IN ELECTRICAL FOR REVIEW.