| Date |
Text |
| 2008-03-05 20:42:31 | 2008-03-05 20:42:31 |
| | |
| | ** DENIED2ND REVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE FBC 13-400.3.B AS THIS REQUIRES |
| | VERSION 2.5. IT WAS CONFIRMED WITH THE FLORIDA BUILDING |
| | COMMISSION/ DEPARTMENT OF COMMUNITY AFFAIRS THAT 3.0 IS |
| | NOT PERMITTED AND ONLY THE ADOPTED 2.5 MAY BE USED. |
| | THIS IS STILL PENDING REVIEW AND COORDINATION FROM |
| | OTHER TRADES FOR ENERGY CALCULATIONS. |
| | PLEASE SEE PREVIOUS REVIEW WHICH REQUESTED THE OWNER |
| | AGENT SIGN CALCULATIONS AS REQUIRED ON CERTIFICATION |
| | SHEETS. |
| | PLEASE ALSO BE SURE THE ENGINEER OF RECORD SIGNS AND |
| | SEALS THESE SAME SHEETS. 13-103.1.1.1, FS 471.025. |
| | (ENGINEER DID SEAL, SIGN COVER) |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |