Date Text
2007-12-19 18:08:49DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT ME1 SUBMIT A STORM ISOMETRIC RISER DIAGRAM
 SHOWING ALL PIPE SIZES, OFFSETS, AND CLEANOUTS REQUIRED
 BY SECTIONS 106.3.5.1.3, 1101.8, 1106 & 1107 & TABLE
 1106.3.
  
 2. IF THE GREASE INTERCEPTOR WILL BE INSTALLED AT THE
 TIME OF THE SHELL, THE INTERCEPTOR SHALL BE SIZED BY
 THE UTILITY DEPT., INDUSTRIAL PRETREATMENT,
 ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO,
 (561) 822-2272, E-MAIL [email protected], OR CALVIN
 WILLIAMS, (561) 822-2284, E-MAIL [email protected].
 THEY WILL GIVE YOU A WRITTEN DETERMINATION AS TO THE
 SIZE OF THE GREASE INTERCEPTOR REQUIRED. ARTICLE III
 SECTION 90-124(7)(F). PLEASE CLARIFY WHEN THE GREASE
 INTERCEPTOR WILL BE INSTALLED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  