| 2007-12-12 16:58:30 | |
| | ** DENIED ** |
| | |
| | ** APPLIED SHELL FOR FUTURE RETAIL. |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE THE ELECTRICAL SHEETS CONTAIN |
| | THE RELEVANT CODES FOR DESIGN. PLEASE LIST THE |
| | FOLLOWING. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE BE SURE THE APPLIED ADDRESS AND |
| | LOCATION IS LISTED IN TITLE BLOCKS. APPLIED ADDRESS FOR |
| | THIS LOCATION IS 8196 OKEECHOBEE BLVD. |
| | FAC 61G15-23.002, FBC 106.5, 106.1.2 |
| | |
| | 3) NOTE: PLEASE CLARIFY CONTINUOUS LOADS ARE SHOWN AT |
| | 125% OR ALREADY FIGURED INTO CALCULATIONS FOR HOUSE PER |
| | 215.3, 230.42 |
| | |
| | 4) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS |
| | SUBMITTED CONTAIN AN ADDENDUM TO THE CALCULATIONS. |
| | PLEASE KNOW THAT ANY CHANGES TO THE REPORT MUST BE |
| | INCLUDED IN THE FLA-COM PROGRAM. |
| | PLEASE BE SURE TO COORDINATE ALL ELECTRICAL LIGHTING ON |
| | PLANS WITH THAT OF THE LIGHTING IN THE INPUT DATA |
| | REPORTS. |
| | PLEASE COMPLETE FIXTURE LEGEND WITH INFORMATION FOR |
| | FIXTURE *B*. DOES NOT SHOW TYPE, WATTAGE ETC. |
| | PLEASE CLARIFY WHERE SITE LIGHTING IS BEING FED FROM. |
| | PLANS SUBMITTED SHOWS SITE LIGHTING (NOT BY CHANE |
| | ENGINEERING) YET NEITHER SHELL BUILDING ELECTRICAL |
| | PLANS/ENERGY CALCULATIONS SUBMITTED UNDER THIS PERMIT |
| | OR 07120184 HAVE THESE SHOWN. |
| | PLEASE BE SURE TO MAKE ADJUSTMENTS. |
| | THE INTERIOR LIGHTING ON THE IDR IS ASSUMPTIONS AT THIS |
| | TIME. |
| | 13-415.2, 13-415.B.1 |
| | |
| | 5) NOTE: PLEASE BE SURE TO ADD NOTES ON PLANS FOR |
| | 13-413.1.ABC.1.1 AND .2.2. (PART OF THIS SEEMS TO BE ON |
| | ME2 HOWEVER PART OF THE NOTE IS UNCLEAR) |
| | |
| | 6) NOTE: PLEASE BE SURE THE OWNER AGENT IS SIGNED ON |
| | THE CERTIFICATION SHEETS ON THE ENERGY CALCULATIONS. |
| | PLEAS ALSO BE SURE THE ENGINEER SIGNS, DATES AND SEALS |
| | THE CERTIFICATION SHEET. (PAGE 3). |
| | 13-103.1.1.1, FS 471.025 |
| | |
| | 7) NOTE: PLEASE CLARIFY LOCATIONS FOR A/C DISCONNECTS |
| | REQUIRED PER 440.11. |
| | |
| | 8) NOTE: PLEASE SEE POSSIBLE COMMENTS FOR THE APPLIED |
| | VALUE AS THE VALUE SEEMS LOW PER FBC 108.3. |
| | THE APPLIED VALUE IS TO INCLUDE ALL LABOR, MATERIALS, |
| | EQUIPMENT, DESIGN COST, EVEN IF ANY OF THESE ITEMS ARE |
| | OWNER SUPPLIED. |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES. |
| | |
| | |
| | |
| | |
| | ** PLEASE KNOW AS THERE IS SOME INFORMATION NOT YET |
| | SUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS ON THE |
| | FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |