| 2007-12-19 18:08:49 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT ME1 SUBMIT A STORM ISOMETRIC RISER DIAGRAM |
| | SHOWING ALL PIPE SIZES, OFFSETS, AND CLEANOUTS REQUIRED |
| | BY SECTIONS 106.3.5.1.3, 1101.8, 1106 & 1107 & TABLE |
| | 1106.3. |
| | |
| | 2. IF THE GREASE INTERCEPTOR WILL BE INSTALLED AT THE |
| | TIME OF THE SHELL, THE INTERCEPTOR SHALL BE SIZED BY |
| | THE UTILITY DEPT., INDUSTRIAL PRETREATMENT, |
| | ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO, |
| | (561) 822-2272, E-MAIL [email protected], OR CALVIN |
| | WILLIAMS, (561) 822-2284, E-MAIL [email protected]. |
| | THEY WILL GIVE YOU A WRITTEN DETERMINATION AS TO THE |
| | SIZE OF THE GREASE INTERCEPTOR REQUIRED. ARTICLE III |
| | SECTION 90-124(7)(F). PLEASE CLARIFY WHEN THE GREASE |
| | INTERCEPTOR WILL BE INSTALLED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |